Communications Specifications
Items | Specifications |
---|---|
Model | CJ1W-CLK23 3G8F7-CLK23-E CJ1W-CLK21-V1 *1 3G8F7-CLK21-EV1 *1 |
Type | Wired (shielded twisted-pair cable) |
Communications method | N:N token-bus method |
Code | Manchester code |
Modulation | Baseband code |
Synchronization | Flag synchronization (conforms to HDLC frames) |
Transmission path format | Multidrop method (bus type) |
Transmission speed | The following are the maximum transmission distances depending on the transmission speed. 2 Mbits/s: 500 m 1 Mbits/s: 800 m 500 kbits/s: 1 km |
Maximum transmission distance | |
Maximum distance between nodes | Not specified. (Maximum transmission distance must be satisfied for the entire system.) |
Medium | Specified shielded twist-pair cable Two signal wires, one shield |
Node connection method | PLC: Connection to terminal block Computer: Connection using special (supplied) connector |
Maximum number of nodes | 32 or 62 nodes *2 *3 |
Applicable Programming Devices | CX-Integrator in CX-One, CX-Net in CX-Programmer *3, and Programming Console |
Communications functions | Data links and message service |
Number of data link words | Send words per node: 4,000 words max. (CJ1W-CLK[]3), 1,000 words max. (All other Units) Number of send/receive words per node: 12,000 words max. (Pre-Ver. 1.2) 20,000 words max. (unit Ver. 1.2 or later) Total number of send words per network: 62,000 words max. |
Data link areas | PLC: Bit areas (CIO Area, Work Area, Link Area *4), Data Memory (DM), Extended DM Area (EM) Computer: FinsGateway event memory |
Message length | 2,012 bytes max. (including the header) |
RAS functions | Polling node backup function Self-diagnosis function (hardware checking at startup) Echoback test and broadcast test (using the FINS command) Watchdog timer Error log function |
Error control | Manchester code check CRC check (CCITT X16 +X12 +X5 +1) |
*1. Discontinuation models in July 2012.
*2. With wired models, the maximum number of nodes is 32 if Repeater Units are not used. A Repeater Unit is required
when building a network with more than 32 nodes. If a Repeater Unit is used, be sure to use only the following
Controller Link Units or Boards and set the Wired Network 62 Node Enable Bit in the DM Parameter Area software
switches at all nodes.
CS1W-CLK23/CLK21-V1
CJ1W-CLK23/CLK21-V1
3G8F7-CLK23-E/CLK21-EV1
*3. CX-Net in CX-Programmer version 3.1 or earlier can be used only in a system with a maximum of 32 nodes (node
address 1 to 32). If a system is to be used with a maximum of 62 nodes (node addresses 1 to 62), use CX-Net in
CX-Programmer version 3.2 or higher or the CX-Integrator.
*4. CJ-series PLCs do not have a Link Area, but LR000 to LR199 are automatically converted CIO 1000 to CIO 1199.
*2. With wired models, the maximum number of nodes is 32 if Repeater Units are not used. A Repeater Unit is required
when building a network with more than 32 nodes. If a Repeater Unit is used, be sure to use only the following
Controller Link Units or Boards and set the Wired Network 62 Node Enable Bit in the DM Parameter Area software
switches at all nodes.
CS1W-CLK23/CLK21-V1
CJ1W-CLK23/CLK21-V1
3G8F7-CLK23-E/CLK21-EV1
*3. CX-Net in CX-Programmer version 3.1 or earlier can be used only in a system with a maximum of 32 nodes (node
address 1 to 32). If a system is to be used with a maximum of 62 nodes (node addresses 1 to 62), use CX-Net in
CX-Programmer version 3.2 or higher or the CX-Integrator.
*4. CJ-series PLCs do not have a Link Area, but LR000 to LR199 are automatically converted CIO 1000 to CIO 1199.
Individual Specifications
Controller Link Units
Item | Specifications |
---|---|
Model | CJ1W-CLK23 CJ1W-CLK21-V1 * |
Applicable PLC | All CJ-series CPU Units |
Number of mountable Units | 8 max. |
Installation site | Install onto a CPU Backplane or Expansion Backplane (classified as a CPU Bus Unit). |
Storage location of network parameters and manually set data link tables | System Bus Unit Area (in the CPU Unit parameter area). |
Storage location of routing tables | CPU Unit parameter area |
Weight | 110 g |
Current consumption: 5 V in PLC | 0.35 A |
* Discontinuation models in July 2012.
