Kontak Kami

KONTAK KAMI : Telpon : 02126071413 Hp/WhatsApp : 081212269831 Perwakilan Jakarta : Gedung LTC Glodok Lantai 1 Blok C30 No.31 Jl.Hayam Wuruk No.127 Jakarta , Indonesia

Rabu, 20 Maret 2019

FX3U-ENET-ADP

Spesifications

  • Manufacturer: Mitsubishi Electric 
  • Ethernet interface block FX3U-ENET-ADP
  • Transmission Specifications Data transmission speed: 100Mbps or 10Mbps, 
  • Communication mode: Full / half duplex 
  • Transmission method: Baseband 
  • The maximum segment length: 100m 
  • The maximum number of nodes / connection: 10BASE-T: cascade up to four stages
    100BASE-TX: cascade up to two-stage
    above is the connection possible number of stages at the time of use repeater hub.
    Can be connected to the number of stages at the time of switching hub used, please check with the manufacturer of the switching hub to be used. 
  • Connector: RJ45 
  • function: · MELSOFT connection
    communicate by · MC protocol
    direct connection with · MELSOFT (simple connection)
    and connection CPU search function and time setting function
    ? time setting function (SNTP client), executable only after the establishment of the trigger conditions
    diagnosis from · MELSOFT function
    data monitoring function 
  • Number of connections: MELSOFT connection + MC protocol + data monitoring ? 4 connection 
  • It can be connected to the number of the basic unit: One
    Ethernet adapter, as well as the communication function expansion board and other communication special adapter, and 1 channel the communication channel (CH) occupation. 
  • Apply PLC: FX3S, FX3G (V2.00 or later), FX3U (since V3.10), FX3GC (V2.00 or later), FX3UC (V3.10 or later)
    connection to the FX3S is required FX3S-CNV-ADP.
    Connection to the FX3G is required FX3G-CNV-ADP.
    FX3U, connection to the FX3UC-32MT-LT (-2), you must have the function expansion board. 
  • mass: 0.1kg 
  • Power Specifications:   
  • Power supply: 30mA / DC5V (internal power supply from DC5V power of the basic unit) 
  • Allowable momentary power failure time: As well as the sequencer to be connected 
  • Ambient temperature: 0 ~ 55 °C ····· operation, -25 ~ 75 °C ····· during storage 
  • Relative humidity: 5 ~ 95% RH (non-condensing) ...... operation 
  • Vibration resistance When the DIN rail mounting Frequency: 10 ~ 57Hz: Half amplitude: 0.035mm X, Y, Z each direction 10 times (for a total of each 80 minutes) 
  • Frequency: 57 ~ 150Hz: Acceleration: 4.9m / s2 X, Y, Z each direction 10 times (for a total of each 80 minutes) 
  • Direct mounting at the time Frequency: 10 ~ 57Hz: Half amplitude: 0.075mm X, Y, Z each direction 10 times (for a total of each 80 minutes) 
  • Frequency: 57 ~ 150Hz: Acceleration: 9.8m / s2 X, Y, Z each direction 10 times (for a total of each 80 minutes) 
  • Impact resistance: 147m / s2, duration of action 11ms, X at half-sine pulse, Y, Z directions 3 times each 
  • Anti-noise: Noise voltage 1,000Vp-p, noise width 1μs, due to rising 1ns, cycle 30 ~ 100Hz of noise simulator 
  • Withstand voltage: All terminals and between the ground terminal: AC500V 1 minute 
  • Insulation resistance: All terminals and between the ground terminal: DC500V 5MΩ more in insulation resistance tester 
  • Working environment: Corrosive, there is no flammable gas, conductive dust (dust) that is not terribly 
  • Use advanced: 2000m or less
    can not be used in the pressurized environment to more than atmospheric pressure. There is a possibility of failure. 
  • Shipping Weight : 1 Kg

Tidak ada komentar: