Functional and Performance Specifications
Item | Specifications | |
---|---|---|
Unit model number | CJ1W-SPU01-V2 | |
Applicable CPU Units | CJ Series | |
Unit classification | CPU Bus Unit | |
Unit number | 0 to F | |
Mounting location | CPU Backplane or CJ-series Expansion Backplane | |
No. of Units per PLC | 16 Unit max. | |
Interfaces | PC card slot | Memory Card slot Used by mounting a Memory Card. * |
COMM port | Connects to an uninterruptive power supply (UPS) for detection of power failure. | |
Ethernet (LAN) ports | One port (10/100Base-TX, RJ45 Modular Connector) | |
UPS power failure input | None (UPS connected to COMM port.) | |
Settings and operation | Unit number switch (UNIT) | Rotary switch: Sets the unit number of the Unit as a CPU Bus Unit. |
Select switch (SELECT) | Toggle switch: Sets the number of the command to execute. | |
Enter button (ENTER) | Pushbutton switch: Confirms and starts execution of the command number set using the select switch. | |
DIP switch (DIPSW) | DIP switch: System settings | |
Card button | Pressed to release the Memory Card inserted in the Memory Card slot. The Memory Card can then be removed. | |
Indications | LED indicators | RUN, ERC, ERH, COMM, LAN1, LAN2, and CARD |
7-segment display | Displays error information and operating status of the SPU Unit. Displays the command number set on the select switch. Displays the IP address. Display other information. | |
Functions | Sampling Saving files Network communications Recipe function | |
Operating modes | Data Storage Mode and Sampling Mode (Either mode can be selected with the Change Operating Mode command.) | |
Current consumption | 5 VDC, 560 mA max. (SPU Unit only) Other: Memory Card (HMC-EF[][][]): 120 mA max. (Supplied from Power Supply Unit.) | |
Dimensions | 51 × 90 × 65 mm (W × H × D) | |
Weight | 180 g max. |
* Use the HMC-EF[][][] Memory Card from OMRON. Normal operation may not be possible with any other compact flash cards.
General Specifications: Specifications conform to the general specifications of the CJ-series CPU Units.
Detailed Specifications
Item | Specifications | |||
---|---|---|---|---|
Sampling | Sampling Mode | Sampling patterns | Realtime sampling: 1 pattern Normal sampling: Up to 3 patterns | |
Starting methods | Any one of the following methods can be used: Start automatically when SPU Unit is started. Start with an SPU-Console operation. Start with the SPU Unit's front-panel command buttons. (Specify the command number.) Start from the CPU Unit's ladder program. | |||
Interval | User-specified intervals: *1 Realtime sampling: 5 ms min. Normal sampling: 100 ms min. | |||
Data Storage Mode (Unit Ver. 1.2 or later) | Data Collection Patterns | Basic Collection Pattern: 1 pattern (required) Data Collection Patterns: Up to 64 patterns | ||
Starting methods | Basic Collection Pattern (required) | Any one of the following methods can be used: Start when a specified event occurs. (Use a memory event or scheduled event. For details, see the description of Data Collection Patterns 1 to 64 below.) Start automatically when SPU Unit is started. Start with an SPU-Console operation. Start with the SPU Unit's front-panel command buttons. (Specify the command number.) Start from the CPU Unit's ladder program. | ||
Data Collection Patterns 1 to 64 | Either of the following methods can be used to start when an event occurs: Memory events: Start when a CPU Unit bit or word value matches a specified condition. Up to 500 memory events can be specified. Scheduled events: Start at a specified time or time interval. Up to 16 scheduled events can be specified. | |||
Interval | User-specified intervals: *2 *3 Basic Collection Pattern: 5 ms min. Data Collection Patterns: 100 ms min. | |||
Data Storage Mode (Unit Ver. 2.0 or later) | Copy option | Basic Collection Pattern: Cannot be set. Data Collection Patterns: Up to 10 patterns. | ||
Shared Sampling Mode and Data Storage Mode settings | Applicable CPU Unit I/O memory areas | CIO Area, WR Area, HR Area, AR Area, DM Area, and EM Area banks 0 to C (CJ2: 0 to 18) | ||
Specifying I/O memory areas | Specify the desired CPU Unit I/O memory area (data area) with a variable. The data type can be specified with the variable. The variables can be managed in groups. | |||
