Kontak Kami

KONTAK KAMI : Telpon : 02126071413 Hp/WhatsApp : 081212269831 Perwakilan Jakarta : Gedung LTC Glodok Lantai 1 Blok C30 No.31 Jl.Hayam Wuruk No.127 Jakarta , Indonesia

Rabu, 25 Mei 2016

CJ-series Controller Link Units CJ1W-CLK

International Standards

  • The standards are abbreviated as follows: U: UL, U1: UL (Class I Division 2 Products for Hazardous Locations), C: CSA, UC: cULus, UC1: cULus (Class I Division 2 Products for Hazardous Locations), CU: cUL, N: NK, L: Lloyd, and CE: EC Directives.
  • Contact your OMRON representative for further details and applicable conditions for these standards.

Controller Link Units

Unit
clas-
sifica-
tion
Product
name
SpecificationsNo. of
unit
numbers
allocated
Current
consumption
(A)
ModelStand-
ards
Communi-
cations
cable
Communi-
cations
type
Duplex
support
Max. Units
mountable
per CPU
Unit
5 V
DC
24 V
DC
CJ1
CPU
Bus
Unit
Controller
Link Unit
Wired shielded
twisted-pair
cable *
Data links
and message
service
No810.35---CJ1W-CLK23UC1, N,
L, CE
Note: This unit cannot be used with the Machine Automation Controller NJ-series. 
* Use the following special cable for shielded, twisted-pair cable. 
  • ESVC0.5×2C-13262 (Bando Electric Wire: Japanese Company) 
  • ESNC0.5×2C-99-087B (JMACS Japan Co., Ltd.: Japanese Company) 
  • ESPC 1P×0.5mm2 (Nagaoka Electric Wire Co.,Ltd.: Japanese Company) 
  • Li2Y-FCY2×0.56qmm (Kromberg & Schubert, Komtec Department: German Company) 
  • 1×2×AWG-20PE+Tr.CUSN+PVC (Draka Cables Industrial: Spanish Company) 
  • #9207 (Belden: US Company)

Accessories

There is no accessory for the CJ series Controller Link Unit.

Controller Link Support Boards

Product nameSpecificationsAccessoriesModelStandards
Communications
cable
Communications
type
Controller Link
Support Board
for PCI Bus
Wired shielded
twisted-pair cable
Data links and
message service
CD-ROM x 1 *
INSTALLATION GUIDE (W467) x 1
Communications connector x 1
3G8F7-CLK23-ECE
* The CD-ROM contains the following software. 
  • Controller Link (PCI) Driver 
  • FinsGateway Version 2003 (PCI-CLK Edition) 
  • FinsGateway Version 3 (PCI-CLK Edition) 
  • Setup Diagnostic Utility 
  • C Library

Repeater Units

NameSpecificationsModelStandards
Controller Link
Repeater Unit
Wire-to-Wire ModelCS1W-RPT01UC1, CE
Wire-to-Optical (H-PCF) Model *1CS1W-RPT02
Wire-to-Optical (GI) Model *2CS1W-RPT03
Using Repeater Units enables T-branches and long-distance wiring for Wired Controller Link networks, 62-node configurations, and converting part of the network to optical cable. 
*1. When using wire-to-optical (H-PCF) cable, use a H-PCF cable (for both Controller Link and SYSMAC LINK) or a H-PCF 
       optical fiber cable with connector. 
*2. When using wire-to-optical (GI) cable, use a GI optical cable (for Controller Link).

Relay Terminal Block

NameSpecificationsModelStandards
Relay Terminal Block for
Wired Controller Link Units
Used for Wired Controller Link Units (set of 5)CJ1W-TB101---
Controller Link Units can be replaced without stopping the communications of the entire network if a Relay Terminal Block is installed in advance on the Unit in a Wired Controller Link network. Relay Terminal Blocks cannot be used on Controller Link Support Boards.

H-PCF Cables and Optical Connectors

NameApplication/constructionSpecificationsModelStandards
Optical Fiber CablesController
Link,
SYSMAC
LINK,
SYSBUS
 
1. Optical fiber
single-core cord
2. Tension member
(plastic-sheathed wire)
3. Filler (plastic)
4. Filler surrounding
signal wires
(plastic, yarn, or fiber)
5. Holding tape (plastic)
6. Heat-resistant PV
sheath
Two-core
optical
cable with
tension
member
Black 10 mS3200-HCCB101---
Black 50 mS3200-HCCB501
Black 100 mS3200-HCCB102
Black 500 mS3200-HCCB502
Black 1000 mS3200-HCCB103
Orange 10 mS3200-HCCO101
Orange 50 mS3200-HCCO501
Orange 100 mS3200-HCCO102
Orange 500 mS3200-HCCO502
Orange 1000 mS3200-HCCO103
Optical
Connectors
(Crimp-cut)
CS1W-RPT02Half lockS3200-COCF2571
Full lockS3200-COCF2071

H-PCF Optical Fiber Cables with Connectors (Black Composite Cables with Two-Optical Lines and Two Power Supply Lines)

ApplicationAppearanceModelStandards
Controller Link,
SYSMAC LINK
S3200-CN[][][]-20-20---
S3200-CN[][][]-20-25
S3200-CN[][][]-25-25
Optical connectors for H-PCF Optical Cables with Connectors are adhesive polished.

Cable Length

The following cable lengths are available: 2 m, 5 m, 15 m, 20 m. For lengths of 21 m or more, contact your OMRON sales representative.

Model Numbers

CJ1W-CLK Lineup 15

Optical Connector Assembly Tool

NameApplicable UnitModelManufacturerStandards
Optical Fiber
Assembly Tool *
This tool is used on site for mounting crimp-cut connectors
and hard plastic-clad silica optical fiber for optical transmission
systems of SYSMAC C-series SYSBUS, SYSMAC LINK, and
Controller Link.
CAK-0057Sumitomo Electric
Industries, Ltd.
---
* There is a risk of quality problems when using cables assembled by typical users, so we recommend purchasing 
   cables with preattached connectors or having a qualified technician assemble the cables.

Tidak ada komentar: