Kontak Kami

KONTAK KAMI : Telpon : 02126071413 Hp/WhatsApp : 081212269831 Perwakilan Jakarta : Gedung LTC Glodok Lantai 1 Blok C30 No.31 Jl.Hayam Wuruk No.127 Jakarta , Indonesia

Senin, 22 Oktober 2018

MITSUBISHI QJ71PB93D



Required Manuals
Model Number
Description
Contents
Included?
Stocked Item
IB(NA)0800324
Profibus-DP Master Module User’s Manual (Hardware)
Covers basic information on QJ71PB92V
Yes
-
SH(NA)080572
Profibus-DP Master Module User’s Manual
Covers using the QJ71PB92V
No
-
Note: Many of these manuals are available by free download from our website, www.meau.com
PROFIBUS-DP Master Module Performance Specifications
Model Number
QJ71PB92V
Stocked Item
S
Certification
UL • cUL • CE
PROFIBUS-DP Station Type
Class 1 master station
External Standard and Characteristics
EIA-RS485 compatible
Communication Cable
Shielded twisted pair cable
Network Configuration
Bus type (tree type if repeater is used)
Transmission Rate (*1) Maximum Transmission Distance (*2)
Transmission Rate
Transmission Distance
Max. Transmission Distance when Using Repeater (*2)
9.6kbps
1200m/segment
4800m/network
19.2kbps
93.75kbps
187.5kbps
1000m/segment
4000m/network
500kbps
400m/segment
1600m/network
1.5Mbps
200m/segment
800m/network
3Mbps
100m/segment
400m/network
6Mbps
12Mbps
Max. No. of Repeaters In a Path
3 repeaters
Max. No. of Stations
32 stations per segment (including repeaters)
Max. No. Slave Stations
125 slaves per single QJ71PB92V master
I/O Data Size
Max. 8192 words (4096 input words, 4096 output words)
I/O Device Points Occupied
32 points
5VDC Internal Current Consumption
0.57A
Weight (kg)
0.13
Base Unit Slots Occupied
1
Notes:
  1. Transmission rate control is within ±0.2% (compatible with IEC 61158-2).
  2. The “maximum transmission distance” in the above table is an example which assumes that 3 repeaters are being used. If more repeaters are used to extend the distance, the maximum transmission distance would be calculated as follows: [Maximum transmission distance (m/network)] = [Number of repeaters +1] x [transmission distance (m/segment)]
PROFIBUS-DP Device Level Network Slave Module
The QJ71PB93D allows a Q Series system to be connected to a third party PROFIBUS-DP network as a slave controller. This allows distributed processing systems to be built where local control of the application can be given to the Q Series, which then supplies information back to a supervisory controller. This could be another Q Series system, fitted with the QJ71PB92D. Configure the QJ71PB93D using the GX Configurator-DP plug in for GX Developer.
Required Manuals
Model Number
Description
Contents
Included?
Stocked Item
SH(NA)080318
Profibus-DP Slave Module type QJ71PB93D User’s Manual
Covers QJ71PB93D and GX Configurator-DP
No
-
IB(NA)0800230
Profibus-DP Slave Module User’s Manual (Hardware) QJ71PB93D 
Basic information on QJ71PB93D
Yes
-
Note: Many of these manuals are available by free download from our website, www.meau.com
Model Number
QJ71PB93D
Stocked Item
-
Certification
UL • cUL • CE
PROFIBUS-DP Station Type
Slave station (EN50170 Volume 2 (Parts 1-4, 8) compliant)
Station Number Setting Range
0 to 125 (*3)
Max. Communication Data Size
Number of I/O data is 192 words in total ( Number of input or output data is up to 122 words)
Transmission Specifications
Electrical Standards
Complies with EIA-RS485
Network Cable
Dedicated PROFIBUS DP cable
Network Configuration
Bus (tree type when a repeater is used)
Transmission Speed / Maximum Transmission Distance (*1, *2)
Transmission Speed
Transmission Distance [m/segment]
Max. Transmission Distance 
with 3 Repeaters [m]
9.6 [kbps]
1200
4800
19.2 [kbps]
45.45 [kbps]
93.75 [kbps]
187.5 [kbps]
1000
4000
500 [kbps]
400
1600
1500 [kbps]
200
800
3 [Mbps]
100
400
6 [Mbps]
12 [Mbps]
Max. Number of Repeaters / Network
3 units (*2)
Max. Number of Stations / Segment
32 stations (including repeaters)
Number of Connection Nodes / Segments
32
I/O Device Points Occupied
32 points
5VDC Internal Power Consumption
0.44
Weight (kg)
0.11
Base Unit Slots Occupied
1
Notes:
  1. Transmission speed control within ±3% (Compliant with EN50170 Volume 2)
  2. Distance that the transmission distance can be expanded by (m/network) using repeaters. 
    Maximum transmission distance (m/network) = (number of repeaters + 1) x transmission distance (m/segment)
  3. Factory set to “126” (EN50170 Volume 2 compliant)
    Set the station number by using sequence program or GX Configurator-DP 4.03D or later.
    Set communication parameters on the master station side.
    GSD (DDB) file may be required without GX Configurator-DP Version 4.03D or later. Please contact your local Mitsubishi representative for the GSD (DDB file).

Tidak ada komentar: