Kontak Kami

KONTAK KAMI : Telpon : 02126071413 Hp/WhatsApp : 081212269831 Perwakilan Jakarta : Gedung LTC Glodok Lantai 1 Blok C30 No.31 Jl.Hayam Wuruk No.127 Jakarta , Indonesia

Rabu, 20 Maret 2019

FX3G-1DA-BD


Spesifications

  • Manufacturer : Mitsubishi Electric
  • FX3G-1DA-BD
  • Analog output board FX3G - 1DA - BD
  • Analog output Analog output range Voltage output : DC 0 V to 10 V (external load resistance 2 kΩ to 1 MΩ)
  • Current output : DC 4 mA to 20 mA (external load resistance 500 Ω or less)
  • Number of output channels : 1 channel
  • Output characteristics : Output characteristics can not be adjusted.
  • Digital input Voltage output : 12 bit binary
  • Current output : 11 bit binary
  • resolution Voltage output : 2.5 mV (10 V x 1/4000)
  • Current output : 8 μA (16 mA X 1/2000)
  • Overall precision Voltage output : Ambient temperature 25 ° C ± 5 ° C: ± 0.5% (± 50 mV) against full scale 10 V Ambient temperature 0 ° C to 55 ° C: Shipment adjusted to ± 1.0% (± 100 mV) external load resistance 2 kΩ for full scale 10 V . Therefore, when it is larger than 2 kΩ, the output voltage slightly increases. In the case of 1 MΩ, the output voltage is up to 2% higher.
  • Current output : Ambient temperature 25 ° C ± 5 ° C ± 0.5 % (± 80 μA) against full scale 16 mA Ambient temperature 0 ° C to 55 ° C ± 1.0% (± 160 μA) for full scale 16 mA
  • D / A conversion time : 60 μs (Data update every calculation cycle)
  • Insulation method : No isolation between analog input and sequencer, between channels
  • Number of occupied I / O points : 0 point (It does not relate to the maximum input / output point number of the sequencer)
  • Application sequencer : FX3S, FX3G (V1.10 or later) When connecting FX3S, you can not use FX3S - CNV - ADP together with function expansion board.
  • Ambient temperature : 0 to 55 ° C. ... Operating, -25 to 75 ° C. ..... Save
  • Relative humidity : 5 to 95% RH (noncondensing).... in operation
  • Anti-vibration When DIN rail is installed Frequency: 10 to 57 Hz : One amplitude: 0.035 mm X, Y, Z 10 times in each direction (80 minutes in total)
  • Frequency: 57 to 150 Hz : Acceleration: 4.9 m / s 2 X, Y, Z 10 times in each direction (80 minutes in total)
  • Direct installation Frequency: 10 to 57 Hz : One amplitude: 0.075 mm X, Y, Z 10 times in each direction (80 minutes in total)
  • Frequency: 57 to 150 Hz : Acceleration: 9.8 m / s 2 10 times in X, Y, Z directions (80 minutes in total)
  • Impact resistance : 147 m / s 2 , working time 11 ms, three times in X, Y, Z directions with a sine half-wave pulse
  • Noise immunity : Noise voltage with 1,000 Vp-p, noise width 1 μs, rising 1 ns, with noise si
  • tor with period of 30 to 100 Hz
  • Withstand voltage : Non-insulated between analog output part and PLC main body (Do not perform withstand voltage test)
  • Insulation resistance : Non-insulated between the analog output part and the programmable controller (Do not conduct the insulation resistance test)
  • Use atmosphere : There is no corrosive property, flammable gas, conductive dust (dust) is not serious
  • Use altitude : It can not be used under an environment pressurized to 2,000 m or less under atmospheric pressure. It may break down.
  • Shipping Weight : 1 Kg

Tidak ada komentar:

Posting Komentar