Spesifications
- Manufacturer : Mitsubishi Electric
- FX3U-3A-ADP
- Analog input / output adapter FX3U - 3A - ADP
- Analog input Analog input range Voltage input : DC 0 to 10 V (input resistance 198.7 kΩ)
- Current input : DC 4 to 20 mA (input resistance 250 Ω)
- Number of input channels : 2 channels
- Absolute maximum input Voltage input : -0.5 V, +15 V
- Current input : -2 mA, +30 mA
- Input characteristics : Input mode (voltage / current input) can be set for each channel.
- Digital output : 12 bit binary
- resolution Voltage input : 2.5 mV (10 V x 1/4000)
- Current input : 5 μA (16 mA X 1/3200)
- Overall precision Voltage input : Ambient temperature 25 ° C ± 5 ° C ± 0.5% (± 50 mV) to full scale 10 V Ambient temperature 0 ° C to 55 ° C ± 1.0% (± 100 mV) to full scale 10 V
- Current input : Ambient temperature 25 ° C ± 5 ° C ± 0.5 % (± 80 μA) against full scale 16 mA Ambient temperature 0 ° C to 55 ° C ± 1.0% (± 160 μA) for full scale 16 mA
- A / D conversion time When FX3U / FX3UC sequencer is connected : 80 μs X Number of used input channels + 40 μs X Number of output output channels (data update every calculation cycle)
- When FX3S / FX3G / FX3GC programmable controller is connected : 90 μs X number of used input channels + 50 μs X number of output output channels (data update every calculation cycle)
- Insulation method : . Insulation between analog input / output section and sequencer by photo coupler . Insulation between drive power supply and analog input / output section by DC / DC converter . No isolation between each channel
- Analog output Analog output range Voltage output : DC 0 to 10 V (external load resistance 5 k to 1 MΩ)
- Current output : DC 4 to 20 mA (external load resistance 500 Ω or less)
- Number of output channels : 1 channel
- Output characteristics : Output mode (voltage / current output) can be set.
- Digital input : 12 bit binary
- resolution Voltage output : 2.5 mV (10 V x 1/4000)
- Current output : 4 μA (16 mA X 1/4000)
- Overall precision Voltage output : Ambient temperature 25 ° C ± 5 ° C ± 0.5% (± 50 mV) to full scale 10 V Ambient temperature 0 ° C to 55 ° C ± 1.0% (± 100 mV) to full scale 10 V External load resistance (Rs) is less than 5 kΩ In addition, the following calculations increase. (It increases by 100 mV per 1%.) 47 X 100 / (Rs + 47) - 0.9 (%)
- Current output : Ambient temperature 25 ° C ± 5 ° C ± 0.5 % (± 80 μA) against full scale 16 mA Ambient temperature 0 ° C to 55 ° C ± 1.0% (± 160 μA) for full scale 16 mA
- D / A conversion time When FX3U / FX3UC sequencer is connected : 80 μs X Number of used input channels + 40 μs X Number of output output channels (data update every calculation cycle)
- When FX3S / FX3G / FX3GC programmable controller is connected : 90 μs X number of used input channels + 50 μs X number of output output channels (data update every calculation cycle)
- Insulation method : . Insulation between analog input / output section and sequencer by photo coupler . Insulation between drive power supply and analog input / output section by DC / DC converter . No isolation between each channel
- Number of occupied I / O points : 0 point (It does not relate to the maximum input / output point number of the sequencer)
- Application sequencer : FX3S, FX3G (Ver.1.20 or later), FX3U (Ver.2.61 or later), FX3GC, FX3UC (Ver.2.61 or later) FX3S - CNV - ADP is required for connection to FX3S. For connection to FX 3 G, FX 3 G - CNV - ADP is required. To connect to FX3U and FX3UC - 32MT - LT (-2), a function expansion board is required.
- mass : About 0.1 Kg
- Power supply Conversion circuit drive power supply : DC24 V + 20% -15% 90 mA Connect a 24 VDC power supply to the terminal block and supply it.
- Interface drive power supply : DC 5 V 20 mA Internal power is supplied from the DC 5 V power supply of the basic unit.
- Ambient temperature : 0 to 55 ° C. ... Operating -25 to 75 ° C. ..... Save
- Relative humidity : 5 to 95% RH (noncondensing).... in operation
- Anti-vibration When DIN rail is installed Frequency: 10 to 57 Hz : One amplitude: 0.035 mm X, Y, Z 10 times in each direction (80 minutes in total)
- Frequency: 57 to 150 Hz : Acceleration: 4.9 m / s 2 X, Y, Z 10 times in each direction (80 minutes in total)
- Direct installation Frequency: 10 to 57 Hz : One amplitude: 0.075 mm X, Y, Z 10 times in each direction (80 minutes in total)
- Frequency: 57 to 150 Hz : Acceleration: 9.8 m / s 2 10 times in X, Y, Z directions (80 minutes in total)
- Impact resistance : 147 m / s 2 , working time 11 ms, three times in X, Y, Z directions with a sine half-wave pulse
- Noise immunity : Noise voltage with 1,000 Vp-p, noise width 1 μs, rising 1 ns, with noise si
- tor with period of 30 to 100 Hz
- Withstand voltage : Between all terminals and ground terminal: 500 VAC for 1 minute
- Insulation resistance : Between all terminals and ground terminal: 500 MV DC 500 MΩ or more with an insulation resistance meter
- ground : Class D grounding (grounding resistance: 100 Ω or less)Grounding should be dedicated ground or common ground.
- Use atmosphere : There is no corrosive property, flammable gas, conductive dust (dust) is not serious
- Use altitude : Can not be used in an environment pressurized to 2000 m or less under atmospheric pressure. It may break down.
- Shipping Weight : 1.1 Kg