CJ1W-ID201 DC Input Unit (12 to 24-VDC, 8 Points)
Name | 8-point DC Input Unit with Terminal Block |
---|---|
Model | CJ1W-ID201 |
Rated Input Voltage | 12 to 24 VDC |
Rated Input Voltage Range | 10.2 to 26.4 VDC |
Input Impedance | 2.4 kΩ |
Input Current | 10 mA typical (at 24 VDC) |
ON Voltage/ON Current | 8.8 VDC min./3 mA min. |
OFF Voltage/OFF Current | 3 VDC max./1 mA max. |
ON Response Time | 8.0 ms max. (Can be set to between 0 and 32 ms in the Setup.) *1 |
OFF Response Time | 8.0 ms max. (Can be set to between 0 and 32 ms in the Setup.) *1 |
Number of Circuits | 8 independent circuits |
Number of Simultaneously ON Points | 100% simultaneously ON |
Insulation Resistance | 20 MΩ min. between external terminals and the GR terminal (100 VDC) |
Dielectric Strength | 1,000 VAC between the external terminals and the GR terminal for 1 minute at a leakage current of 10 mA max. |
Internal Current Consumption | 80 mA max. |
Weight | 110 g max. |
Circuit Configuration | The signal names of the terminals are the device variable names. The device variable names are the names that use "Jxx" as the device name. |
External connection and terminal-device variable diagram | Polarity of the input power supply can be connected in either direction. The signal names of the terminals are the device variable names. The device variable names are the names that use "Jxx" as the device name. |
*1. The ON response time will be 20 μs maximum and OFF response time will be 400 μs maximum even if the response
time are set to 0 ms due to internal element delays.
*2. Terminal numbers A0 to A8 and B0 to B8 are used in the external connection and terminal-device variable diagrams.
They are not printed on the Units.
Note: Although 16 I/O bits (1 word) are allocated, only 8 of these can be used for external I/O.
time are set to 0 ms due to internal element delays.
*2. Terminal numbers A0 to A8 and B0 to B8 are used in the external connection and terminal-device variable diagrams.
They are not printed on the Units.
Note: Although 16 I/O bits (1 word) are allocated, only 8 of these can be used for external I/O.
CJ1W-ID211 DC Input Unit (24 VDC, 16 Points)
Name | 16-point DC Input Unit with Terminal Block | |
---|---|---|
Model | CJ1W-ID211 | |
Rated Input Voltage | 24 VDC | |
Rated Input Voltage Range | 20.4 to 26.4 VDC | |
Input Impedance | 3.3 kΩ | |
Input Current | 7 mA typical (at 24 VDC) | |
ON Voltage/ON Current | 14.4 VDC min./3 mA min. | |
OFF Voltage/OFF Current | 5 VDC max./1 mA max. | |
ON Response Time | 8.0 ms max. (Can be set to between 0 and 32 ms in the Setup.) *1 | |
OFF Response Time | 8.0 ms max. (Can be set to between 0 and 32 ms in the Setup.) *1 | |
Number of Circuits | 16 (16 points/common, 1 circuit) | |
Number of Simultaneously ON Points | 100% simultaneously ON (at 24 VDC) (Refer to the following illustration.) | |
Insulation Resistance | 20 MΩ min. between external terminals and the GR terminal (100 VDC) | |
Dielectric Strength | 1,000 VAC between the external terminals and the GR terminal for 1 minute at a leakage current of 10 mA max. | |
Internal Current Consumption | 80 mA max. | |
Weight | 110 g max. | |
Circuit Configuration | The signal names of the terminals are the device variable names. The device variable names are the names that use "Jxx" as the device name. | |
External connection and terminal-device variable diagram | Polarity of the input power supply can be connected in either direction. The signal names of the terminals are the device variable names. The device variable names are the names that use "Jxx" as the device name. |
*1. The ON response time will be 20 μs maximum and OFF response time will be 400 μs maximum even if the response
time are set to 0 ms due to internal element delays.
*2. Terminal numbers A0 to A8 and B0 to B8 are used in the external connection and terminal-device variable diagrams.
