Spesifikasi CJ2M

General Specifications

ItemCJ2M-
CPU1[]CPU3[]
EnclosureMounted in a panel
GroundingLess than 100 Ω
CPU Unit Dimensions90 mm × 75 mm × 31 mm90 mm × 75 mm × 62 mm
Weight (see note 2)130 g or less190 g or less (see note 1)
Current Consumption5 VDC, 0.5 A5 VDC, 0.7 A
Operation 
Environment
Ambient Operating Temperature0 to 55 °C
Ambient Operating Humidity10% to 90% (with no condensation)
AtmosphereMust be free from corrosive gases.
Ambient Storage Temperature- 20 to 70 °C (excluding battery)
Altitude2,000 m or less
Pollution Degree2 or less: Conforms to JIS B3502 and IEC 61131-2.
Noise Immunity2 kV on power supply line (Conforms to IEC 61000-4-4.)
Overvoltage CategoryCategory II: Conforms to JIS B3502 and IEC 61131-2.
EMC Immunity LevelZone B
Vibration ResistanceConforms to IEC60068-2-6 
5 to 8.4 Hz with 3.5-mm amplitude, 8.4 to 150 Hz 
Acceleration of 9.8 m/s2 for 100 min in X, Y, and Z directions 
(10 sweeps of 10 min each = 100 min total)
Shock ResistanceConforms to IEC60068-2-27 
147 m/s2, 3 times in X, Y, and Z directions (100 m/s2 for Relay 
Output Units)
BatteryLife5 years at 25 °C
WeightApprox. 10 g
ModelCJ1W-BAT01
Applicable StandardsConforms to cULus, NK, LR, and EC Directives.
Note:1. Without a Serial Option Board. 
        2. Includes wight of end covers and battery.

Performance Specifications

ItemsCJ2M-
CPU11/31CPU12/32CPU13/33CPU14/34CPU15/35
User Memory5K steps10K steps20K steps30K steps60K steps
I/O Bits2,560 bits
Proc- 
essing 
Speed
Overhead Processing TimeNormal Mode: 
CJ2M-CPU3[]: 270 μs * 
CJ2M-CPU1[]: 160 μs * 
* The following time must be added when using EtherNet/IP tag data links for the CJ2M-CPU3[]. 
100 μs + (Number of words transferred × 1.8 μs) 
The following time must be added when using Pulse I/O Modules with a CJ2M CPU Unit: 
10 μs × Number of Pulse I/O Modules
Execution TimeBasic Instructions: 0.04 μs min. 
Special Instructions: 0.06 μs min.
Inter-
rupts
I/O Interrupts and External InterruptsInterrupt task startup time: 31 μs 
Return time to cyclic task: 10 μs
Scheduled InterruptsMinimum time interval: 0.4 ms (set in 0.1 ms increments)
Interrupt task startup time: 30 μs 
Return time to cyclic task: 11 μs
Maximum Number of Connectable UnitsTotal per CPU Rack or Expansion Rack: 10 Units max.; 
Total per PLC: 40 Units max.
Basic I/O UnitsNo limit 
However, a maximum of two CJ1W-INT01 Interrupt Input Units can be mounted.
Special I/O UnitsUnits for up to 96 unit numbers can be mounted. (Unit numbers run from 0 to 95. Units are allocated between 1 and 8 unit numbers.)
CPU Bus UnitsCJ2M-CPU3[]: 15 Units max. 
CJ2M-CPU1[]: 16 Units max.
Pulse I/O Modules2 Units max. * 
* Supported only by CJ2M CPU Units with unit version 2.0 or later. A Pulse I/O Module must be mounted.
Slots for which interrupts can be usedSlots 0 to 4 on CPU Rack
Maximum Number of Expansion Racks3 max.
CIO AreaI/O Area2,560 bits (160 words): Words CIO 0000 to CIO 0159
Link Area3,200 bits (200 words): Words CIO 1000 to CIO 1199
CPU Bus Unit Area6,400 bits (400 words): Words CIO 1500 to CIO 1899
Special I/O Unit Area15,360 bits (960 words): Words CIO 2000 to CIO 2959
Pulse I/O Area20 inputs, 12 outputs (CIO 2960 to CIO 2963)
Serial PLC Link Words1,440 bits (90 words): Words CIO 3100 to CIO 3189
DeviceNet Area9,600 bits (600 words): Words CIO 3200 to CIO 3799
Internal I/O Area3,200 bits (200 words): Words CIO 1300 to CIO 1499 (Cannot be used for external I/O.) 
37,504 bits (2,344 words): Words CIO 3800 to CIO 6143 (Cannot be used for external I/O.)
Work Area8,192 bits (512 words): Words W000 to W511 (Cannot be used for external I/O.)
Holding Area8,192 bits (512 words): Words H000 to H511 
Bits in this area maintain their ON/OFF status when PLC is turned OFF or operating mode is changed. 
Words H512 to H1535: These words can be used only for function blocks. They can be used only for function block instances (i.e., they are allocated only for internal variables in function blocks).
Auxiliary AreaRead-only: 31,744 bits (1,984 words) 
7,168 bits (448 words): Words A0 to A447 
24,576 bits (1,536 words): Words A10000 to A11535 * 
Read/write: 16,384 bits (1,024 words) in words A448 to A1471 * 
* A960 to A1471 and A10000 to A11535 cannot be accessed by CPU Bus Units, Special I/O Units, PTs, and Support Software that do not specifically support the CJ2 CPU Units.
Temporary Area16 bits: TR0 to TR15
Timer Area4,096 timer numbers (T0000 to T4095 (separate from counters))
Counter Area4,096 counter numbers (C0000 to C4095 (separate from timers))
DM Area32k words * 
DM Area words for Special I/O Units: D20000 to D29599 (100 words × 96 Units) 
DM Area words for CPU Bus Units: D30000 to D31599 (100 words × 16 Units) 
* Bits in the EM Area can be addressed either by bit or by word. These bits cannot be addressed by CPU Bus Units, Special I/O Units, PTs, and Support Software that do not specifically support the CJ2 CPU Units.
EM Area32k words/bank × 4 banks max.: E00_00000 to E3_32767 max. * 
* Bits in the EM Area can be addressed either by bit or by word. These bits cannot be addressed by CPU Bus Units, Special I/O Units, PTs, and Support Software that do not specifically support the CJ2 CPU Units.
32K words × 1 bank32K words × 4 banks
Force-S/R Enabled Banks *1Bank 0 hexBank 0 to 3 hex
Index RegistersIR0 to IR15 
These are special registers for storing PLC memory addresses for indirect addressing. (Index Registers can be set so that they are unique in each task or so that they are shared by all tasks.)
Cyclic Task Flag Area128 flags
Memory Card128 MB, 256 MB, or 512 MB
Operating ModesPROGRAM Mode: Programs are not executed. Preparations can be executed prior to program execution in this mode. 
MONITOR Mode: Programs are executed, and some operations, such as online editing, and changes to present values in I/O memory, are enabled in this mode. 
RUN Mode: Programs are executed. This is the normal operating mode.
Execution ModeNormal Mode
Programming LanguagesLadder Logic (LD), 
Sequential Function Charts (SFC), 
Structured Text (ST), and 
Instruction Lists (IL)
Function 
Blocks
Maximum number of definitions2562,048
Maximum number of instances2562,048
FB Program Area20K steps
TasksType of TasksCyclic tasks 
Interrupt tasks (Power OFF interrupt tasks, scheduled interrupt tasks, I/O interrupt tasks, and external interrupt tasks, and input interrupt tasks *2)
Number of TasksCyclic tasks: 128 
Interrupt tasks: 256 
(Interrupt tasks can be defined as cyclic tasks to create extra cyclic tasks. Therefore, the total number of cyclic tasks is actually 384 max.)
Symbols 
(Varia- 
bles)
Type of SymbolsLocal symbols: Can be used only within a single task in the PLC. 
