Spesifications
- Manufacturer: Mitsubishi Electric
- Analogue output adapter FX3U-4DA-ADP
- Analog output range Voltage output : DC0V ~ 10V (external load 5kΩ ~ 1MΩ)
- Current output : DC4mA ~ 20mA (or less external load 500Ω)
- Number of output channels : 4 channel
- Output characteristic: For each channel, you can set the output mode (voltage / current output).
- Digital input : 12bit binary
- resolution Voltage output : 2.5mV (10V × 1/4000)
- Current output : 4μA (16mA × 1/4000)
- Overall accuracy Voltage output : Ambient temperature 25 °C ± 5 °C: 0.5% ± with respect to full-scale 10V (± 50mV)
ambient temperature 0 °C ~ 55 °C: ± 1.0 % for the full-scale 10V (± 100mV)
external load resistance (Rs) is less than 5kΩ If, following the calculation amount will increase. (100mV will increase per Pasento 1)
(47 × 100) ÷ (Rs Tasu 47) -0.9 (Pasento) - Current output : Ambient temperature 25 °C ± 5 °C: 0.5% ± with respect to full-scale 16mA (± 80μA)
ambient temperature 0 °C ~ 55 °C: full scale 16mA for ± 1.0% (± 160μA) - D / A conversion time FX3U / FX3UC PLC : 200μs (every calculation cycle update of the data)
- FX3S / FX3G / FX3GC sequencer : 250μs (every calculation cycle update of the data)
- Insulation method : Analog output section and between the sequencer, insulated by photo-coupler is between the power supply and the analog output section, insulated by a DC / DC converter is between-each channel, non-isolated
- O occupied points : 0 points (no relation to the maximum input and output points of the sequencer)
- Apply sequencer : FX3S, FX3G, FX3U, FX3GC, FX3UC (FX3UC-32MT-LT since Ver.1.20)
connection to the FX3S is required FX3S-CNV-ADP.
Connection to the FX3G is required FX3G-CNV-ADP.
Connection to the FX3U and FX3UC-32MT-LT (-2), you must have the function expansion board. - mass : 0.1kg
- Power Specifications : -
- Power supply :
DC5V 15mA (internal power supply from the sequencer)
DC24V Tasu 20 Pasento -15 Pasento 150MA (external power supply) - Ambient temperature : 0 ~ 55 °C ····· -25 ~ 75 °C ····· during storage operations
- Relative humidity : 5 ~ 95% RH (non-condensing) ...... operation
- Vibration resistance When the DIN rail mounting- Frequency: 10 ~ 57Hz : Half amplitude: 0.035mm X, Y, Z each direction 10 times (for a total of each 80 minutes)
- When the DIN rail mounting- Frequency: 57 ~ 150Hz : Acceleration: 4.9m / s2 X, Y, Z each direction 10 times (for a total of each 80 minutes)
- Direct mounting at the time- Frequency: 10 ~ 57Hz : Half amplitude: 0.075mm X, Y, Z each direction 10 times (for a total of each 80 minutes)
- Direct mounting at the time- Frequency: 57 ~ 150Hz : Acceleration: 9.8m / s2 X, Y, Z each direction 10 times (for a total of each 80 minutes)
- Impact : 147m / s2, duration of action 11ms, X at half-sine pulse, Y, Z directions 3 times each
- Anti-noise : Noise voltage 1,000Vp-p, noise width 1μs, due to rising 1ns, cycle 30 ~ 100Hz of noise simulator
- Withstand voltage : All terminals and between the ground terminal: AC500V 1 minute
- Insulation resistance : All terminals and between the ground terminal: DC500V 5MΩ more in insulation resistance tester
- Ground: Class D grounding (ground resistance: 100Ω or less) <common ground is not allowed with the high-voltage system>
ground, please dedicated ground or shared ground. - Use atmosphere : Corrosive, there is no flammable gas, conductive dust (dust) that is not terribly
- Advanced use : 2000m or less can not be used in the pressurized environment to more than atmospheric pressure. There is a possibility of failure.
- Shipping Weight: 1.1 Kg