Safe, easy and cost-effective M2M communication
The FP Modem-56k unit expands the number of communication alternatives available to FP series PLCs, e.g. dial-up, dedicated/leased line and multidrop network communication. If the PSTN supports text message service, the PLC can even send and receive short text messages.
A Windows driver allows the FP Modem-56k to be used together with various Windows software, such as OPC, SCADA, etc.
Enjoy the plug & play convenience of FP Modem-56k to facilitate modem communication between PLCs or between your PLC and PC.
Outstanding features for industrial telecontrol
- Extremely compact
- Operating voltage 24V DC
- Attachable to a 35mm DIN rail
- Maximum line speed of up to 56kbit/s
- Leased line mode (pier-to-pier) up to 20km at 33.6kbit/s
- Multidrop leased line mode according to V.23 at 1200bit/s
- DCD output for connection to the digital input of a PLC
- PSTN text message send + receive
- CLIP decoder for calling line identification and callback
- Serial data communication interfaces RS232C and RS485 are built in
Combining the FP Modem-56k with the FP Web-Server expands the horizon of telecontrol even more, e.g. access the Internet, send e-mails, dial up an FP Web-Server for local or wide area network access, etc.
Compliant and certified for the following countries: Belgium, Denmark, Germany, Finland, France, Greece, Ireland, Italy, Luxembourg, Netherlands, Norway, Austria, Portugal, Sweden, Switzerland, Spain, United Kingdom and US.
User libraries, e.g. Panasonic CONTROL LIBRARY “MODEM” (NCL-CM-LIB), make the integration of communication functions into PLC programs easy, saving programming time and money.
Specifications
Specifications | |
---|---|
Part number | FP-MODEM-56k |
Operating voltage | 24V DC (10.8 to 26.6V DC) |
Current consumption | Approx. 50mA |
LEDs | Power, DCD (Carrier Detect), RI (Ring), RTS (Request To Send), RxD, TxD (Data) |
Ambient temperature | 0 to +55°C |
Connection to PLC, PC or FP Web-Server | RS232C (Sub-D 9-pin female), RS485 (Phoenix screw terminal) |
Connection to the telephone network | RJ12 jack and RJ12 - RJ12 cable; national adapter is not enclosed |
Carrier detect connection | Phoenix screw terminal |
Error correction | V.42, LAPM, MNP |
Data compression | V.42bis, V.44 |
Dialing method | Pulse dialing, tone dialing (DTMF) |
Control/Operation | Extended AT command set, Hayes compatible (V.250) |
Operation modes | Automatic selection, V.21, V.22, V.23, V.22bis, V.32, V.32bis, V.34, V.90, V.92 |
DTE speed (RS232C baud rate) | 300, 600, 1200, 2400, 4800, 9600, 19200, 38400, 57600, 115200bit/s |
Line transmission speed | Up to 56kbit/s with V.90 |
Certification, approvals | CE mark (ES-203021 approval) US approval (US:CO4MM05B077FP) |
Dimensions (WxHxD) | 25 x 90 x 64mm |
Product downloads
Cable drawings
Description | Release date | File size | Language |
---|---|---|---|
FP Modem-56k RS232C Cable for FP Series PLC COM Port with 9-pin Sub-D connector, 0.5m, CABMODPLC211 | 2005-06-27 | 56 KB | English |
FP Modem-56k RS232C cable for FP Series PLC COM port with screw terminal, 0.5m, CABMOD111D | 2007-03-22 | 62 KB | English |
RS232 cable between FP Modem-56k and Tool port, 2m, CABMODPLC311D | 2007-03-22 | 80 KB | English |
Data sheets
Description | Release date | File size | Language |
---|---|---|---|
FP Modem-56k Unit | 2.2 MB | English |
Manuals
Description | Release date | File size | Language |
---|---|---|---|
Announcement of discontinued production (FP-MODEM-EU unit) | 2010-03-01 | 250 KB | English |
FP Modem-56k Technical Manual | 2010-02-01 | 3.22 MB | English |
Shortforms
Description | Release date | File size | Language |
---|---|---|---|
Short Form Programmable Logic Controllers | 2016-10-20 | 2.47 MB | English |
Tidak ada komentar:
Posting Komentar