Safe, easy and cost-effective M2M communication

The FP Modem-56k unit expands the number of communication alternatives available to FP series PLCs, e.g. dial-up, dedicated/leased line and multidrop network communication. If the PSTN supports text message service, the PLC can even send and receive short text messages.
 
A Windows driver allows the FP Modem-56k to be used together with various Windows software, such as OPC, SCADA, etc.

Enjoy the plug & play convenience of FP Modem-56k to facilitate modem communication between PLCs or between your PLC and PC.

Outstanding features for industrial telecontrol

  • Extremely compact 
  • Operating voltage 24V DC 
  • Attachable to a 35mm DIN rail 
  • Maximum line speed of up to 56kbit/s 
  • Leased line mode (pier-to-pier) up to 20km at 33.6kbit/s 
  • Multidrop leased line mode according to V.23 at 1200bit/s 
  • DCD output for connection to the digital input of a PLC 
  • PSTN text message send + receive 
  • CLIP decoder for calling line identification and callback 
  • Serial data communication interfaces RS232C and RS485 are built in
Combining the FP Modem-56k with the FP Web-Server expands the horizon of telecontrol even more, e.g. access the Internet, send e-mails, dial up an FP Web-Server for local or wide area network access, etc.
Compliant and certified for the following countries: Belgium, Denmark, Germany, Finland, France, Greece, Ireland, Italy, Luxembourg, Netherlands, Norway, Austria, Portugal, Sweden, Switzerland, Spain, United Kingdom and US.
User libraries, e.g. Panasonic CONTROL LIBRARY “MODEM” (NCL-CM-LIB), make the integration of communication functions into PLC programs easy, saving programming time and money.

Specifications

Specifications
Part numberFP-MODEM-56k
Operating voltage24V DC (10.8 to 26.6V DC)
Current consumptionApprox. 50mA
LEDsPower, DCD (Carrier Detect), RI (Ring), RTS (Request To Send), RxD, TxD (Data)
Ambient temperature0 to +55°C
Connection to PLC, PC or FP Web-ServerRS232C (Sub-D 9-pin female), RS485 (Phoenix screw terminal)
Connection to the telephone networkRJ12 jack and RJ12 - RJ12 cable; national adapter is not enclosed
Carrier detect connectionPhoenix screw terminal
Error correctionV.42, LAPM, MNP
Data compressionV.42bis, V.44
Dialing methodPulse dialing, tone dialing (DTMF)
Control/OperationExtended AT command set, Hayes compatible (V.250)
Operation modesAutomatic selection, V.21, V.22, V.23, V.22bis, V.32, V.32bis, V.34, V.90, V.92
DTE speed (RS232C baud rate)300, 600, 1200, 2400, 4800, 9600, 19200, 38400, 57600, 115200bit/s
Line transmission speedUp to 56kbit/s with V.90
Certification, approvalsCE mark (ES-203021 approval) 
US approval (US:CO4MM05B077FP)
Dimensions (WxHxD)25 x 90 x 64mm


Product downloads

Cable drawings

DescriptionRelease dateFile sizeLanguage
FP Modem-56k RS232C Cable for FP Series PLC COM Port with 9-pin Sub-D connector, 0.5m, CABMODPLC2112005-06-2756 KBEnglish
FP Modem-56k RS232C cable for FP Series PLC COM port with screw terminal, 0.5m, CABMOD111D2007-03-2262 KBEnglish
RS232 cable between FP Modem-56k and Tool port, 2m, CABMODPLC311D2007-03-2280 KBEnglish

Data sheets

DescriptionRelease dateFile sizeLanguage
FP Modem-56k Unit2.2 MBEnglish

Manuals

DescriptionRelease dateFile sizeLanguage
Announcement of discontinued production (FP-MODEM-EU unit)2010-03-01250 KBEnglish
FP Modem-56k Technical Manual2010-02-013.22 MBEnglish

Shortforms

DescriptionRelease dateFile sizeLanguage
Short Form Programmable Logic Controllers2016-10-202.47 MBEnglish