They are not printed on the Units.
time are set to 0 ms due to internal element delays.
*2. Terminal numbers A0 to A8 and B0 to B8 are used in the external connection and terminal-device variable diagrams.
They are not printed on the Units.
CJ1W-ID212 DC Input Unit (24 VDC, 16 Points)
Name | 16-point DC Input Unit with Terminal Block | |
---|---|---|
Model | CJ1W-ID212 | |
Rated Input Voltage | 24 VDC | |
Rated Input Voltage Range | 20.4 to 26.4 VDC | |
Input Impedance | 3.3 kΩ | |
Input Current | 7 mA typical (at 24 VDC) | |
ON Voltage/ON Current | 14.4 VDC min./3 mA min. | |
OFF Voltage/OFF Current | 5 VDC max./1 mA max. | |
ON Response Time | 8.0 ms max. (Can be set to between 0 and 32 ms in the Setup.) *1 | |
OFF Response Time | 8.0 ms max. (Can be set to between 0 and 32 ms in the Setup.) *1 | |
Number of Circuits | 16 (16 points/common, 1 circuit) | |
Number of Simultaneously ON Points | 100% simultaneously ON (at 24 VDC) (Refer to the following illustration.) | |
Insulation Resistance | 20 MΩ min. between external terminals and the GR terminal (100 VDC) | |
Dielectric Strength | 1,000 VAC between the external terminals and the GR terminal for 1 minute at a leakage current of 10 mA max. | |
Internal Current Consumption | 130 mA max. | |
Weight | 110 g max. | |
Circuit Configuration | The signal names of the terminals are the device variable names. The device variable names are the names that use "Jxx" as the device name. | |
External connection and terminal-device variable diagram | Polarity of the input power supply can be connected in either direction. The signal names of the terminals are the device variable names. The device variable names are the names that use "Jxx" as the device name. |
*1. The ON response time will be 15 μs maximum and OFF response time will be 90 μs maximum even if the response
time are set to 0 ms due to internal element delays.
*2. Terminal numbers A0 to A8 and B0 to B8 are used in the external connection and terminal-device variable diagrams.
They are not printed on the Units.
time are set to 0 ms due to internal element delays.
*2. Terminal numbers A0 to A8 and B0 to B8 are used in the external connection and terminal-device variable diagrams.
They are not printed on the Units.
CJ1W-ID231 DC Input Unit (24 VDC, 32 Points)
Name | 32-point DC Input Unit with Fujitsu Connector | |
---|---|---|
Model | CJ1W-ID231 | |
Rated Input Voltage | 24 VDC | |
Rated Input Voltage Range | 20.4 to 26.4 VDC | |
Input Impedance | 5.6 kΩ | |
Input Current | 4.1 mA typical (at 24 VDC) | |
ON Voltage/ON Current | 19.0 VDC min./3 mA min. | |
OFF Voltage/OFF Current | 5 VDC max./1 mA max. | |
ON Response Time | 8.0 ms max. (Can be set to between 0 and 32 in the Setup.) * | |
OFF Response Time | 8.0 ms max. (Can be set to between 0 and 32 in the Setup.) * | |
Number of Circuits | 32 (16 points/common, 2 circuits) | |
Number of Simultaneously ON Points | 75% (12 points/common) simultaneously ON (at 24 VDC) (Refer to the following illustration.) | |
Insulation Resistance | 20 MΩ min. between external terminals and the GR terminal (100 VDC) | |
Dielectric Strength | 1,000 VAC between the external terminals and the GR terminal for 1 minute at a leakage current of 10 mA max. | |
Internal Current Consumption | 90 mA max. | |
Weight | 70 g max. | |
Accessories | None | |
Circuit Configuration | The signal names of the terminals are the device variable names. The device variable names are the names that use "Jxx" as the device name. | |
External connection and terminal-device variable diagram | The input power polarity can be connected in either direction. Be sure to wire both pins A9 and A18 (COM0), and set the same polarity for both pins. Be sure to wire both pins B9 and B18 (COM1), and set the same polarity for both pins. The signal names of the terminals are the device variable names. The device variable names are the names that use "Jxx" as the device name. |
* The ON response time will be 20 μs maximum and OFF response time will be 400 μs maximum even if the response
times are set to 0 ms due to internal element delays.
