Kontak Kami

KONTAK KAMI : Telpon : 02126071413 Hp/WhatsApp : 081212269831 Perwakilan Jakarta : Gedung LTC Glodok Lantai 1 Blok C30 No.31 Jl.Hayam Wuruk No.127 Jakarta , Indonesia

Rabu, 25 Mei 2016

CJ series Position Control Units CJ1W-NC[][]3

International Standards

  • The standards are abbreviated as follows: U: UL, U1: UL(Class I Division 2 Products for Hazardous Locations), C: CSA, UC: cULus, UC1: cULus (Class I Division 2 Products for Hazardous Locations), CU: cUL, N: NK, L: Lloyd, and CE: EC Directives.
  • Contact your OMRON representative for further details and applicable conditions for these standards.

Position Control Unit

Unit 
type
NameSpecificationsNo. of 
unit 
numbers 
allocated
Current 
consumption (A)
ModelStandards
Control method/ 
Control output 
interface
Number of 
control 
axes
5 V 
system
24 V 
system
CJ1 
Special 
I/O 
Units
Position 
control 
unit
Open-loop control 
by pulse train 
output/Open- 
collector output
1 axis10.25---CJ1W-NC113UC1, CE
2 axes0.25---CJ1W-NC213
4 axes *20.36---CJ1W-NC413
Open-loop control 
by pulse train 
output/Line-driver 
output
1 axis10.25---CJ1W-NC133
2 axes0.25---CJ1W-NC233
4 axes *20.36---CJ1W-NC433
Space 
Unit
The ambient operation temperature range can be increased to 
0 to 55 °C if the CJ1W-SP001 CJ-series Space Unit is used.
CJ1W-SP001UC1, CE
Note: This unit cannot be used with the Machine Automation Controller NJ-series. 
* The ambient operating temperature of the CJ1W-NC413/NC433 is 0 to 50°C. Allowable power supply voltage range for 
   external power supply is 22.8 to 25.2 V DC.

Software

NameSpecificationsNumber of 
licenses
ModelStand- 
ards
FA Integrated 
Tool Package 
CX-One 
Ver.4.[]
The CX-One is a comprehensive software package 
that integrates Support Software for OMRON PLCs 
and components. CX-One runs on the following OS. 
OS: Windows XP (Service Pack 3 or higher, 32-bit 
version)/Windows Vista (32-bit/64-bit version)/ 
Windows 7 (32-bit/64-bit version)/Windows 8 (32- 
bit/64-bit version)/Windows 8.1 (32-bit/64-bit 
version)/Windows 10 (32-bit/64-bit version) 

CX-One Ver.4. [] includes CX-Position Ver.2. []. 
For details, refer to the CX-One catalog (Cat. No. 
R134).
1 license * 
DVD
CXONE-AL01D-V4---
* Multi licenses (3, 10, 30, or 50 licenses) and DVD media without licenses are also available for the CX-One.

Servo Relay Unit/Cables

NameApplicable unitsApplicable drivesNumber 
of 
control 
axes
Cable 
length
ModelStand- 
ards
Servo 
Relay 
Unit
For CJ1W-NC113/133 
(No communication supported)
---1 axis---XW2B-20J6-1B---
For CJ1W-NC213/233/413/433 
(No communication supported)
---2 axes---XW2B-40J6-2B
For CJ1W-NC113/133/213/ 
233/413/433 
(Communication supported)
---2 axes---XW2B-40J6-4A
Position 
Control 
Unit 
Cables 
for 
Servo 
Relay 
Unit
Open- 
collector 
output
For CJ1W-NC113OMNUC G/G5 Series, 
SMARTSTEP 2
1 axis0.5mXW2Z-050J-A14---
1mXW2Z-100J-A14
SMARTSTEP 
Junior Series
0.5mXW2Z-050J-A16
1mXW2Z-100J-A16
For CJ1W- 
NC213/413
OMNUC G/G5 Series, 
SMARTSTEP 2
2 axes0.5mXW2Z-050J-A15
1mXW2Z-100J-A15
SMARTSTEP 
Junior Series
0.5mXW2Z-050J-A17
1mXW2Z-100J-A17
Line- 
driver 
output
For CJ1W-NC313OMNUC G/G5 Series, 
SMARTSTEP 2
1 axis0.5mXW2Z-050J-A18
1mXW2Z-100J-A18
SMARTSTEP 
Junior Series
0.5mXW2Z-050J-A20
1mXW2Z-100J-A20
For CJ1W- 
NC233/413
OMNUC G/G5 Series, 
SMARTSTEP 2
2 axes0.5mXW2Z-050J-A19
1mXW2Z-100J-A19
SMARTSTEP 
Junior Series
0.5mXW2Z-050J-A21
1mXW2Z-100J-A21

Accessories

The Position Control Unit includes the 40-pin solder-type connectors C500-CE404 (socket: Fujitsu FCN-361J040-AU, cover: Fujitsu FCN-360C040-J2).

