CJ-series Process Analog I/O Unit CJ1W-PTS

International Standards

  • The standards are abbreviated as follows: U: UL, U1: UL (Class I Division 2 Products for Hazardous Locations), C: CSA, UC: cULus, UC1: cULus (Class I Division 2 Products for Hazardous Locations), CU: cUL, N: NK, L: Lloyd, and CE: EC Directives.
  • Contact your OMRON representative for further details and applicable conditions for these standards.

Process I/O Units

Isolated-type Thermocouple Input Units

Unit 
classi- 
fica- 
tion
Product 
name
Input 
points
Signal
range
selec-
tion
Signal 
range
Conver-
sion 
speed 
(resolu- 
tion)
Accuracy
(at 
ambient 
tempera- 
ture of 
25 °C)
Ex- 
ternal 
con- 
nec- 
tion
No. 
of 
unit 
num- 
bers 
allo- 
cated
Current 
consump-
tion (A)
ModelStand-
ards

V
24 
V
CJ1 
Special
I/O 
Units
Process
Input 
Units 
(Iso- 
lated- 
type 
Thermo-
couple 
Input 
Units)

inputs
Set 
sepa- 
rately 
for 
each 
input
Thermo-
couple: 
B, E, J, 
K, L, N, 
R, S, T, 
U, 
WRe5- 
26, PLII 
DC 
voltage: 
± 100 
mV
Conver- 
sion 
speed: 
10 ms/ 
2 inputs,
Resolu- 
tion: 
1/64,000
Standard 
accuracy: 
±0.05% of
F.S. *1
Remov-
able 
terminal
block
10.180.06
*2
CJ1W-PTS15UC1, 
CE

inputs
Com- 
mon 
inputs
Thermo-
couple: 
R, S, K, 
J, T, L, 
B
Conver- 
sion 
speed: 
250 ms/ 
4 inputs
Accuracy: 
(±0.3% of 
PV or 
±1°C, 
whichever
is larger) 
±1 digit 
max. *3
0.25---CJ1W-PTS51
Note: This unit cannot be used, with the Machine Automation Controller NJ-series. 
*1. The accuracy depends on the sensors used and the measurement temperatures. For details, refer to the user's 
       manual. 
*2. This is for an external power supply, and not for internal current consumption. 
*3. L and −100°C or less for K and T are ±2°C±1 digit max., and 200°C or less for R and S is ±3°C±1 digit max. No 
       accuracy is specified for 400°C or less for B.

Isolated-type Resistance Thermometer Input Units

Unit 
classi- 
fica- 
tion
Product 
name
Input 
points
Signal
range
selec-
tion
Signal 
range
Conver-
sion 
speed 
(resolu-
tion)
Accuracy
(at 
ambient 
tempera- 
ture of 
25 °C)
Ex- 
ternal 
con- 
nec- 
tion
No. 
of 
unit 
num- 
bers 
allo- 
cated
Current 
consump-
tion (A)
ModelStand-
ards

V
24 
V
CJ1 
Special
I/O 
Units
Process
Analog 
Input 
Units 
(Iso- 
lated- 
type 
Resist- 
ance 
Thermo-
couple 
Input 
Units)
1644_lu_2_1

inputs
Com- 
mon 
inputs
Resist-
ance 
ther- 
mom- 
eter: 
Pt100, 
JPt100
Conver-
sion 
speed: 
250 ms/ 
4 inputs
Accuracy: 
±0.3% of 
PV or 
±0.8°C, 
whichever
is larger, 
±1 digit 
max.
Remov-
able 
terminal
block
10.25-CJ1W-PTS52UC1, 
CE
Note: This unit cannot be used, with the Machine Automation Controller NJ-series. 
* This is for an external power supply, and not for internal current consumption.

CJ1W-PTS15 Isolated-type Thermocouple Input Unit

ItemSpecifications
ModelCJ1W-PTS15
Applicable ControllerCJ Series
Unit classificationCJ-series Special I/O Unit
Mounting positionCJ-series CPU Rack or CJ-series Expansion Rack
Maximum number of Units40 (within the allowable current consumption and power consumption range)
Unit numbers00 to 95 (Cannot duplicate Special I/O Unit numbers.)
Areas for
data
exchange
with CPU
Unit
Special I/O Unit Area
(Operation Data)
10 words/Unit
Thermocouple Input Unit to CPU Unit:
All process values, process value alarms (LL, L, H, HH), conversion data enabled flags, sensor errors.
DM Area words
allocated to Special
I/O Units
(Setting parameter)
100 words/Unit
CPU Unit to Thermocouple Input Unit:
Temperature sensor type, input range (user set), process value alarm setting (L, H), zero/span
adjustment value.
Expansion Control/
Monitor Area words
(Expansion
Operation Data)
35 words/Unit
CPU Unit to Thermocouple Input Unit:
Hold function selection start/reset, adjustment period control, control bits
Thermocouple Input Unit to CPU Unit:
Adjustment period warnings/notices (for each input), peak and bottom values, top and valley values
Expansion Setting
Area words
(Expansion Setting
parameter)
46 words/Unit
CPU Unit to Thermocouple Input Unit:
Expansion Setting Area settings, adjustment period control, peak and bottom detection, top and valley
detection
Number of temperature sensor
inputs
2
Temperature sensor typeThe sensor type, input range, and scaling can be set individually for each of 2 inputs, which are each
selectable from B, E, J, K, L, N, R, S, T, U, WRe5-26, PL II, and mV.
ScalingData to be stored in the allocated words in the CIO area must be scaled (with the minimum and
maximum values set by user) (2 inputs set separately). For example, data can be stored at 0% to 100%.
Data storage in the CIO AreaThe value derived from carrying out the following processing in order of the actual process data in
the input range is stored in four digits hexadecimal (binary values) in the allocated words in the CIO
Area.
1) Mean value processing → 2) Scaling → 3) Zero/span adjustment → 4) Output limits
Accuracy (25 ° C)±0.05% (Depends on the Sensor used and the measured temperature. Refer to Accuracy by Sensor
Type and Measured Temperature Range on Data Sheet for details.)
Temperature coefficient±0.01%/°C (For full scale of electromotive force. *)
Resolution1/64000
Cold junction compensation
error
±1°C, at 20 ±10°C
Maximum signal input±120 mV
Input impedance20 kΩ min.
Input disconnection detection
current
0.1 μA (typical)
Warmup time45 min
Response time100 ms (travel time from input 0% to 90%, for ±100 mV step input and with moving average for 4
samples)
Conversion period10 ms/2 inputs
Maximum time to store data in
CPU Unit
Conversion period + one CPU Unit cycle
Disconnection detectionDetects disconnections at each input and turns ON the Disconnection Detection Flag.
Hardware detection time: Approx. 0.5 s max.
The process value overrange direction for when a disconnection occurs can be specified. (High: 115%
of set input range; low: -15% of set input range)
FunctionMean value
processing
(input filter)
Calculates the moving average for the specified number of process values (1 to 128), and stores that
value in the CIO Area as the process value.
Process value alarmProcess value 4-point alarm (LL, L, H, HH), alarm hysteresis, and ON-delay timer (0 to 60 s) are
available.
Rate-of-change
calculation
Calculates the amount of change per comparison time interval (1 to 16 s).
Rate-of-change
alarm
Rate-of-change 2-point alarm (L, H), alarm hysteresis (shared with process value alarm), and ON-
delay timer (0 to 60 s, shared with process value alarm) are available.
Adjustment period
control
When zero/span adjustment is executed, the date is internally recorded at the Unit. When the preset
zero/span adjustment period and number of days notice have elapsed (allocated in Expansion Setting
Area), this function turns ON a warning flag to give notice that it is time for readjustment.
Peak and bottom
detection
This function detects the maximum (peak) and minimum (bottom) analog input values, from when the
Hold Start Bit (output) allocated to the Expansion Control/Monitor Area turns ON until it turns OFF,
and stores them in the Expansion Control/Monitor Area.
Top and valley
detection
This function detects the top and valley values for analog inputs, from when the Hold Start Bit
(output) allocated to the Expansion Control/Monitor Area turns ON until it turns OFF, and stores
them in the Expansion Control/Monitor Area.
IsolationBetween inputs and Controller signals, and between inputs: Isolation by transformer for power supply,
and by photocoupler for signals.
Cold junction compensation circuit: No isolation from input 2
Insulation resistance20 MΩ (at 500 V DC) between inputs
Dielectric strengthBetween inputs: 1,000 V AC, at 50/60 Hz, for 1 min, leakage current 10 mA max.
External connectionsTerminal block (detachable)
Unit number settingsSet by rotary switches on front panel, from 0 to 95.
IndicatorsFour LED indicators on front panel (for normal operation, errors detected at the Thermocouple Input
Unit, errors related to the CPU Unit, and use of external power supply).
Front panel connectorSensor input connector terminal block (detachable)
Effect on CPU Unit cycle time0.3 ms
Current consumption5 V DC at 180 mA max.
External power supply24 VDC +10%/-15% 60 mA max., inrush current: 20 A for 1 ms max.
(The external 24-VDC power supply must be isolated.)
Dimensions31 × 90 × 65 mm (W × H × D)
Weight150 g max.
Standard accessoriesTwo cold junction sensors (installed in terminal block)
* The method for calculating the error in temperature measurements, including the temperature coefficient, is given 
   below. The "full scale of electromotive force" is the difference between the high limit and low limit converted to 
   electromotive force for each thermocouple.
CJ1W-PTS Specifications 2

