Specification
Analog/Digital (4A/D) module
|
Voltage input
|
Current input
|
Power supply voltage
|
24V DC (20.4V DC ~ 28.8V DC) (-15% ~ +20%)
| |
Analog input channel
|
4 channels/module
| |
Range of analog input
|
+-10V
|
+-20mA
|
Range of digital conversion
|
+-8,000
|
+-4,000
|
Resolution
|
14 bits (1LSB = 2.5mV)
|
13 bits (1LSB = 5uA)
|
Input impedance
|
0.5Ω
or lower
| |
Overall accuracy
|
+-0.5% when in full scale (25°C, 77°F)
+-1% when in full scale within the range of 0 ~ 55°C, 32 ~ 131°F
| |
Responding time
|
3ms × the number of channels
| |
Isolation
|
Internal circuit and analog output terminals are isolated by optical coupler.
No isolation among analog channels.
| |
Range of absolute input
|
+-15V
|
+-32mA
|
Digital data format
|
13 significant bits out of 16 bits are available; in 2's complement
| |
Average function
|
Yes. Available for setting up in CR#2 ~ CR#5; range: K1 ~ K20.
| |
Self-diagnosis
|
Upper and lower bound detection/channel
| |
Communication mode
(RS-485)
|
ASCII/RTU mode. Communication speed: 4,800/9,600/19,200/38,400/57,600/115,200 bps. ASCII data format: 7-bit, even bit, 1 stop bit (7, E, 1). RTU data format: 8-bit, even bit, 1 stop bit (8, E, 1). RS-485 cannot be used when connected to PLC MPU.
| |
When connected to DVP-PLC
MPU in series
|
The modules are numbered from 0 to 7 automatically by their distance from MPU. No.0 is the closest to MPU and No.7 is the furthest. Maximum 8 modules are allowed to connect to MPU and will not occupy any digital I/O points.
| |
Max. rated power consumption
|
24V DC (20.4V DC ~ 28.8V DC) (-15% ~ +20%), 2.5W, supplied by external power
| |
Operation/storage
|
Operation: 0°C ~ 55°C (temperature); 5 ~ 95% (humidity); pollution degree 2
Storage: -25°C ~ 70°C (temperature); 5 ~ 95% (humidity)
| |
Vibration/shock immunity
|
International standards: IEC 61131-2, IEC 68-2-6 (TEST Fc)/IEC 61131-2 & IEC 68-2-27
(TEST Ea)
|