Variable data types | BOOL, INT, UINT, DINT, UDINT, REAL, LREAL, STRING, CHANNEL, UINT BCD, UDINT BCD, WORD, DWORD, CHANNEL BLOCK | |||
Maximum number of variables | 7,776 words total for all variables | |||
Record Condition setting | Set whether or not to use a record condition. If a record condition is used, sampling data is stored within the SPU Unit only when the record condition is met. For example, sampling data can be recorded only while a specified bit is ON or a specified word contains a particular value (comparison). | |||
Data exchange with the CPU Unit | CPU Bus Unit Area CPU Unit to SPU Unit: Command execution (such as starting/stopping sampling, clearing a sampling file, or saving a sampling file). SPU Unit to CPU Unit: SPU Unit status information | |||
Saving files | Collected data file format | CSV files | Indices (record number), time stamps (hh:mm:ss:ms), ns, sampling indices (serial numbers starting at 0 when sampling is started), data for each symbol delimited with comma, records delimited with carriage returns | |
Record contents | ||||
Number of sampling result records stored in one file | Any one of the following methods can be used. The number of records can be specified. A time period can be specified. (The number of records is calculated automatically from the time period and interval between samples.) With a version 1.2 or later SPU Unit, the number of records can be left unspecified. (In this case, data is added to the file until data collection is stopped. Records are added to one file from the start of data collection until the end.) | |||
Scaling | Instead of directly storing the values collected from the CPU Unit's I/O memory, the collected values can be scaled with a linear equation or upper/lower limit range before storage (unit version 1.2 or later). | |||
File size | 2 GB per file | |||
Record size | Specified by user. | |||
Number of records | Specified by user or calculated automatically. | |||
Saving method | Data can be saved to a single file or multiple files (up to 1,200 files). | |||
Network communications | Windows network shared folders | Files in the Memory Card inserted in the PC card slot in the SPU Unit can be shared with a Windows XP, Vista, 7 or 8 personal computer. | ||
FTP | FTP server/client provided. | |||
FINS communications | FINS server to execute FINS command Routing to transfer FINS messages | |||
Recipe function | Data Storage Mode (Unit Ver. 2.0 or later) | Number of fields | 10,000 | |
Recipe files | File format: CSV The file size is restricted by the size of file that can be stored in the recipe folder. Records: Specified by the user. | |||
Number of records | No limit, but restricted by the file size that can be stored in the recipe folder. | |||
Writing method | Conversion method: Each field is written to the specified address in the specified data type. Continuous region method: Data written to continuos memory addresses. | |||
Searching for recipe keys | Searching within files: The text string that was passed as the key is searched for in the target search columns in the recipe files and the rows for any matches that are found are extracted as recipe data. Searching for file names: The text string that was passed as the key is searched for in the recipe file names (i.e., a search is made for key.csv), and the files with matching files names are used as recipe files just like previous versions. Key list search: A search is made for recipe keys with the method used for unit version 2.0. |
*1. In both cases, the sampling cannot be performed faster than the CPU Unit's cycle time. The actual sampling interval
will always be longer than the CPU Unit's cycle time even if the sampling interval is set shorter than the cycle time.
*2. The Data Collection Patterns use the data collected by the Basic Collection Pattern, so the data will be collected at the
Basic Collection Pattern’s interval even if the Data Collection Pattern’s interval is set shorter than the Basic Collection
Pattern’s interval.
*3. The actual Basic Collection Pattern interval will always be longer than the CPU Unit's cycle time even if the sampling
interval is set shorter than the cycle time.
