- Analog Input Unit (High speed type) , I/O 4 inputs, Signal range 1 to 5 V (1/10,000) 0 to 10 V (1/20,000) -5 to 5 V (1/20,000) -10 to 10 (1/40,000) and 4 to 20 mA (1/10,000) , Conversion period 20 us/1 point 25 us/2 point 30 us/3 points 35 us/4 points The Direct conversion is perovided *1, Accuracy at ambient temperature of 25 C Voltage +0.2% of F.S. Current +0.4% of F.S. , Current consumption (A) 5 v 0.52 : CJ1W-AD042
- Analog Inputs Units, I/O points 8 inputs, Signal range 1 to 5 V 0 tO 5 V 0 to 1o V -10 to 10 V 4 to 20 mA, Resolution 1/4,000 (Settable to 1/8,000)*2 , Conversion period 1 ms/point (250 us/point can also be set.)*2 , Accuracy at ambient temperature of 25 C Voltage +0.2% of F.S. Current +0.4 of F.S.*3 Current consumption (A) 5 V 0.42 : CJ1W-AD081-V1
- Analog Inputs Units, I/O points 4 inputs, Signal range 1 to 5 V 0 to 5 V 0 to 10 V -10 to 10 V 4 to 20 mA , Resolution 1/4,000 (Settable to 1/8,000)*2, Conversion period 1 ms/point (250 us/point can also be set )*2 , Accuracy at ambient temperature of 25 C Voltage +0.2% of F.S. Current +0.4% of F.S.*3,Current consumption (A) 5 V 0.42 : CJ1W-AD041-V1