Applicable Connectors

NameSpecificationsModel
External I/O Connectors
40 pin, soldered, right angle w/cover (included with the Unit)C500-CE404
40 pin, crimped right angle w/coverC500-CE405
40 pin, Pressure welded, w/o coverC500-CE403
40 pin, soldered, w/coverC500-CE401
40 pin, crimped w/coverC500-CE402

Basic Specifications

ItemModel
CJ1W-NC113/133CJ1W-NC213/233CJ1W-NC413/433
Power supply 
voltage
5 V DC (for the PCU itself)
24 V DC (external power supply)
5 V DC (external power supply; line driver output only)
Allowable power
supply voltage 
range
4.75 to 5.25 V DC (for the PCU itself)
21.6 to 26.4 V DC (external power supply)22.8 to 25.2 V DC 
(external power supply)
4.75 to 5.25 V DC (external power supply; line driver output only)
Internal current 
consumption
250 mA max. at 5 V DC250 mA max. at 5 V DC360 mA max. at 5 V DC
Current 
consumption of 
external power 
supply
NC113: 30 mA max. at 24 V DC
NC133: 10 mA max. at 24 V DC
NC133: 60 mA max. at 5 V DC
NC213: 50 mA max. at 24 V DC
NC233: 20 mA max. at 24 V DC
NC233: 120 mA max. at 5 V DC
NC413: 100 mA max. at 24 V DC
NC433: 30 mA max. at 24 V DC 
NC433: 230 mA max. at 5 V DC
External 
dimensions
90 (H) × 31 (W) × 65 (D) (all models)
Weight100 g max.100 g max.150 g max.
Ambient 
operating 
temperature
0 to 55 ° C0 to 50 ° C *
Note: Specifications not listed above conform to CJ Series general specifications. 
* Refer to Operation Manual 3-3-5 Mounting Precaution for CJ1W-NC413/NC433 for information on the ambient operating 
  temperature of the CJ1W-NC413/433.

Performance Specifications

ItemModel
CJ1W-NC113/133CJ1W-NC213/233CJ1W-NC413/433
Applicable PLC modelsCJ-series PLCs *1
Unit typeSpecial I/O Unit
I/O requirementsWords5 words10 words20 words
Controlled driverPulse-train input-type Servo Drive or stepping motor driver 
NC113/213/413 models have open collector output. 
NC133/233/433 models have line driver output.
ControlControl systemOpen-loop control by pulse train output
Number of control 
axes
1 axis2 axes4 axes
Control unitPulse
Positioning operationsTwo types: memory operation and direct operation
Positioning 
operations
Independent1 axis2 independent axes4 independent axes
Linear interpolationNone2 axes max.4 axes max.
Speed control1 axis2 independent axes4 independent axes
Interrupt feeding1 axis2 independent axes4 independent axes
PositionsRange-1,073,741,823 to 1,073,741,823 pulses *2
Data items100/axis
SpeedsRange1 pps to 500 kpps
Data items100/axis
Acceleration and 
deceleration times
Range0 to 250 s, until maximum speed is reached.
Data items9/axis for acceleration and deceleration each
Functions and 
settings
Origin searchOrigin proximity input signal: selectable (absent, N.O. or N.C. contact). 
Origin input signal: selectable (N.O. or N.C. contact) 
Origin compensation: -1,073,741,823 to 1,073,741,823 pulses 
Origin search speed: High-speed or proximity-speed can be set. 
Origin detection method: May be set to stop upon origin input signal after proximity input 
signal has turned ON, to stop upon origin input signal after proximity input signal has 
turned OFF, to stop upon origin input signal without using proximity input signal, or to stop 
upon origin input signal after limit input signal has turned OFF. 
N.O. = Normally open 
N.C. = Normally closed
JoggingJogging can be executed at a specified speed.
Dwell times19/axis can be set from 0 to 9.99 s (unit: 0.01 s).
Acceleration/ 
deceleration curves
Trapezoidal or S-curve (Can be set separately for each axis.)
ZonesZone Flag turns ON when present position is within a specified zone. Three zones can be 
set for each axis.
Software limitsCan be set within a range of -1,073,741,823 to 1,073,741,823 pulses.
Backlash 
compensation
0 to 9,999 pulses. Compensation speed can also be set.
TeachingWith a command from the PLC, the present position can be taken as the position data.
Deceleration stopThe STOP command causes positioning to decelerate to a stop according to the specified 
deceleration time.
Emergency stopPulse outputs are stopped by an external emergency stop command.
Present position 
preset
The PRESENT POSITION PRESET command can be used to change the present position 
to a specified value.
OverrideWhen the override enabling command is executed during positioning, the target speed is 
changed by applying the override coefficient. Possible to set to a value from 1 to 999% (by 
an increment of 1%)
Data saving1) Saving to flash memory. (Can be written 100,000 times.) 
2) Reading from PLC area by data reading instruction. 
3) Reading by Support Software and saving to personal computer hard disk or floppy disk.
External I/OInputsPrepare the following inputs for each axis: 
CW and CCW limit input signals, origin proximity input signal, origin input signal, emergency 
stop input signal, positioning completed signal, interrupt input signal
OutputsPrepare the following outputs for each axis: 
Pulse outputs 
CW/CCW pulses, pulse outputs and direction outputs can be switched. 
Either error counter reset or origin-adjustment command outputs can be selected 
depending on the mode.
Pulse output distribution period1-axis operation: 4 ms 
Linear interpolation: 8 ms
Response timeRefer to Operation manual Appendix A Performance Characteristics.
Self-diagnostic functionFlash memory check, memory loss check, CPU bus check
Error detection functionOvertravel, CPU error, software limit over, emergency stop
*1. The additional functions supported by unit version 2.0 can be used only when the PCU is installed with a CJ1-H or 
       CJ1M CPU Unit (either CPU Unit Ver. 2.0 or Pre-Ver. 2.0 CPU Unit). These functions cannot be used if the PCU is 
       installed with a CJ1 CPU Unit. 
*2. When performing linear interpolation, the distances that can be moved will vary.

Tidak ada komentar:

Posting Komentar