International Standards
- The standards are abbreviated as follows: U: UL, U1: UL (Class I Division 2 Products for Hazardous Locations), C: CSA, UC: cULus, UC1: cULus (Class I Division 2 Products for Hazardous Locations), CU: cUL, N: NK, L: Lloyd, and CE: EC Directives.
- Contact your OMRON representative for further details and applicable conditions for these standards.
Unit type | Name | Specifications | No. of unit numbers allocated | Current con- sumption (A) | Model | Stand- ards | |||
---|---|---|---|---|---|---|---|---|---|
Communi- cations functions | No. of I/O points | Max. Units mountable per CPU Unit | 5 V | 24 V | |||||
CJ1 Special I/O Units | CompoBus/S Master Unit | Remote I/O communi- cations | 256 max. (128 inputs and 128 outputs) | 40 | 1 or 2 (variable) | 0.15 | --- | CJ1W-SRM21 | UC1, N, L, CE, |
128 max. (64 inputs and 64 outputs) |
Note: This unit cannot be used with the Machine Automation Controller NJ-series.
Communication Specifications
Item | Specification | |
---|---|---|
Communications method | Special CompoBus/S protocol | |
Communications baud rate | High-speed Communications Mode: 750 kbps Long-distance Communications Mode: 93.75 kbps | |
Modulation method | Baseband method | |
Coding method | Manchester coding method | |
Error control checks | Manchester code check, frame length check, and parity check | |
Cable | VCTF cable (JIS C 3306) | Two 0.75 mm2 conductors (2 signal wires) Four 0.75 mm2 conductors (2 signal wires and 2 power supply wires) |
Special Flat Cable | Four 0.75 mm2 conductors (2 signal wires and 2 power supply wires) | |
Commu- nications distance | 2-conductor VCTF cable | High-speed Communications Mode Main line length: 100 m max. Branch line length: 3 m max. Total branch line length: 50 m max. |
Long-distance Communications Mode Main line length: 500 m max. Branch line length: 6 m max. Total branch line length: 120 m max. | ||
4-conductor VCTF cable | High-speed Communications Mode Main line length: 30 m max. Branch line length: 3 m max. Total branch line length: 30 m max. | |
Long-distance Communications Mode: Flexibly branched, provided that the total length of cable is a maximum of 200 m. | ||
Special Flat Cable | High-speed Communications Mode Main line length: 30 m max. Branch line length: 3 m max. Total branch line length: 30 m max. When 4-conductor VCTF cable or Special Flat Cable is used to connect fewer than 16 Slaves, the main line can be up to 100 m long and the total branch line length can be up to 50 m in High-speed Communications Mode. | |
Long-distance Communications Mode: Flexibly branched, provided that the total length of cable is a maximum of 200 m. |
Specifications
I/O points | 256 (128 inputs and 128 outputs) or 128 (64 inputs and 64 outputs) (Switch- selectable) |
---|---|
Applicable PLC models | CJ-series PLCs |
Unit type | Special I/O Unit |
Allocated words * | For 256 I/O: 20 words (8 for inputs, 8 for outputs, 4 for status) For 128 I/O: 10 words (4 for inputs, 4 for outputs, 2 for status) |
No. of mountable Master Units | 40 |
Node address | 8 addresses per node |
No. of connectable Slaves | 32 |
Status information | Communications Error Flags, Participation Flags |
* Uses Special I/O Unit Area (in CIO Area).