Note: Observe the following restrictions when connecting to a 2-wire sensor.
• Make sure the input power supply voltage is larger than the ON voltage (19 V) plus the residual voltage of the
sensor (approx. 3 V).
• Use a sensor with a minimum load current of 3 mA min.
• Connect bleeder resistance if you connect a sensor with a minimum load current of 5 mA or higher.
times are set to 0 ms due to internal element delays.
Note: Observe the following restrictions when connecting to a 2-wire sensor.
• Make sure the input power supply voltage is larger than the ON voltage (19 V) plus the residual voltage of the
sensor (approx. 3 V).
• Use a sensor with a minimum load current of 3 mA min.
• Connect bleeder resistance if you connect a sensor with a minimum load current of 5 mA or higher.
CJ1W-ID232 DC Input Unit (24 VDC, 32 Points)
Name | 32-point DC Input Unit with MIL Connector | |
---|---|---|
Model | CJ1W-ID232 | |
Rated Input Voltage | 24 VDC | |
Rated Input Voltage Range | 20.4 to 26.4 VDC | |
Input Impedance | 5.6 kΩ | |
Input Current | 4.1 mA typical (at 24 VDC) | |
ON Voltage/ON Current | 19.0 VDC min./3 mA min. | |
OFF Voltage/OFF Current | 5 VDC max./1 mA max. | |
ON Response Time | 8.0 ms max. (Can be set to between 0 and 32 in the Setup.) * | |
OFF Response Time | 8.0 ms max. (Can be set to between 0 and 32 in the Setup.) * | |
Number of Circuits | 32 (16 points/common, 2 circuits) | |
Number of Simultaneously ON Points | 75% (12 points/common) simultaneously ON (at 24 VDC) (Refer to the following illustration.) | |
Insulation Resistance | 20 MΩ min. between external terminals and the GR terminal (100 VDC) | |
Dielectric Strength | 1,000 VAC between the external terminals and the GR terminal for 1 minute at a leakage current of 10 mA max. | |
Internal Current Consumption | 90 mA max. | |
Weight | 70 g max. | |
Accessories | None | |
Circuit Configuration | The signal names of the terminals are the device variable names. The device variable names are the names that use "Jxx" as the device name. | |
External connection and terminal-device variable diagram | The input power polarity can be connected in either direction. Be sure to wire both pins 23 and 24 (COM0), and set the same polarity for both pins. Be sure to wire both pins 3 and 4 (COM1), and set the same polarity for both pins. The signal names of the terminals are the device variable names. The device variable names are the names that use "Jxx" as the device name. |
* The ON response time will be 20 μs maximum and OFF response time will be 400 μs maximum even if the response
times are set to 0 ms due to internal element delays.
Note: Observe the following restrictions when connecting to a 2-wire sensor.
• Make sure the input power supply voltage is larger than the ON voltage (19 V) plus the residual voltage of the
sensor (approx. 3 V).
• Use a sensor with a minimum load current of 3 mA min.
• Connect bleeder resistance if you connect a sensor with a minimum load current of 5 mA or higher.
times are set to 0 ms due to internal element delays.
Note: Observe the following restrictions when connecting to a 2-wire sensor.
• Make sure the input power supply voltage is larger than the ON voltage (19 V) plus the residual voltage of the
sensor (approx. 3 V).
• Use a sensor with a minimum load current of 3 mA min.
• Connect bleeder resistance if you connect a sensor with a minimum load current of 5 mA or higher.