Note: For details, refer to "CS1W-SPU01/SPU02-V2, CJ1W-SPU01-V2 SPU Units Operation Manual"(Cat. No. V236).
will always be longer than the CPU Unit's cycle time even if the sampling interval is set shorter than the cycle time.
*2. The Data Collection Patterns use the data collected by the Basic Collection Pattern, so the data will be collected at the
Basic Collection Pattern’s interval even if the Data Collection Pattern’s interval is set shorter than the Basic Collection
Pattern’s interval.
*3. The actual Basic Collection Pattern interval will always be longer than the CPU Unit's cycle time even if the sampling
interval is set shorter than the cycle time.
Note: For details, refer to "CS1W-SPU01/SPU02-V2, CJ1W-SPU01-V2 SPU Units Operation Manual"(Cat. No. V236).
SPU-Console (Setting/Monitoring Software) Specifications
The SPU-Console is a software product used for OMRON's Storage and Processing Unit (called the SPU Unit) to set and operate the SPU Unit, monitor operating status/errors, display trend graphs, and perform other operations from a personal computer.
SPU-Console Specifications
Item | Specifications | |
---|---|---|
Model number | WS02-SPTC1-V2 (SPU-Console Ver. 2.2) | |
System requirements | Computer hardware | Computer that meets the system requirements for Microsoft Windows |
CD-ROM drive | Required for installation. | |
Display | Super VGA (800 × 600) or better high-resolution video adapter and monitor | |
Mouse | Must conform to the models supported by the applicable OS. | |
Network card | A separate Ethernet network card is required for computers that do not have a LAN port. | |
OS | Microsoft Windows XP Home Edition Microsoft Windows XP Professional Microsoft Windows Vista Microsoft Windows 7 (32bit/64bit) Microsoft Windows 8 (32bit/64bit) | |
Application platform | Microsoft.NET Framework Version 1.1 Microsoft.NET Framework Version 2.0 | |
Communications platform | FinsGateway Version 2003 | |
Functions | Unit information, Unit setup, variable settings, collection pattern settings, event settings, recipe settings, trend graphs, and reports | |
Unit information | Monitor | SPU Unit operating status and error information are displayed. |
Operation | Operations, such as starting sampling | |
Unit setup | IP network settings | |
FINS network settings | ||
Variable settings | Setting items to sample (by specifying I/O memory addresses using variables) | |
Collection pattern settings | Collection pattern settings (period, file designations for saving, etc.) | |
Recipe settings (Data Storage Mode) | Recipe settings (recipe file, write destination, key, etc.) | |
Event settings (in Data Storage Mode) | Memory event settings | Settings for conditions according to changes in memory (e.g., bits turning ON) |
Scheduler settings | Settings for schedules (e.g., specific times, time intervals) | |
Trend graphs | Historical trends | CSV files are read and displayed. |
Realtime trends (Sampling Mode) | Current sampling data is read and displayed in trend graphics in real time. |
Software Package Contents
The WS02-SPTC1-V2 contains the following software and data.
SPU-Console Execution Program
The program that performs SPU Unit settings and operations.
Microsoft .NET Framework Version 1.1 Redistribution Package
Microsoft .NET Framework Version 1.1 is required to run the SPU-Console. The Microsoft .NET Framework Version 1.1 Redistribution Package provided in the package can be used to install Microsoft .NET Framework in the computer.
SPU Unit System Data
This system data is transferred to the SPU Unit.
FinsGateway Version 2003
This communications middleware is required to run the SPU-Console.
Manual Data
The manual data includes the SPU Unit Operation Manual (Cat. No. V236), the SPU-Console Operation Manual (Cat. No. V230), the SPU-Console Version 1.3 Operation Manual (Cat. No. V231), and the SPU-Console Version 2.2 Operation Manual (Cat. No. V237) in PDF (portable document format).