Required Manuals
Model Number
|
Description
|
Contents
|
Included?
|
Stocked Item
|
IB(NA)0800324
|
Profibus-DP Master Module User’s Manual (Hardware)
|
Covers basic information on QJ71PB92V
|
Yes
|
-
|
SH(NA)080572
|
Profibus-DP Master Module User’s Manual
|
Covers using the QJ71PB92V
|
No
|
-
|
Note: Many of these manuals are available by free download from our website, www.meau.com
PROFIBUS-DP Master Module Performance Specifications
Model Number
|
QJ71PB92V
| |||
Stocked Item
|
S
| |||
Certification
|
UL • cUL • CE
| |||
PROFIBUS-DP Station Type
|
Class 1 master station
| |||
External Standard and Characteristics
|
EIA-RS485 compatible
| |||
Communication Cable
|
Shielded twisted pair cable
| |||
Network Configuration
|
Bus type (tree type if repeater is used)
| |||
Transmission Rate (*1) Maximum Transmission Distance (*2)
|
Transmission Rate
|
Transmission Distance
|
Max. Transmission Distance when Using Repeater (*2)
| |
9.6kbps
|
1200m/segment
|
4800m/network
| ||
19.2kbps
| ||||
93.75kbps
| ||||
187.5kbps
|
1000m/segment
|
4000m/network
| ||
500kbps
|
400m/segment
|
1600m/network
| ||
1.5Mbps
|
200m/segment
|
800m/network
| ||
3Mbps
|
100m/segment
|
400m/network
| ||
6Mbps
| ||||
12Mbps
| ||||
Max. No. of Repeaters In a Path
|
3 repeaters
| |||
Max. No. of Stations
|
32 stations per segment (including repeaters)
| |||
Max. No. Slave Stations
|
125 slaves per single QJ71PB92V master
| |||
I/O Data Size
|
Max. 8192 words (4096 input words, 4096 output words)
| |||
I/O Device Points Occupied
|
32 points
| |||
5VDC Internal Current Consumption
|
0.57A
| |||
Weight (kg)
|
0.13
| |||
Base Unit Slots Occupied
|
1
|
Notes:
- Transmission rate control is within ±0.2% (compatible with IEC 61158-2).
- The “maximum transmission distance” in the above table is an example which assumes that 3 repeaters are being used. If more repeaters are used to extend the distance, the maximum transmission distance would be calculated as follows: [Maximum transmission distance (m/network)] = [Number of repeaters +1] x [transmission distance (m/segment)]
PROFIBUS-DP Device Level Network Slave Module
The QJ71PB93D allows a Q Series system to be connected to a third party PROFIBUS-DP network as a slave controller. This allows distributed processing systems to be built where local control of the application can be given to the Q Series, which then supplies information back to a supervisory controller. This could be another Q Series system, fitted with the QJ71PB92D. Configure the QJ71PB93D using the GX Configurator-DP plug in for GX Developer.
Required Manuals
Model Number
|
Description
|
Contents
|
Included?
|
Stocked Item
|
SH(NA)080318
|
Profibus-DP Slave Module type QJ71PB93D User’s Manual
|
Covers QJ71PB93D and GX Configurator-DP
|
No
|
-
|
IB(NA)0800230
|
Profibus-DP Slave Module User’s Manual (Hardware) QJ71PB93D
|
Basic information on QJ71PB93D
|
Yes
|
-
|
Note: Many of these manuals are available by free download from our website, www.meau.com
Model Number
|
QJ71PB93D
| |||
Stocked Item
|
-
| |||
Certification
|
UL • cUL • CE
| |||
PROFIBUS-DP Station Type
|
Slave station (EN50170 Volume 2 (Parts 1-4, 8) compliant)
| |||
Station Number Setting Range
|
0 to 125 (*3)
| |||
Max. Communication Data Size
|
Number of I/O data is 192 words in total ( Number of input or output data is up to 122 words)
| |||
Transmission Specifications
|
Electrical Standards
|
Complies with EIA-RS485
| ||
Network Cable
|
Dedicated PROFIBUS DP cable
| |||
Network Configuration
|
Bus (tree type when a repeater is used)
| |||
Transmission Speed / Maximum Transmission Distance (*1, *2)
|
Transmission Speed
|
Transmission Distance [m/segment]
|
Max. Transmission Distance
with 3 Repeaters [m]
| |
9.6 [kbps]
|
1200
|
4800
| ||
19.2 [kbps]
| ||||
45.45 [kbps]
| ||||
93.75 [kbps]
| ||||
187.5 [kbps]
|
1000
|
4000
| ||
500 [kbps]
|
400
|
1600
| ||
1500 [kbps]
|
200
|
800
| ||
3 [Mbps]
|
100
|
400
| ||
6 [Mbps]
| ||||
12 [Mbps]
| ||||
Max. Number of Repeaters / Network
|
3 units (*2)
| |||
Max. Number of Stations / Segment
|
32 stations (including repeaters)
| |||
Number of Connection Nodes / Segments
|
32
| |||
I/O Device Points Occupied
|
32 points
| |||
5VDC Internal Power Consumption
|
0.44
| |||
Weight (kg)
|
0.11
| |||
Base Unit Slots Occupied
|
1
|
Notes:
- Transmission speed control within ±3% (Compliant with EN50170 Volume 2)
- Distance that the transmission distance can be expanded by (m/network) using repeaters.Maximum transmission distance (m/network) = (number of repeaters + 1) x transmission distance (m/segment)
- Factory set to “126” (EN50170 Volume 2 compliant)Set the station number by using sequence program or GX Configurator-DP 4.03D or later.Set communication parameters on the master station side.GSD (DDB) file may be required without GX Configurator-DP Version 4.03D or later. Please contact your local Mitsubishi representative for the GSD (DDB file).