CJ1W-ID233 DC Input Unit (24 VDC, 32 Points)
Name | 32-point DC Input Unit with MIL Connector | |
---|---|---|
Model | CJ1W-ID233 | |
Rated Input Voltage | 24 VDC | |
Rated Input Voltage Range | 20.4 to 26.4 VDC | |
Input Impedance | 5.6 kΩ | |
Input Current | 4.1 mA typical (at 24 VDC) | |
ON Voltage/ON Current | 19.0 VDC min./3 mA min. | |
OFF Voltage/OFF Current | 5 VDC max./1 mA max. | |
ON Response Time | 8.0 ms max. (Can be set to between 0 and 32 in the Setup.) * | |
OFF Response Time | 8.0 ms max. (Can be set to between 0 and 32 in the Setup.) * | |
Number of Circuits | 32 (16 points/common, 2 circuits) | |
Number of Simultaneously ON Points | 75% (12 points/common) simultaneously ON (at 24 VDC) (Refer to the following illustration.) | |
Insulation Resistance | 20 MΩ min. between external terminals and the GR terminal (100 VDC) | |
Dielectric Strength | 1,000 VAC between the external terminals and the GR terminal for 1 minute at a leakage current of 10 mA max. | |
Internal Current Consumption | 200 mA max. | |
Weight | 70 g max. | |
Accessories | None | |
Circuit Configuration | The signal names of the terminals are the device variable names. The device variable names are the names that use "Jxx" as the device name. | |
External connection and terminal-device variable diagram | The input power polarity can be connected in either direction. Be sure to wire both pins 23 and 24 (COM0), and set the same polarity for both pins. Be sure to wire both pins 3 and 4 (COM1), and set the same polarity for both pins. The signal names of the terminals are the device variable names. The device variable names are the names that use "Jxx" as the device name. |
* The ON response time will be 15 μs maximum and OFF response time will be 90 μs maximum even if the response
times are set to 0 ms due to internal element delays.
Note: Observe the following restrictions when connecting to a 2-wire sensor.
• Make sure the input power supply voltage is larger than the ON voltage (19 V) plus the residual voltage of the
sensor (approx. 3 V).
• Use a sensor with a minimum load current of 3 mA min.
• Connect bleeder resistance if you connect a sensor with a minimum load current of 5 mA or higher.
times are set to 0 ms due to internal element delays.
Note: Observe the following restrictions when connecting to a 2-wire sensor.
• Make sure the input power supply voltage is larger than the ON voltage (19 V) plus the residual voltage of the
sensor (approx. 3 V).
• Use a sensor with a minimum load current of 3 mA min.
• Connect bleeder resistance if you connect a sensor with a minimum load current of 5 mA or higher.
CJ1W-ID261 DC Input Unit (24 VDC, 64 Points)
Name | 64-point DC Input Unit with Fujitsu Connector | |
---|---|---|
Model | CJ1W-ID261 | |
Rated Input Voltage | 24 VDC | |
Rated Input Voltage Range | 20.4 to 26.4 VDC | |
Input Impedance | 5.6 kΩ | |
Input Current | 4.1 mA typical (at 24 VDC) | |
ON Voltage/ON Current | 19.0 VDC min./3 mA min. | |
OFF Voltage/OFF Current | 5 VDC max./1 mA max. | |
ON Response Time | 8.0 ms max. (Can be set to between 0 and 32 in the Setup.) * | |
OFF Response Time | 8.0 ms max. (Can be set to between 0 and 32 in the Setup.) * | |
Number of Circuits | 64 (16 points/common, 4 circuits) | |
Number of Simultaneously ON Points | 50% (16 points/common) simultaneously ON (at 24 VDC) (Refer to the following illustrations.) | |
Insulation Resistance | 20 MΩ min. between external terminals and the GR terminal (100 VDC) | |
Dielectric Strength | 1,000 VAC between the external terminals and the GR terminal for 1 minute at a leakage current of 10 mA max. | |
Internal Current Consumption | 90 mA max. | |
Weight | 110 g max. | |
Accessories | None | |
Circuit Configuration | The signal names of the terminals are the device variable names. The device variable names are the names that use "Jxx" as the device name. | |
External connection and terminal-device variable diagram | CN1 | CN2 |
The input power polarity can be connected in either direction. Be sure to wire both pins A9 and A18 (COM0) of CN1, and set the same polarity for both pins. Be sure to wire both pins B9 and B18 (COM1) of CN1, and set the same polarity for both pins. The signal names of the terminals are the device variable names. The device variable names are the names that use "Jxx" as the device name. | The input power polarity can be connected in either direction. Be sure to wire both pins A9 and A18 (COM2) of CN2, and set the same polarity for both pins. Be sure to wire both pins B9 and B18 (COM3) of CN2, and set the same polarity for both pins. The signal names of the terminals are the device variable names. The device variable names are the names that use "Jxx" as the device name. |
* The ON response time will be 120 μs maximum and OFF response time will be 400 μs maximum even if the response
times are set to 0 ms due to internal element delays.
