- Proces Input Units (Isolated type Units With Universal Inputs), Signal range Fully universal inputs pt100 JPt100 Pt1000 K J L R S B 4 to 20 mA 0 to 20 mA 1 to 5 V 0 TO 5 V 0 to 10 V, Conversion speed (resolution) Conversion speed 250 ms/ 4 inputs, Accuracy (at ambient Temperature of 25 C) Accuracy Platinum resistance thermometer input (+ 0.3% of PV OR +0.8 C whichever is large) + 1 digit max Thermocouple input (+0.3% of PV or + 1,5 C whichever is large) + 1 digit max *1 Voltage or current input +0.3% of F S +1 digit max, Current Consumption (A) 5 V 0.32 : CJ1W-AD04U
- Proces Input Units (Isolated type Units with Universal Inputs), Signal range Universal Input Pt100 (3-wire) JPt100 (3-wire) Pt1000 (3-wire) Pt100 (4-wire) K J T E L U N R S B WRe5-26 PL II 4 to 20 mA 0to 20 mA 1 to 5 V 0 to 1,25 V 0 to 5 V 0to 10 V +100 mV selectable -1,25 to 1,25 V -5 TO 5 V -10 t0 10 V +10 V selectable range potentiometer, Conversion speed (resolution) Resolution (conversion speed) 1/256,000 (conversion cycle 60 ms/ 4 inputs) 1/64,000 (Conversion cycle 5 ms/ 4 inputs), Accuracy (at ambient temperature) of 25 C) standard Accuracy +0.05% 0f F S, Current Consumption (A) 5 V 0.3 : CJ1W-PH41U*2