Global symbols: Can be used in all tasks in the PLC. 
Network symbols (tags) *: I/O memory in the CPU Unit can be externally accessed using symbols, depending on parameter settings. 
* Supported only by the CJ2M-CPU3[].
Data Type of SymbolsBOOL (bit) 
UINT (one-word unsigned binary) 
UDINT (two-word unsigned binary) 
ULINT (four-word unsigned binary) 
INT (one-word signed binary) 
DINT (two-word signed binary) 
LINT (four-word signed binary) 
UINT BCD (one-word unsigned BCD) *3 
UDINT BCD (two-word unsigned BCD) *3 
ULINT BCD (four-word unsigned BCD) *3 
REAL (two-word floating-point) 
LREAL (four-word floating-point) 
CHANNEL (word) *3 
NUMBER (constant or number) *3 
WORD (one-word hexadecimal) 
DWORD (two-word hexadecimal) 
LWORD (four-word hexadecimal) 
STRING (1 to 255 ASCII characters) 
TIMER (timer) *4 
COUNTER (counter) *4 
User defined data types (data structures)
Maximum Size of Symbol32k words
Array Symbols (Array Variables)One-dimensional arrays
Number of Array Elements32,000 elements max.
Number of Registrable Network Symbols (Tags) *52,000 max.
Length of Network Symbol (Tag) Name *5255 bytes max.
Encoding of Network Symbols (Tags) *5UTF-8
Data 
Tracing
Memory Capacity8,000 words 
(The EM Area can be specified from the CX-Programmer to use up to 32K words multiplied by the number of banks supported by the CPU Unit model.)
Number of SamplingsBits = 31, one-word data =16, two-word data = 8, four-word data = 4
Sampling Cycle1 to 2,550 ms (Unit: 1 ms)
Trigger ConditionsON/OFF of specified bit 
Data comparison of specified word 
Data size: 1 word, 2 words, 4 words 
Comparison Method: Equals (=), Greater Than (>), Greater Than or Equals (≥), Less Than (<), Less Than or Equals (≤), Not Equal (≠)
Delay Value- 32,768 to +32,767 ms
File MemoryMemory Card (128, 256, or 512 Mbytes) (Use the Memory Cards provided by OMRON.) 
EM file memory (Part of the EM Area can be converted for use as file memory.)
Source/ 
Comment
Memory
Function block program memory, comment file, program index file, symbol tablesCapacity: 1 Mbytes
Commu- 
nications
Logical Ports for 
Communications
Logical Ports8 ports (Used for SEND, RECV, CMND, PMCR, TXDU, and RXDU instructions.)
Extended 
Logical Ports
64 ports (Used for SEND2, RECV2, CMND2, and PMCR2 instructions.)
CIP 
Communications 
Specification
Class 3 
(Connection 
Type)
Number of connections: 64
UCMM (Non- 
connection 
Type)
Maximum number of clients that can communicate at the same time: 32 
Maximum number of servers that can communicate at the same time: 40
Peripheral (USB) PortUSB 2.0-compliant B-type connector
Baud Rate12 Mbps max.
Transmission Distance5 m max.
Serial PortCJ2M-CPU1[] interface: Conforms to EIA RS-232C. 
CJ2M-CPU3[]: No serial ports with default system 
One of the following Serial Option Boards can be mounted. 
CP1W-CIF01 RS-232C Option Board 
CP1W-CIF11 RS-422A/485 Option Board (not isolated, max. transmission distance: 50 m) 
CP1W-CIF12 RS-422A/485 Option Board (isolated, max. transmission distance: 500 m)
Communications MethodHalf-duplex
Synchronization MethodStart-stop
Baud Rate0.3, 0.6, 1.2, 2.4, 4.8, 9.6, 19.2, 38.4, 57.6, or 115.2 (kbps)
Transmission Distance15 m max.