Note: Observe the following restrictions when connecting to a 2-wire sensor.
• Make sure the input power supply voltage is larger than the ON voltage (19 V) plus the residual voltage of the
sensor (approx. 3 V).
• Use a sensor with a minimum load current of 3 mA min.
• Connect bleeder resistance if you connect a sensor with a minimum load current of 5 mA or higher.
times are set to 0 ms due to internal element delays.
Note: Observe the following restrictions when connecting to a 2-wire sensor.
• Make sure the input power supply voltage is larger than the ON voltage (19 V) plus the residual voltage of the
sensor (approx. 3 V).
• Use a sensor with a minimum load current of 3 mA min.
• Connect bleeder resistance if you connect a sensor with a minimum load current of 5 mA or higher.
CJ1W-ID262 DC Input Unit (24 VDC, 64 Points)
Name | 64-point DC Input Unit with MIL Connector | |
---|---|---|
Model | CJ1W-ID262 | |
Rated Input Voltage | 24 VDC | |
Rated Input Voltage Range | 20.4 to 26.4 VDC | |
Input Impedance | 5.6 kΩ | |
Input Current | 4.1 mA typical (at 24 VDC) | |
ON Voltage/ON Current | 19.0 VDC min./3 mA min. | |
OFF Voltage/OFF Current | 5 VDC max./1 mA max. | |
ON Response Time | 8.0 ms max. (Can be set to between 0 and 32 in the Setup.) * | |
OFF Response Time | 8.0 ms max. (Can be set to between 0 and 32 in the Setup.) * | |
Number of Circuits | 64 (16 points/common, 4 circuits) | |
Number of Simultaneously ON Points | 50% (8 points/common) simultaneously ON (at 24 VDC) (Refer to the following illustrations.) | |
Insulation Resistance | 20 MΩ min. between external terminals and the GR terminal (100 VDC) | |
Dielectric Strength | 1,000 VAC between the external terminals and the GR terminal for 1 minute at a leakage current of 10 mA max. | |
Internal Current Consumption | 90 mA max. | |
Weight | 110 g max. | |
Accessories | None | |
Circuit Configuration | The signal names of the terminals are the device variable names. The device variable names are the names that use "Jxx" as the device name. | |
External connection and terminal-device variable diagram | CN1 | CN2 |
The input power polarity can be connected in either direction. Be sure to wire both pins 23 and 24 (COM0) of CN1, and set the same polarity for both pins. Be sure to wire both pins 3 and 4 (COM1) of CN1, and set the same polarity for both pins. The signal names of the terminals are the device variable names. The device variable names are the names that use "Jxx" as the device name. | The input power polarity can be connected in either direction. Be sure to wire both pins 23 and 24 (COM2) of CN2, and set the same polarity for both pins. Be sure to wire both pins 3 and 4 (COM3) of CN2, and set the same polarity for both pins. The signal names of the terminals are the device variable names. The device variable names are the names that use "Jxx" as the device name. |
* The ON response time will be 120 μs maximum and OFF response time will be 400 μs maximum even if the response
times are set to 0 ms due to internal element delays.
Note: Observe the following restrictions when connecting to a 2-wire sensor.
• Make sure the input power supply voltage is larger than the ON voltage (19 V) plus the residual voltage of the
sensor (approx. 3 V).
• Use a sensor with a minimum load current of 3 mA min.
• Connect bleeder resistance if you connect a sensor with a minimum load current of 5 mA or higher.
times are set to 0 ms due to internal element delays.
