International Standards
- The standards are abbreviated as follows: U: UL, U1: UL(Class I Division 2 Products for Hazardous Locations), C: CSA, UC: cULus, UC1: cULus (Class I Division 2 Products for Hazardous Locations), CU: cUL, N: NK, L: Lloyd, and CE: EC Directives.
- Contact your OMRON representative for further details and applicable conditions for these standards.
Name | Appear- ance | Specifications | Number of unit numbers allocated | Power consumption (A) | Model | Stand- ards | ||
---|---|---|---|---|---|---|---|---|
Type of communi- cations | Maximum number of I/O points per Master Unit | 5-V system | 24-V system | |||||
CJ1 Special I/O Unit | Remote I/O communica- tions Message communica- tions | Word Slave Units: 1,024 inputs and 1,024 outputs (2,048 I/O points total) Bit Slave Units: 256 inputs and 256 outputs (512 I/O points total) | 1, 2, 4, or 8 | 0.4 | - | CJ1W-CRM21 | CE, U, U1, L, N |
Note: Observe the following precautions if you use the CompoNet Master Unit in an NJ-series Machine Automation
Controller.
• Supported only by the CPU Units with unit version 1.01 or later and the Sysmac Studio version 1.02 or higher.
• You cannot use the simple backup function.
• You cannot send FINS commands to the CompoNet Master Unit.
Controller.
• Supported only by the CPU Units with unit version 1.01 or later and the Sysmac Studio version 1.02 or higher.
• You cannot use the simple backup function.
• You cannot send FINS commands to the CompoNet Master Unit.
Software
How to Select Required Support Software for Your Controller
The required Support Software depends on the Controller to connect. Please check the following table when purchasing the Support Software.
Item | Omron PLC System | Omron Machine Automation Controller System |
Controller | CS, | NJ- |
Software | FA Integrated Tool Package CX- | Automation Software Sysmac Studio |
FA Integrated Tool Package CX-One
Product name | Specifications | Model | Stand- ards | ||
---|---|---|---|---|---|
Number of licenses | Media | ||||
FA Integrated Tool Package CX-One Ver.4.[] | The CX-One is a comprehensive software package that integrates Support Software for OMRON PLCs and components. CX-One runs on the following OS. OS:Windows XP (Service Pack 3 or higher, 32-bit version)/Windows Vista (32-bit/64-bit version)/ Windows 7 (32-bit/64-bit version)/Windows 8 (32-bit/ 64-bit version)/Windows 8.1 (32-bit/64-bit version) / Windows 10 (32-bit/64-bit version) CX-One Version 4.[] includes CX-Integrator Ver.3.[]. For details, refer to the CX-One catalog (Cat. No. R134) | 1 license * | DVD | CXONE-AL01D-V4 | - |
* Multi licenses (3, 10, 30, or 50 licenses) and DVD media without licenses are also available for the CX-One.
Automation Software Sysmac Studio
Please purchase a DVD and required number of licenses the first time you purchase the Sysmac Studio. DVDs and licenses are available individually. Each model of licenses does not include any DVD.
Product name | Specifications | Model | Stand- ards | ||
---|---|---|---|---|---|
Number of licenses | Media | ||||
Sysmac Studio Standard Edition Ver.1.[][] | The Sysmac Studio provides an integrated development environment to set up, program, debug, and maintain NJ-series Controllers and other Machine Automation Controllers, as well as EtherCAT slaves. Sysmac Studio runs on the following OS. OS: Windows XP (Service Pack 3 or higher, 32-bitversion) / Windows Vista (32-bit version) / Windows 7 (32-bit/64-bit version) / Windows 8 (32-bit/64-bit version) / Windows 8.1 (32-bit/64-bitversion) / Windows 10 (32-bit/64-bit version) The Sysmac Studio Standard Edition DVD includes Support Software to set up EtherNet/IP Units, DeviceNet slaves, Serial Communications Units, and Support Software for creating screens on HMIs (CX-Designer). For details, refer to the Sysmac Integrated Catalogue (P072). | - (Media only) | DVD | SYSMAC-SE200D | - |
1 license * | - | SYSMAC-SE201L | - |
* Multi licenses are available for the Sysmac Studio (3, 10, 30, or 50 licenses).
Communication Specifications
Item | Specification | |
Communications protocol | CompoNet Network protocol | |
Types of communications | Remote I/ communications ( communications as required with Controllers * | |
Baud rate | 4 Mbps * | |
Modulation | Base- | |
Coding | Manchester code | |
Error control | Manchester code rules, | |
Communications media | The following media can be used. Round cable I ( Round cable II ( Flat Cable I ( Flat Cable II ( | |
Communications distance and wiring | Refer to Cable Types, | |
Connectable Master Units | CompoNet Master Units | |
Connectable Slave Units | CompoNet Slave Units | |
Maximum I/ | Word Slave Units: Bit Slave Units: | |
Maximum number of nodes | Word Slave Units: Bit Slave Units: Repeater Units: | |
Bits allocated per node address | Word Slave Units: Bit Slave Units: | |
Maximum number of nodes per trunk line or sub- line | 32 nodes ( | |
Applicable node addresses | Word Slave Units: Bit Slave Units: Repeater Units: | |
Repeater Unit application conditions | Up to 64 Repeater Units can be connected per network. from the Master Unit, allowed between a Slave Unit and the Master Unit) | |
Signal lines | Two lines: | |
Power lines | Two lines: Power is supplied from the Master Unit or Repeater Units. | |
Communications power supply | 24 VDC ± 10% | |
Connection forms | Flat Cable at baud rate of 93. Other cables or baud rates: | |
Connections for Slave Units and Repeater Units: |
*1. FINS message communications are supported by CJ-series Controllers only.
*2. Drop-line connections are not supported with a baud rate of 4 Mbps, so Slaves with prewired cables (Bit Slaves)
cannot be used.
*3. Round cable, Flat Cable, and Flat Cable II are all different types of cable. To use more than one type of cable at a
time, Repeater Units must be used to separate them on trunk lines and sub-trunk lines.
*2. Drop-line connections are not supported with a baud rate of 4 Mbps, so Slaves with prewired cables (Bit Slaves)
cannot be used.
*3. Round cable, Flat Cable, and Flat Cable II are all different types of cable. To use more than one type of cable at a
time, Repeater Units must be used to separate them on trunk lines and sub-trunk lines.
Cable Types, Baud Rates, and Maximum Distances
This section provides specifications on the maximum cable length and maximum number of nodes for each type of cable. Do not exceed these specifications.
Restrictions (at Baud Rate of 4 Mbps (No Branch Lines))
Cable type | Maximum length per segment ( Repeater Units) | Branch line length | Total branch line length per segment | Branch location restrictions | Maximum number of Slave Units per segment * |
Round cable I | 30 m ( | 0 m * | 0 m * | - | 32 nodes |
Flat Cable I and Flat Cable II Round Cable II | 30 m ( | 0 m * | 0 m * | - | 32 nodes |
*1. T-branches cannot be connected (only multidrop connections are possible).
*2. Number of nodes including Repeater Units
*2. Number of nodes including Repeater Units
Restrictions (at Baud Rate of 3 Mbps)
Cable type | Maximum length per segment ( length with Repeater Units) | Branch line length | Total branch line length per segment | Branch location restrictions | Maximum number of nodes per branch * | Sub- branch line length | Total sub- branch line length per segment | Maximum number of Slave Units per segment * |
Round cable I | 30 m ( | 0. | 8 m | 3 branches/ | 1 node | 0 m | 0 m | 32 nodes |
Flat Cable I and Flat Cable II Round Cable II | 30 m ( | 0. | 8 m | 3 branches/ | 1 node | 0 m | 0 m | 32 nodes |
*1. The maximum number of nodes per branch is the maximum number of Slave Units or Repeater Units that can be
connected to one branch line using multidrop or T-branch connections (sub-branches).