CJ1W-PTS51 Isolated-type Thermocouple Input Unit

ItemSpecifications
ModelCJ1W-PTS51
Applicable ControllerCJ Series
Unit classificationCJ-series Special I/O Unit
Mounting positionCJ-series CPU Rack or CJ-series Expansion Rack
Maximum number of Units40 (within the allowable current consumption and power consumption range)
Unit numbers00 to 95 (Cannot duplicate Special I/O Unit numbers.)
Areas for
data
exchange
with CPU
Unit
Special I/O Unit Area
(Operation Data)
10 words/Unit
Thermocouple Input Unit to CPU Unit:
All process values, process value alarms (L, H), conversion data enabled flag, sensor errors, cold
junction sensor errors
DM Area words
allocated to Special
I/O Units
(Setting parameter)
100 words/Unit
CPU Unit to Thermocouple Input Unit:
Temperature sensor type, input range (same for all I/O), process value alarm setting (L, H), zero/span
adjustment value.
Number of temperature sensor
inputs
4
Temperature sensor typesSelectable from K, J, L, R, S, T, B. (Same setting for all inputs.)
Data storage in the CIO AreaThe actual process data in the input range is stored in four digits hexadecimal (binary or BCD values)
in the allocated words in the CIO Area.
Accuracy (25°C)With Celsius selected: ±0.3% of PV or ±1°C, whichever is greater, ±1 digit max.
With fahrenheit selected: ±0.3% of PV or ±2°F, whichever is greater, ±1 digit max.
However, the accuracy of K and T at -100°C or lower and L is ±2°C ±1 digit max.
The accuracy of R and S at 200°C or lower is ±3°C ± 1 digit max.
The accuracy of B at 400°C or lower is not specified.
PV: Process value data
Temperature characteristicsRefer to Temperature Characteristics According to Thermocouple Type on Data Sheet.
Warmup time30 min
Conversion period250 ms/4 inputs
Maximum time to store data in
CPU Unit
Conversion period + one CPU Unit cycle
Sensor error detectionInput Types Other Than B:
A Sensor error is detected and the Sensor Error Flag is turned ON if the upper or lower limit of the
set input range is exceeded by 20°C or 20°F. The process value overrange direction when a
Sensor error occurs can be specified (high: set input range +20°C or +20°F, low: set input range
-20°C or -20°F).
B Input Type:
A Sensor error is detected and the Sensor Error Flag is turned ON if the upper limit of 1,820°C or
3,220°F or the lower limit of 0°C or 0°F is exceeded. The process value overrange direction
when a Sensor error occurs can be specified (high: set input range 1,820°C or 3,220°F, low: set
input range 0°C or 0°F).
FunctionProcess value alarmProcess value 2-point alarm (HH, H, LL, L), alarm hysteresis, and ON-delay timer (0 to 60 s) are
available.
External alarm outputs: One per input (H or L).
External alarm 
outputs
NPN outputs (with short-circuit protection)
External power supply voltage: 20.4 to 26.4 V DC
Max. switching capacity: 100 mA (for one output)
Leakage current: 0.3 mA max.
Residual voltage: 3 V max.
IsolationBetween inputs and Controller signal: Transformer for power supply and photocoupler for signals
Between each input: Transformer for power supply and photocoupler for signals.
Insulation resistance20 MΩ max. (at 500 V DC).
Between all output and NC terminals and external AC terminals (Power Supply Unit)
Between all input terminals and external AC terminals (Power Supply Unit)
Between all input terminals and all output terminals
Between all external DC terminals (input, output, and NC terminals) and FG plate
Between all input and output terminals and all NC terminals
Dielectric strengthBetween all output and NC terminals and external AC terminals (Power Supply Unit)
2,000 VAC, 50/60 Hz 1 min., detection current: 1 mA
Between all input terminals and external AC terminals (Power Supply Unit)
Between all input terminals and all output terminals
Between all external DC terminals (input, output, and NC terminals) and FG plate
1,000 VAC, 50/60 Hz 1 min., detection current: 1 mA
Between all channels
500 VAC, 50/60 Hz 1 min., detection current: 1mA
External connectionsTerminal block (detachable)
Unit number settingsSet by rotary switches on front panel, from 0 to 95.
IndicatorsSeven LED indicators on front panel (for normal operation, errors detected at the Thermocouple
Input Unit, errors related to the CPU Unit, and four indicators for external alarm outputs.)
Current consumption (supplied
from Power Supply Unit)
5 V DC at 250 mA max.
Dimensions31 × 90 × 65 mm (W × H × D)
Weight150 g max.

CJ1W-PTS52 Isolated-type Resistance Thermometer Input Unit (Pt100, JPt100)

ItemSpecifications
ModelCJ1W-PTS52
Applicable ControllerCJ Series
Unit classificationCJ-series Special I/O Unit
Mounting positionCJ-series CPU Rack or CJ-series Expansion Rack
Maximum number of Units40 (within the allowable current consumption and power consumption range)
Unit numbers00 to 95 (Cannot duplicate Special I/O Unit numbers.)
Areas for
data
exchange
with CPU
Unit
Special I/O Unit Area
(Operation Data)
10 words/Unit
Resistance Thermometer Input Unit to CPU Unit:
All process values, process value alarms (L, H), conversion data enabled flags, sensor errors.
DM Area words
allocated to Special
I/O Units
(Setting parameter)
100 words/Unit
CPU Unit to Resistance Thermometer Input Unit:
Temperature sensor type, input range (user set), process value alarm setting (L, H), zero/span
adjustment value.
Number of temperature sensor
inputs
4
Temperature sensor typePt100 (JIS, IEC), JPt100
Sensor type, input range, and scaling to industrial units are the same for all I/O.
Data storage in the CIO AreaThe actual process data in the input range is stored in four digits hexadecimal (binary or BCD values)
in the allocated words in the CIO Area.
Accuracy (25 ° C)± 0.3% of PV or ± 0.8°C, whichever is greater, ± 1 digit max.
± 0.3% of PV or ± 1.6°F, whichever is greater, ± 1 digit max.
PV: Process value data
Temperature characteristicsRefer to Temperature Characteristics According to Platinum Resistance Thermometer Type on Data
Sheet.
Sensing method3-wire method
Influence of conductor
resistance
0.4°C/Ω max.
Warmup time10 min
Conversion period250 ms/4 inputs
Maximum time to store data in
CPU Unit
Conversion period + one CPU Unit cycle
Sensor error detectionDetects sensor error at each input and turns ON the Sensor error Flag.
Hardware detection time: Approx. 0.5 s max.
The process value overrange direction for when a sensor error occurs can be specified. (High: +20
digit of set input range; low: -20 digit of set input range)
FunctionProcess value alarmProcess value 2-point alarm (H, L), alarm hysteresis, and ON-delay timer (0 to 60 s are available).
External alarm
outputs
NPN outputs (with short-circuit protection)
External power supply voltage: 20.4 to 26.4 V DC
Max. switching capacity: 100 mA (for one output)
Leakage current: 0.3 mA max.
Residual voltage: 3 V max.
IsolationBetween inputs and Controller signal: Transformer for power supply and photocoupler for signals
Between each input: Transformer for power supply and photocoupler for signals
Insulation resistance20 MΩ max. (at 500 V DC).
Between all output and NC terminals and external AC terminals (Power Supply Unit)
Between all input terminals and external AC terminals (Power Supply Unit)
Between all input terminals and all output terminals
Between all external DC terminals (input, output, and NC terminals) and FG plate
Between all input and output terminals and all NC terminals
Dielectric strengthBetween all output and NC terminals and external AC terminals (Power Supply Unit)
2,000 V AC, 50/60 Hz 1 min., detection current: 1 mA
Between all input terminals and external AC terminals (Power Supply Unit)
Between all input terminals and all output terminals
Between all external DC terminals (input, output, and NC terminals) and FG plate
1,000 V AC, 50/60 Hz 1 min., detection current: 1 mA
Between all channels
500 VAC, 50/60 Hz 1 min., detection current: 1 mA
External connectionsTerminal block (detachable)
Unit number settingsSet by rotary switches on front panel, from 0 to 95.
IndicatorsSeven LED indicators on front panel (for normal operation, errors detected at the Resistance
Thermometer Input Unit, errors detected at the CPU Unit, and four indicators for external alarm
outputs.)
Current consumption5 V DC at 250 mA max
Dimensions31 × 90 × 65 mm (W × H × D)
Note: The height including the Backplane is 145 mm.
Weight150 g max.