Note: Observe the following restrictions when connecting to a 2-wire sensor.
• Make sure the input power supply voltage is larger than the ON voltage (19 V) plus the residual voltage of the
sensor (approx. 3 V).
• Use a sensor with a minimum load current of 3 mA min.
• Connect bleeder resistance if you connect a sensor with a minimum load current of 5 mA or higher.
CJ1W-IA201 AC Input Unit (200 VAC, 8 Points)
Name | 8-point AC Input Unit with Terminal Block |
---|---|
Model | CJ1W-IA201 |
Rated Input Voltage | 200 to 240 VAC 50/60 Hz |
Rated Input Voltage Range | 170 to 264 VAC |
Input Impedance | 21 kΩ (50 Hz), 18 kΩ (60 Hz) |
Input Current | 9 mA typical (at 200 VAC, 50 Hz), 11 mA typical (at 200 VAC, 60 Hz) |
ON Voltage/ON Current | 120 VAC min./4 mA min. |
OFF Voltage/OFF Current | 40 VAC max./2 mA max. |
ON Response Time | 18.0 ms max. (default setting: 8 ms) *1 |
OFF Response Time | 48.0 ms max. (default setting: 8 ms) *1 |
Number of Circuits | 8 (8 points/common, 1 circuit) |
Number of Simultaneously ON Points | 100% (8 points/common) simultaneously ON |
Insulation Resistance | 20 MΩ min. between external terminals and the GR terminal (500 VDC) |
Dielectric Strength | 2,000 VAC between the external terminals and the GR terminal for 1 minute at a leakage current of 10 mA max. |
Internal Current Consumption | 80 mA max. |
Weight | 130 g max. |
Accessories | None |
Circuit Configuration | The signal names of the terminals are the device variable names. The device variable names are the names that use "Jxx" as the device name. |
External connection and terminal-device variable diagram | The signal names of the terminals are the device variable names. The device variable names are the names that use "Jxx" as the device name. |
*1. Can be set to 0 ms, 0.5 ms, 1 ms, 2 ms, 4 ms, 8 ms, 16 ms, or 32 ms in the settings. When the response times have
been set to 0 ms, the ON response time will be 10 ms maximum and the OFF response time will be 55 ms maximum
due to internal element delays.
*2. Terminal numbers A0 to A8 and B0 to B8 are used in the external connection and terminal-device variable diagrams.
They are not printed on the Units.
Note: Although 16 I/O bits (1 word) are allocated, only 8 of these can be used for external I/O.
been set to 0 ms, the ON response time will be 10 ms maximum and the OFF response time will be 55 ms maximum
due to internal element delays.
*2. Terminal numbers A0 to A8 and B0 to B8 are used in the external connection and terminal-device variable diagrams.
They are not printed on the Units.
Note: Although 16 I/O bits (1 word) are allocated, only 8 of these can be used for external I/O.
CJ1W-IA111 AC Input Unit (100 VAC, 16 points)
Name | 16-point AC Input Unit with Terminal Block |
---|---|
Model | CJ1W-IA111 |
Rated input voltage | 100 to 120 VAC 50/60 Hz *2 |
Rated Input Voltage Range | 85 to 132 VAC |
Input Impedance | 14.5 kΩ (50 Hz), 12 kΩ (60 Hz) |
Input Current | 7 mA typical (at 100 VAC, 50 Hz), 8 mA typical (at 100 VAC, 60 Hz) |
ON Voltage/ON Current | 70 VAC min./4 mA min |
OFF Voltage/OFF Current | 20 VAC max./2 mA max |
ON Response Time | 18 ms max. (default setting: 8 ms) *1 |
OFF Response Time | 48 ms max. (default setting: 8 ms) *1 |
Number of Circuits | 16 (16 points/common, 1 circuit) |
Number of Inputs ON Simultaneously | 100% simultaneously ON (16 points/common) |
Insulation Resistance | 20 MΩ min. between external terminals and the GR terminal (500 VDC) |
Dielectric Strength | 2,000 VAC between the external terminals and the GR terminal for 1 minute at a leakage current of 10 mA max. |
Internal Current Consumption | 90 mA max. |
Weight | 130 g max. |
Accessories | None |
Circuit Layout | The signal names of the terminals are the device variable names. The device variable names are the names that use "Jxx" as the device name. |
External connection and terminal-device variable diagram | The signal names of the terminals are the device variable names. The device variable names are the names that use "Jxx" as the device name. |
*1. Can be set to 0 ms, 0.5 ms, 1 ms, 2 ms, 4 ms, 8 ms, 16 ms, or 32 ms in the settings. When the response times have
been set to 0 ms, the ON response time will be 10 ms maximum and the OFF response time will be 55 ms maximum
due to internal element delays.
