Features
- Improved reliability and easy maintenance
Spring clamp terminals provide high reliability and easy wiring. Shutoff circuit (hardware) securely provides emergency output shutoffs. The inverter with the safety stop function can comply with the safety standard without incurring too much cost. Parameter writing/reading can be restricted with a 4-digit password. The lives of the cooling fan and capacitor have been extended. Using the self-diagnosis function, the part life warning can be output and the degree of deterioration can be monitored to prevent malfunction.
- Pursuing the best performance
The General-purpose magnetic flux vector control and the auto tuning function enable operation in applications that require large starting torque. (150% 1Hz, 200% 3Hz (3.7K or lower with the slip compensation))
- Easy-to-use (Pursing the easy operation)
The non-slip, adaptable scroll speed setting dial allows for quick jumps or precise increments based on turning speed. Setting can be made easily from a personal computer with FR Configurator. An enclosure surface operation panel, which can be attached on an enclosure surface, is available as an option. Operation panel for the FR-E500 series inverters can be also connected . The inverters with 0.4K or higher capacity have built-in regenerative brake transistors, and their usage can be extended to a lift application.
- Environmentally friendly
Filter options reduce the electromagnetic noise generated at the inverter and enables the compliance with the harmonic suppression guidelines of japan.
Model
FR-D740[]-0.4K
Specifications
Control method : Soft-PWM control, high carrier frequency PWM control (V/F control, General-purpose magnetic flux vector control, Optimum excitation control can be selected)
Starting torque : 150% 1Hz , 200% 3 Hz (3.7K or lower) with General-purpose magnetic flux vector control and slip compensation.
Output frequency range: 0.2 to 400Hz
Regenerative /deceleration time setting : 0.1K/0.2K....150%, 0.4/0.75K ...100%, 1.5K...50%, 2.2K or higher ...20%
Accelerations/deceleration time setting : 0 to 3600s (up to two types of accelerations can be set individually)
Multi-speed : 15 speed
Speed command : 0 to 5VDC, 0 to 10VDC, 4 to 20mA, digital input with setting dial, digital setting with operation panel or parameter unit.
Alarm output : 1 changeover contact output (230VAC 0.3A 30VDC 0.3A) open collector output
Output signal : One type of open collector and one type of contact output ( 1 changeover contact) can be selected from inverter running, up to frequency, frequency detection, output current detection, operation ready, overload warning, fault output, and alarm, etc.
Monitor function : One monitored item can be selected from output frequency, motor current (steady or peak value), output voltage, frequency setting value, converter output voltage, regenerative brake duty, and output power, etc. Pulse train output (1440 pulses/s 1mA)
Restart after instantaneous power failure : Available (reduced voltage (frequency search selectable))
Communication function : RS-485 supported (Modbus-RTU) as standard.