Controller Link Support Boards (for PCI Bus), New Models
Item | Specifications | |||
---|---|---|---|---|
Model | 3G8F7-CLK23-E | 3G8F7-CLK13-E | 3G8F7-CLK53-E | |
Computer-compatible models | IBM PC/AT or compatible CPU: Intel Celeron 400 MHz or better Main memory: 128 MB minimum One or more PCI bus slots (PCI bus revision 2.0 or later, power supply: 5 V) Free hard disk space: 70 MB min. CD-ROM drive: One required for installation Display: VGA (640 x 480 (pixels) min.) (Other conditions conform to the OS.) | |||
Compatible OS | FinsGateway Version2003 *1 Windows 7 (32bit) Professional Windows 7 (32bit) Home Premium Windows Vista Business Windows Vista Home Premium Windows XP Professional Windows XP Home Edition Windows 2000 Professional FinsGateway Version3 *2 Windows XP Professional Windows XP Home Edition Windows 2000 Professional Windows NT4.0 (Service Pack 3 or higher) Windows ME Windows 98SE | |||
Weight | 104 g | 120 g (excluding mounting bracket) | 124 g (excluding mounting bracket) | |
Current consumption | 5 V in PLC | 0.35 A | 0.54 A | 0.60 A |
External 24 V | --- | 0.35 A | 0.35 A |
*1. Install the software from CD Ver. 3.10 or higher if the operating system is Windows 7 (32bit) or Windows Vista.
*2. Install FinsGateway version 3 if the operating system is Windows NT 4.0 (Service pack 3 or higher), Windows ME, or
Windows 98SE. In that case, however, the new functions of Controller Link Support Boards for the PCI Bus cannot be
used (i.e., automatic data link creation with 1:N allocation, changing data link tables with active data links, 62-node
setting for wired models, and maximum of 4000 send words).
*2. Install FinsGateway version 3 if the operating system is Windows NT 4.0 (Service pack 3 or higher), Windows ME, or
Windows 98SE. In that case, however, the new functions of Controller Link Support Boards for the PCI Bus cannot be
used (i.e., automatic data link creation with 1:N allocation, changing data link tables with active data links, 62-node
setting for wired models, and maximum of 4000 send words).
Controller Link Support Boards (for PCI Bus), Old Models
Item | Specifications | |||
---|---|---|---|---|
Model *1 | 3G8F7-CLK21-EV1 | 3G8F7-CLK21-EV1 | 3G8F7-CLK52-EV1 | |
Computer-compatible models | IBM PC/AT or compatible CPU: Intel Celeron 400 MHz or better Main memory: 128 MB minimum One or more PCI bus slots (PCI bus revision 2.0 or later, power supply: 5 V) Free hard disk space: 70 MB min. CD-ROM drive: One required for installation Display: VGA (640 x 480 (pixels) min.) (Other conditions conform to the OS.) | |||
Compatible OS *2 | FinsGateway Version2003 Windows XP Professional Windows XP Home Edition Windows 2000 Professional FinsGateway Version3 Windows XP Professional Windows XP Home Edition Windows 2000 Professional Windows NT4.0 (Service Pack 3 or higher) Windows ME Windows 98SE | |||
Weight | 104 g | 120 g (excluding mounting bracket) | 124 g (excluding mounting bracket) | |
Current consumption | 5 V in PLC | 0.35 A | 0.54 A | 0.60 A |
External 24 V | --- | 0.35 A | 0.35 A |
*1. Discontinuation models in July 2012.
*2. Install FinsGateway version 3 if the operating system is Windows NT 4.0 (Service pack 3 or higher), Windows ME, or
Windows 98SE. In that case, however, the new functions of Controller Link Support Boards for the PCI Bus cannot be
used (i.e., automatic data link creation with 1:N allocation, changing data link tables with active data links, 62-node
setting for wired models, and maximum of 4000 send words).
*2. Install FinsGateway version 3 if the operating system is Windows NT 4.0 (Service pack 3 or higher), Windows ME, or
Windows 98SE. In that case, however, the new functions of Controller Link Support Boards for the PCI Bus cannot be
used (i.e., automatic data link creation with 1:N allocation, changing data link tables with active data links, 62-node
setting for wired models, and maximum of 4000 send words).
Repeater Units
Item | Specifications | ||
---|---|---|---|
Model | CS1W-RPT01 | CS1W-RPT02 | CS1W-RPT03 |
Supported Units/Boards | All wired Controller Link Units and Boards Note: If a maximum of 62 nodes is used, models that support 62 nodes must be used. | ||
Transmission line | Wire-to-wire | Wire-to-optical (H-PCF) | Wire-to-optical (GI) |
Transmission line format | Multi-drop Tree | 1:1 type | 1:1 type |
Installation | Repeater Units are not mounted to the PLC. They are mounted separately with screws or on a DIN Track. | ||
Weight | 126 g | 113 g (excluding mounting bracket) | 116 g (excluding mounting bracket) |
Allowable power supply voltage range | 20.4 to 26.4 V DC (24 V DC -15 to 10%) | ||
Current consumption | 24 V DC at 0.06 A | 24 V DC at 0.07 A | |
Inrush current | 2.5 A max. at 24 V DC (5 ms after startup) |
Repeater Units are used to expand the Controller Link network for wired models. For Wired-to-optical Repeater Units, always use a set of two (1:1).
Optical Ring Controller Link Units and Boards cannot be connected to the optical cable section between Repeater Units.
Optical Ring Controller Link Units and Boards cannot be connected to the optical cable section between Repeater Units.
Tidak ada komentar: