Kontak Kami

KONTAK KAMI : Telpon : 02126071413 Hp/WhatsApp : 081212269831 Perwakilan Jakarta : Gedung LTC Glodok Lantai 1 Blok C30 No.31 Jl.Hayam Wuruk No.127 Jakarta , Indonesia

Rabu, 25 Mei 2016

CJ-series B7A Interface Unit CJ1W-B7A


It transmits 16 points of I/O signals per word with a pair of cables. Easy and minimized wiring effort. This unit is available for CJ/NJ controller.

A CJ1W-B7A unit can transmit 64 points of I/O signals.
The slim body can downsize machines to which CJ1W-B7A is connected.
It is a basic I/O unit. No complicated setting and programs are required.

International Standards

  • The standards are abbreviated as follows: U: UL, U1: UL (Class I Division 2 Products for Hazardous Locations), C: CSA, UC: cULus, UC1: cULus (Class I Division 2 Products for Hazardous Locations), CU: cUL, N: NK, L: Lloyd, and CE: EC Directives.
  • Contact your OMRON representative for further details and applicable conditions for these standards.
Unit
type
NameSpecificationsNo. of
words
allocated
Current
consumption (A)
ModelStandards
I/O pointsExternal
connection
5 V24 V
CJ1
Basic
I/O
Units
B7A
Interface
Units
64 inputsRemovable
terminal block
4 words0.07---CJ1W-B7A14UC1, CE
64 outputs0.07---CJ1W-B7A04
32 inputs/
outputs
0.07---CJ1W-B7A22

B7A Communications Specifications

ItemSpecifications
Transmission methodOne-way time-sharing multiplex transmissions
Transmission delay
(communications delay
on transmission path)
High-speed3 ms typical, 5 ms max.
Standard19.2 ms typical, 31 ms max.
Transmission pointsCJ1W-B7A1464 inputs (4 ports)
CJ1W-B7A0464 outputs (4 ports)
CJ1W-B7A2232 inputs (2 ports), 32 outputs (2 ports)
External power supply
voltage *1
12 to 24 V DC (allowable voltage range: 10.8 to 26.4 V)
External supply
current *2
CJ1W-B7A1440 mA min.
CJ1W-B7A04150 mA min.
CJ1W-B7A2280 mA min.
Minimum input time
*3
High-speed16 ms
Standard2.4 ms
Transmission distanceHigh-speedPower supply on one side
(common power supply)
10 m max.
50 m max. (with shielded cable)
Power supply on both sides
(separate power supplies)
10 m max.
100 m max. (with shielded cable)
StandardPower supply on one side
(common power supply)
100 m max.
Power supply on both sides
(separate power supplies)
500 m max.
CablesVCTF, 0.75 mm2, 3 conductors (power supply on one side (common power supply))
VCTF, 0.75 mm2, 2 conductors (power supply on both sides (separate power supplies))
Shielded cable, 0.75 mm2, 3 conductors (power supply on one side (common power supply))
Shielded cable, 0.75 mm2, 2 conductors (power supply on both sides (separate power supplies))
Note: 1. When separate power supplies are used, the B7A Interface Unit and B7A Link Terminal are supplied by separate 
              external power supplies. 
           2. When a common power supply is used, the B7A Interface Unit and B7A Link Terminal are supplied by the same 
                external power supply. 
*1. We recommend OMRON S8[][]-series Power Supply Units for the external power supplies. 
*2. The capacity of the external supply current does not include the capacity required by the B7A Link Terminal. 
*3. The minimum input time is the minimum time required by the B7A Interface Unit to read the input signals from the 
       CPU Unit.

Specifications

ModeStandard modeHigh-speed mode
I/O pointsIN 32/OUT 32 (CJ1W-B7A22)
IN 64 (CJ1W-B7A14)
OUT 64 (CJ1W-B7A04)
Transmission methodOne-way time-sharing multiplex transmissions
Transmission distance500m max.100m max.
Transmission delay19.2ms (typical)3ms (typical)
Minimum input time16ms2.4ms
Power Supply voltage
(allowable voltage range)
12 to 24VDC (10.8 to 26.4VDC)
I/O memory AllocationsEach Unit is allocated 4 words in the I/O Area (which starts at CIO 0000). The words are allocated
according to the mounting position of the Unit.
Transmission error bitA transmission error bit for each input port is allocated in the Basic I/O Unit Information Area.
CableVCTF, 0.75mm2 recommended.

CJ1W-B7A14/04/22

CJ1W-B7A Dimensions 2 CJ1W-B7A14/04/22_Dim