*2. Use an input voltage of 90 VAC or higher when connecting 2-wire sensors.
*3. Terminal numbers A0 to A8 and B0 to B8 are used in the external connection and terminal-device variable diagrams.
They are not printed on the Units.
been set to 0 ms, the ON response time will be 10 ms maximum and the OFF response time will be 55 ms maximum
due to internal element delays.
*2. Use an input voltage of 90 VAC or higher when connecting 2-wire sensors.
*3. Terminal numbers A0 to A8 and B0 to B8 are used in the external connection and terminal-device variable diagrams.
They are not printed on the Units.
Bit Allocations for Input Unit
8-point Input Unit
Allocated CIO word | Signal name (CJ/NJ) | |
---|---|---|
CIO | Bit | |
Wd m (Input) | 00 | IN0/Jxx_Ch1_In00 |
01 | IN1/Jxx_Ch1_In01 | |
: | : | |
06 | IN6/Jxx_Ch1_In06 | |
07 | IN7/Jxx_Ch1_In07 | |
08 | - | |
09 | - | |
: | : | |
14 | - | |
15 | - |
16-point Input Unit
Allocated CIO word | Signal name (CJ/NJ) | |
---|---|---|
CIO | Bit | |
Wd m (Input) | 00 | IN0/Jxx_Ch1_In00 |
01 | IN1/Jxx_Ch1_In01 | |
: | : | |
14 | IN14/Jxx_Ch1_In14 | |
15 | IN15/Jxx_Ch1_In15 |
32-point Input Unit
Allocated CIO word | Signal name (CJ/NJ) | |
---|---|---|
CIO | Bit | |
Wd m (Input) | 00 | IN0/Jxx_Ch1_In00 |
01 | IN1/Jxx_Ch1_In01 | |
: | : | |
14 | IN14/Jxx_Ch1_In14 | |
15 | IN15/Jxx_Ch1_In15 | |
Wd m+1 (Input) | 00 | IN0/Jxx_Ch2_In00 |
01 | IN1/Jxx_Ch2_In01 | |
: | : | |
14 | IN14/Jxx_Ch2_In14 | |
15 | IN15/Jxx_Ch2_In15 |
64-point Input Unit
Allocated CIO word | Signal name (CJ/NJ) | |
---|---|---|
CIO | Bit | |
Wd m (Input) | 00 | IN0/Jxx_Ch1_In00 |
01 | IN1/Jxx_Ch1_In01 | |
: | : | |
14 | IN14/Jxx_Ch1_In14 | |
15 | IN15/Jxx_Ch1_In15 | |
Wd m+1 (Input) | 00 | IN0/Jxx_Ch2_In00 |
01 | IN1/Jxx_Ch2_In01 | |
: | : | |
14 | IN14/Jxx_Ch2_In14 | |
15 | IN15/Jxx_Ch2_In15 | |
Wd m+2 (Input) | 00 | IN0/Jxx_Ch3_In00 |
01 | IN1/Jxx_Ch3_In01 | |
: | : | |
14 | IN14/Jxx_Ch3_In14 | |
15 | IN15/Jxx_Ch3_In15 | |
Wd m+3 (Input) | 00 | IN0/Jxx_Ch4_In00 |
01 | IN1/Jxx_Ch4_In01 | |
: | : | |
14 | IN14/Jxx_Ch4_In14 | |
15 | IN15/Jxx_Ch4_In15 |