Features
ES2 series is a small PLC for basic sequential control. It is economical, highly efficient and functional.
Specifications
*MPU points: 16 / 20 / 24 / 32 / 40 / 60
*Program capacity: 16k steps
*Built-in with 3 COM ports: 1 RS-232 port and 2 RS-485 ports, all are able to operate independently (Master/Slave)
*Max. I/O points: 256 input points + 16 output points, or 256 output points + 16 input points
*DVP-EX2 MPU is built in with 12-bit 4AD/2DA and offers analog/temperature modules of 14-bit resolution.
*Built-in with 8 high-speed input points (2 points for 100kHz, 6 points for 10kHz) and supports U/D, U/D Dir, A/B counting modes
*New motion control instructions: Close loop control, alignment mark, shield, immediate variable speed, S-Curve acceleration/deceleration
*Application in emerging industry: Exclusive instructions and function blocks designed for PV solar tracker
*Handy instructions for frequency inverter: For controlling the forward running, reverse running, RUN and STOP of Delta's AC motor drives
*Password protection: Password for subroutine, user ID, restriction on trial times
*Highly efficient instruction efficient instruction execution
Model
Item
|
16ES2
00_
|
24ES2
00_
|
32ES2
00_
|
40ES2
00_
|
60ES2
00_
|
20EX2
00_
|
32ES2
11T
| |
Power supply
voltage
|
100 ~ 240VAC (-15% ~ 10%), 50/60Hz + - 5%
|
24VDC
(-15~+20%)
| ||||||
Connector
|
European standard removable terminal block (Pin pitch: 5mm)
| |||||||
Operation
|
ES
200
|
DVP-ES2 starts to run when the power rises to 95 ~ 100VAC and stops when the power drops to 70VAC. If the power is suddenly cut off, the MPU will continue running for 10ms.
| ||||||
ES
211
|
DVP-ES2 starts to run when the power rises to 20.4VDC~28.8VDC and stops when the power drops to 17.5VDC. If the power is suddenly cut off, the MPU will continue running for 10ms.
| |||||||
Power supply fuse
|
2A/250VAC
|
2.5A / 30VDC,
Polyswitch
| ||||||
Power consumption
|
30VA
| |||||||
DC24V current output
|
500mA
|
/
| ||||||
Power supply protection
|
DC24V output short circuit protection
|
/
| ||||||
Voltage withstand
|
1,500VAC (Primary-secondary), 1,500VAC (Primary-PE),
500VAC (Secondary-PE)
| |||||||
Insulation resistance
|
> 5M Ohm at 500VDC (between all I/O points and ground)
| |||||||
Noise immunity
|
ESD: 8KV Air Discharge
EFT: Power Line: 2KV, Digital I/O: 1KV, Analog & Communication I/O: 1KV
RS: 26MHz ~ 1GHz, 10V/m
| |||||||
Grounding
|
The diameter of grounding wire shall not be less than that of L, N terminal of the power supply. (When many PLCs are in use at the same time, please make sure every PLC is properly grounded.)
| |||||||
Environment
|
Operation: 0°C~55°C (temperature), 50~95% (humidity), pollution degree 2
Storage: -25°C~70°C (temperature), 5~95% (humidity)
| |||||||
Agency approvals
|
UL508
European community EMC Directive 89/336/EEC and Low Voltage Directive
73/23/EEC
| |||||||
Vibration/shock immunity
|
International standards: IEC61131-2, IEC 68-2-6 (TEST Fc)/ IEC61131-2 &
IEC 68-2-27 (TEST Ea)
| |||||||
Weight (g)
|
R
|
377
|
414
|
489
|
554
|
696
|
462
|
/
|
T
|
351
|
387
|
432
|
498
|
614
|
442
|
321
|
Tidak ada komentar: