Kontak Kami

KONTAK KAMI : Telpon : 02126071413 Hp/WhatsApp : 081212269831 Perwakilan Jakarta : Gedung LTC Glodok Lantai 1 Blok C30 No.31 Jl.Hayam Wuruk No.127 Jakarta , Indonesia

Selasa, 19 Maret 2019

MITSUBISHI QX41Y41P

  • Manufacturer : Mitsubishi Electric
  • QX41Y41P
  • DC input / transistor output combined unit QX41Y41P
  • Input specification :
  • Input format : DC input (plus common type)
  • Number of input points : 32 points
  • Rated input voltage : DC 24 V (+ 20 / -15%, ripple ratio within 5%)
  • Rated input current : About 4 mA
  • ON voltage / ON current : 19 V or more / 3 mA or more
  • OFF voltage / OFF current : 11 V or less / 1.7 mA or less
  • Input resistance : About 5.6 kΩ
  • Input response time OFF → ON : 1 ms / 5 ms / 10 ms / 20 ms / 70 ms or less
  • ON → OFF : 1 ms / 5 ms / 10 ms / 20 ms / 70 ms or less
  • Input common type : 32 points 1 common
  • Output format : Transistor output (sink type)
  • Number of output points : 32 points
  • Rated load voltage : DC 12 to 24 V (+ 20 / -15%)
  • Maximum load current : 0.1 A / 1 point, 2 A / 1 common
  • Maximum inrush current : 0.7 A less than 10 ms
  • Leakage current at OFF : 0.1 mA or less
  • Maximum voltage drop during ON : DC 0.1 V (TYP.) 0.1 A, DC 0.2 V (MAX.) 0.1 A
  • Output response time OFF → ON : 1ms or less
  • ON → OFF : 1 ms or less (rated load, resistance load)
  • Surge suppressor : Zener diode
  • fuse : None
  • Protection function Overheat protection function : Operate in units of 1 point
  • Overload protection function : Overcurrent detection, overload protection limit current: 1 to 3A / 1 point operation in 1 point
  • External power supply Voltage : DC 12 to 24 V (+ 20 / -15%) (ripple ratio within 5%)
  • Current : Maximum 15mA / 1 common (24 VDC, all points ON)
  • Output common method : 32 points 1 common
  • Insulation method : Photocoupler isolation
  • Withstand voltage : AC 560 Vrms / 3 cycles (altitude 2000 m)
  • Insulation resistance : 10 MΩ or more with an insulation resistance meter
  • Protection grade : IP2X
  • Operation indication : ON indication (LED) SW display with 32 switches
  • External wiring connection method : 40 pin connector X 2
  • Applicable connector : A6CON1, A6CON2, A6CON3, A6CON4 (sold separately)
  • Number of occupied I / O points : 64 points (I / O assignment: 64 input / output mixing points)
  • DC 5 V Internal current consumption : 130 mA (TYP. All points ON)
  • External dimensions Height (H) : 98 mm
  • Width (W) : 27.4 mm
  • Depth (D) : 90 mm
  • mass : 0.20 Kg
  • Shipping Weight : 1.2 Kg

Tidak ada komentar: