Spesifications
- Manufacturer: Mitsubishi Electric
- RS-485 communication for function expansion board FX3G-485-BD
- Transmission standard : RS-485 standard, conform to the RS-422 standard
- Insulation method : Non-insulated (between the communication line and the CPU)
- Transmission distance : Up to 50m
- External device connection method : Europe terminal blocks
- Communication system : Half-duplex bi-directional
- Communication procedure : Non-procedural, computer link (dedicated protocol format 1, dedicated protocol format 4), parallel link, a simple PC-to-PC link, inverter communication
FX3G is compatible with the inverter communication later Ver.1.10. - communication speed No-protocol, the computer link : 300/600/1200/2400/4800/9600/19200/38400 (bps)
- Parallel link : 115200 (bps)
- Simple PC-to-PC link : 38400 (bps)
- Inverter communication : 4800/9600/19200/38400 (bps)
- Display (LED) : RD, SD
- O occupied points : 0 points (no relation to the maximum input and output points of the sequencer)
- Apply sequencer : FX3S, FX3G
FX3S when connected, can not be used in conjunction function expansion board and FX3S-CNV-ADP. - Ambient temperature : 0 ~ 55 °C ····· operation, -25 ~ 75 °C ····· during storage
- Relative humidity : 5 ~ 95% RH (non-condensing) ...... operation
- Vibration resistance When the DIN rail mounting Frequency: 10 ~ 57Hz : Half amplitude: 0.035mm X, Y, Z each direction 10 times (for a total of each 80 minutes)
- Frequency: 57 ~ 150Hz : Acceleration: 4.9m / s2 X, Y, Z each direction 10 times (for a total of each 80 minutes)
- Direct mounting at the time Frequency: 10 ~ 57Hz : Half amplitude: 0.075mm X, Y, Z each direction 10 times (for a total of each 80 minutes)
- Frequency: 57 ~ 150Hz : Acceleration: 9.8m / s2 X, Y, Z each direction 10 times (for a total of each 80 minutes)
- Impact : 147m / s2, duration of action 11ms, X at half-sine pulse, Y, Z directions 3 times each
- Anti-noise : Noise voltage 1,000Vp-p, noise width 1μs, due to rising 1ns, cycle 30 ~ 100Hz of noise simulator
- Withstand voltage : Non-isolated between communication line and the PLC main unit
(Please do not withstand voltage test) - Insulation resistance : Non-isolated between communication line and the PLC main unit
(Please do not insulation resistance test) - Use atmosphere : Corrosive, there is no flammable gas, conductive dust (dust) that is not terribly
- Advanced use : 2,000m or less (can not be used under the pressurized environment to more than atmospheric pressure. There is a possibility of failure.)
- Shipping Weight : 1 Kg