Kontak Kami

KONTAK KAMI : Telpon : 02126071413 Hp/WhatsApp : 081212269831 Perwakilan Jakarta : Gedung LTC Glodok Lantai 1 Blok C30 No.31 Jl.Hayam Wuruk No.127 Jakarta , Indonesia
Tampilkan postingan dengan label QJ71PB93D. Tampilkan semua postingan
Tampilkan postingan dengan label QJ71PB93D. Tampilkan semua postingan

Senin, 22 Oktober 2018

MITSUBISHI QJ71PB93D



Required Manuals
Model Number
Description
Contents
Included?
Stocked Item
IB(NA)0800324
Profibus-DP Master Module User’s Manual (Hardware)
Covers basic information on QJ71PB92V
Yes
-
SH(NA)080572
Profibus-DP Master Module User’s Manual
Covers using the QJ71PB92V
No
-
Note: Many of these manuals are available by free download from our website, www.meau.com
PROFIBUS-DP Master Module Performance Specifications
Model Number
QJ71PB92V
Stocked Item
S
Certification
UL • cUL • CE
PROFIBUS-DP Station Type
Class 1 master station
External Standard and Characteristics
EIA-RS485 compatible
Communication Cable
Shielded twisted pair cable
Network Configuration
Bus type (tree type if repeater is used)
Transmission Rate (*1) Maximum Transmission Distance (*2)
Transmission Rate
Transmission Distance
Max. Transmission Distance when Using Repeater (*2)
9.6kbps
1200m/segment
4800m/network
19.2kbps
93.75kbps
187.5kbps
1000m/segment
4000m/network
500kbps
400m/segment
1600m/network
1.5Mbps
200m/segment
800m/network
3Mbps
100m/segment
400m/network
6Mbps
12Mbps
Max. No. of Repeaters In a Path
3 repeaters
Max. No. of Stations
32 stations per segment (including repeaters)
Max. No. Slave Stations
125 slaves per single QJ71PB92V master
I/O Data Size
Max. 8192 words (4096 input words, 4096 output words)
I/O Device Points Occupied
32 points
5VDC Internal Current Consumption
0.57A
Weight (kg)
0.13
Base Unit Slots Occupied
1
Notes:
  1. Transmission rate control is within ±0.2% (compatible with IEC 61158-2).
  2. The “maximum transmission distance” in the above table is an example which assumes that 3 repeaters are being used. If more repeaters are used to extend the distance, the maximum transmission distance would be calculated as follows: [Maximum transmission distance (m/network)] = [Number of repeaters +1] x [transmission distance (m/segment)]
PROFIBUS-DP Device Level Network Slave Module
The QJ71PB93D allows a Q Series system to be connected to a third party PROFIBUS-DP network as a slave controller. This allows distributed processing systems to be built where local control of the application can be given to the Q Series, which then supplies information back to a supervisory controller. This could be another Q Series system, fitted with the QJ71PB92D. Configure the QJ71PB93D using the GX Configurator-DP plug in for GX Developer.
Required Manuals
Model Number
Description
Contents
Included?
Stocked Item
SH(NA)080318
Profibus-DP Slave Module type QJ71PB93D User’s Manual
Covers QJ71PB93D and GX Configurator-DP
No
-
IB(NA)0800230
Profibus-DP Slave Module User’s Manual (Hardware) QJ71PB93D 
Basic information on QJ71PB93D
Yes
-
Note: Many of these manuals are available by free download from our website, www.meau.com
Model Number
QJ71PB93D
Stocked Item
-
Certification
UL • cUL • CE
PROFIBUS-DP Station Type
Slave station (EN50170 Volume 2 (Parts 1-4, 8) compliant)
Station Number Setting Range
0 to 125 (*3)
Max. Communication Data Size
Number of I/O data is 192 words in total ( Number of input or output data is up to 122 words)
Transmission Specifications
Electrical Standards
Complies with EIA-RS485
Network Cable
Dedicated PROFIBUS DP cable
Network Configuration
Bus (tree type when a repeater is used)
Transmission Speed / Maximum Transmission Distance (*1, *2)
Transmission Speed
Transmission Distance [m/segment]
Max. Transmission Distance 
with 3 Repeaters [m]
9.6 [kbps]
1200
4800
19.2 [kbps]
45.45 [kbps]
93.75 [kbps]
187.5 [kbps]
1000
4000
500 [kbps]
400
1600
1500 [kbps]
200
800
3 [Mbps]
100
400
6 [Mbps]
12 [Mbps]
Max. Number of Repeaters / Network
3 units (*2)
Max. Number of Stations / Segment
32 stations (including repeaters)
Number of Connection Nodes / Segments
32
I/O Device Points Occupied
32 points
5VDC Internal Power Consumption
0.44
Weight (kg)
0.11
Base Unit Slots Occupied
1
Notes:
  1. Transmission speed control within ±3% (Compliant with EN50170 Volume 2)
  2. Distance that the transmission distance can be expanded by (m/network) using repeaters. 
    Maximum transmission distance (m/network) = (number of repeaters + 1) x transmission distance (m/segment)
  3. Factory set to “126” (EN50170 Volume 2 compliant)
    Set the station number by using sequence program or GX Configurator-DP 4.03D or later.
    Set communication parameters on the master station side.
    GSD (DDB) file may be required without GX Configurator-DP Version 4.03D or later. Please contact your local Mitsubishi representative for the GSD (DDB file).