Spesifications
- Manufacturer : Mitsubishi Electric
- FX3U-4AD-PT-ADP
- Analog input adapter for Pt 100 type temperature sensor FX 3 U - 4 AD - PT - ADP
- Temperature sensor . temperature control input signal : Platinum resistance temperature detector 3 wire type Pt 100 JIS C 1604 - 1997
- Number of input channels : 4 channels
- Rated temperature range : -50 ° C to + 250 ° C (-58 ° F to + 482 ° F)
- Digital output : -500 to + 2500 (-580 to + 4820 ) Within parentheses, the digital value at Fahrenheit setting
- resolution : 0.1 ° C (0.18 ° F)
- Overall accuracy : Ambient temperature 25 ° C ± 5 ° C: ± 0.5% with full scale Ambient temperature 0 ° C to 55 ° C: ± 1.0% with full scale
- control method : Depending on the sequence program
- Conversion speed FX3U / FX3UC PLC : 200 μs (Data update every calculation cycle)
- FX3S / FX3G / FX3GC Sequencer : 250 μs (Data update every calculation cycle)
- Insulation method : . Isolation between analog input part and sequencer by photo coupler . Insulation between analog input part and power supply by DC / DC converter . No isolation between each channel
- Number of occupied I / O points : 0 point (It does not relate to the maximum input / output point number of the sequencer)
- Application sequencer : FX3S, FX3G, FX3U, FX3GC, FX3UC (FX3UC - 32MT - LT is Ver.1.30 or later) FX3S - CNV - ADP is required for connection to FX3S. For connection to FX 3 G, FX 3 G - CNV - ADP is required. To connect to FX3U and FX3UC - 32MT - LT (-2), a function expansion board is required.
- mass : 0.1 Kg
- Power supply : DC 5 V 15 mA (internal power supply from the sequencer) DC 24 V + 20% -15% 50 mA (external power supply)
- Ambient temperature : 0 to 55 ° C. ... Operating -25 to 75 ° C. ..... Save
- Relative humidity : 5 to 95% RH (noncondensing).... in operation
- Anti-vibration When DIN rail is installed Frequency: 10 to 57 Hz : One amplitude: 0.035 mm X, Y, Z 10 times in each direction (80 minutes in total)
- Frequency: 57 to 150 Hz : Acceleration: 4.9 m / s 2 X, Y, Z 10 times in each direction (80 minutes in total)
- Direct installation Frequency: 10 to 57 Hz : One amplitude: 0.075 mm X, Y, Z 10 times in each direction (80 minutes in total)
- Frequency: 57 to 150 Hz : Acceleration: 9.8 m / s 2 10 times in X, Y, Z directions (80 minutes in total)
- Impact resistance : 147 m / s 2 , working time 11 ms, three times in X, Y, Z directions with a sine half-wave pulse
- Noise immunity : Noise voltage with 1,000 Vp-p, noise width 1 μs, rising 1 ns, with noise si
- tor with period of 30 to 100 Hz
- Withstand voltage : Between all terminals and ground terminal: 500 VAC for 1 minute
- Insulation resistance : Between all terminals and ground terminal: 500 MV DC 500 MΩ or more with an insulation resistance meter
- ground : Class D grounding (grounding resistance: 100 Ω or less)Grounding should be dedicated ground or common ground.
- Use atmosphere : There is no corrosive property, flammable gas, conductive dust (dust) is not serious
- Use altitude : Can not be used in an environment pressurized to 2000 m or less under atmospheric pressure. It may break down.
- Shipping Weight : 1.1 Kg