*2. Number of nodes including Repeater Units
connected to one branch line using multidrop or T-branch connections (sub-branches).
*2. Number of nodes including Repeater Units
Restrictions (at Baud Rate of 1.5 Mbps)
Cable type | Maximum length per segment ( length with Repeater Units) | Branch line length | Total branch line length per segment | Branch location restrictions | Maximum number of nodes per branch * | Sub- branch line length | Total sub- branch line length per segment | Maximum number of Slave Units per segment * | |
Round cable I | Without branches | 100 m ( | 0 m * | 0 m * | - | - | - | - | 32 nodes |
With branches | 30 m ( | 2. | 25 m | 3 branches/ | 3 nodes | 0 m | 0 m | 32 nodes | |
Flat Cable I and Flat Cable II Round Cable II | 30 m ( | 2. | 25 m | 3 branches/ | 3 nodes | 0. | 2 m * | 32 nodes |
*1. The maximum number of nodes per branch is the maximum number of Slave Units or Repeater Units that can be
connected to one branch line using multidrop or T-branch connections (sub-branches).
*2. Number of nodes including Repeater Units
*3. T-branches cannot be connected (only multidrop connections are possible).
*4. T-branch connections from sub-branch lines.
connected to one branch line using multidrop or T-branch connections (sub-branches).
*2. Number of nodes including Repeater Units
*3. T-branches cannot be connected (only multidrop connections are possible).
*4. T-branch connections from sub-branch lines.
Restrictions (at Baud Rate of 93.75 kbps)
Cable type | Maximum length per segment ( length with Repeater Units) | Branch line length | Total branch line length per segment | Branch location restrictions | Maximum number of nodes per branch * | Sub- branch line length | Total sub- branch line length per segment | Maximum number of Slave Units per segment * |
Round cable I | 500 m ( | 6 m | 120 m | 3 branches/ | 1 node | - | - | 32 nodes |
Flat Cable I and Flat Cable II Round Cable II | No restrictions to a total length per segment of 200 m | 32 nodes |
*1. The maximum number of nodes per branch is the maximum number of Slave Units or Repeater Units that can be
connected to one branch line using multidrop or T-branch connections (sub-branches).
*2. Number of nodes including Repeater Units
connected to one branch line using multidrop or T-branch connections (sub-branches).
*2. Number of nodes including Repeater Units
Specifications
Model | CJ1W- |
Applicable Controllers | NJ * |
Unit classification | CJ- |
Current consumption ( supplied from Power Supply Unit) | 400 mA max. |
Communications power supply connector | One communications power supply connector for Slave Units and Repeater Units on the trunk line when using Flat Cable * |
Communications power supply connector allowable current capacity | 5 A max. |
Maximum number of mountable Master Units | One word number assigned: Two word numbers assigned: Four word numbers assigned: Eight word numbers assigned: |
Mounting location | According to NJ/ |
Communications power ON/ monitoring | The ON/ power supply connector. |
Data stored in Master Unit ( | 1) Registration Table Registration Table Check Type Registered Slave Unit Participation Monitoring Time, Mode, Software Settings Table Communications Error Communications Stop Mode Communications Error Input Data Zero Clear Mode Network settings 2) stopping) |
Noise immunity | Conforms to IEC 61000- |
Vibration resistance | 10 to 61. directions for 80 min each ( |
Shock resistance | 196 m/ |
Dielectric strength | 1, Between communications connector or external current supply connector and GR terminal on Power Supply Unit Between communications connector or external current supply connector and all Unit connectors |
Insulation resistance | 20 MΩ min. |
Ambient operating temperature | 0 to 55°C |
Ambient operating humidity | 10 to 90% |
Ambient operating atmosphere | No corrosive gases |
Storage temperature | - |
Weight | 130 g max. |
*1. Supported only by the CPU Units with unit version 1.01 or later and the Sysmac Studio version 1.02 or higher.
*2. The Master Unit does not required communications power.
*2. The Master Unit does not required communications power.