EtherNet/IP Port *6-
Trans- 
mission 
Specifi- 
cations
Media Access 
Method
CSMA/CD
ModulationBaseband
Transmission 
Paths
Star
Baud Rate100 Mbps (100Base-TX)
Transmission 
Media
Shielded twisted-pair (STP) cable; Categories: 5, 5e
Transmission 
Distance
100 m (between ethernet switch and node)
Number of 
Cascade 
Connections
No restrictions if ethernet switch is used.
Commu- 
nications
Specifi- 
cations
CIP 
Communications: 
Tag Data Links
Number of 
Connections
32
Packet Interval 
(Refresh period)
1 to 10,000 ms (Unit: 0.5 ms) 
Can be set for each connection. (Data will be refreshed at the set interval, regardless of the number of nodes.)
Permissible 
Communications
Band
3,000 packets per second *7
Number of 
Registerable Tag
32
Type of TagsCIO, DM, EM, HR, WR, and Network symboles
Number of Tags 
per Connection
8 (Seven tags if PLC status is included in the segment.)
Maximum Link 
Data Size per 
Node (total 
size of all tags)
640 words
Maximum Data 
Size per 
Connection
640 words *8 (Data is synchronized within each connection.)
Number of 
Registrable Tag 
Set
32 (1 connection = 1 segment)
Maximum Tag 
Set Size
640 words *8 (One word is used when PLC status is included in the segment.)
Maximum 
Number of Tags 
Refreshable in a 
Single Cycle of 
CPU Unit *9
Output/send (CPU Unit to EtherNet/IP): 32 
Input/receive (EtherNet/IP to CPU Unit): 32
Data Size 
Refreshable in a 
Single Cycle of 
CPU Unit *9
Output/send (CPU to EtherNet/IP): 640 words 
Input/receive (EtherNet/IP to CPU): 640 words
Change of Tag 
Data Link 
Parameter 
Settings during 
Operation
OK *10
Multi-cast 
Packet Filter 
*11
OK
CIP 
Communications: 
Explicit Messages
-
Class 3 
(Connection 
Type)
Number of connections: 128
UCMM (Non- 
connection 
Type)
Maximum number of clients that can communicate at the same time: 16 
Maximum number of servers that can communicate at the same time: 16
CIP RoutingOK (CIP routing is enabled for the following remote Units: CJ1W-EIP21, CJ2H-CPU6[]-EIP, CJ2M-CPU3[], and CS1W-EIP21.)
FINS 
Communications
-
FINS/UDPOK
FINS/TCP16 connections max.
EtherNet/IP 
Conformance Test
Conforms to A5.
EtherNet/IP 
Interface
10Base-T/100Base-TX 
Auto Negotiation/Fixed Setting
*1. Force-setting/resetting bits in the EM Area is possible only for banks specified for the EM Area force-set/reset function. 
*2. Supported only by CJ2M CPU Units with unit version 2.0 or later. A Pulse I/O Module must be mounted. 
*3. Cannot be used in Function blocks. 
*4. Can be used only in Function blocks. 
*5. Supported only by the CJ2M-CPU3[]. 
*6. The EtherNet/IP port is built into CJ2M-CPU3[] only. 
*7. "Packets per second" is the number of communications packets that can be processed per second. 
*8. Unit version 2.0 of built-in EtherNet/IP section: 20 words. 
*9. If the maximum number is exceeded, refreshing will require more than one CPU Unit cycle. 
*10.When changing parameters, however, the EtherNet/IP port where the change is made will be restarted. In addition, a 
        timeout will temporarily occur at the other node that was communicating with that port, and it will then recover 
        automatically. 
*11.The EtherNet/IP port supports an IGMP client, so unnecessary multicast packets are filtered by using an Ethernet 
         switch that supports IGMP snooping.

Function Specifications

FunctionsDescription
Cycle 
Time 
Man- 
agement
Minimum Cycle TimeA minimum cycle time can be set. 
(0.2 to 32,000 ms; Unit: 0.1 ms) 
The minimum cycle time setting can be changed in MONITOR mode.
Cycle Time MonitoringThe cycle time is monitored. 
(0.01 to 40,000 ms; Unit: 0.01 ms)
Background ProcessingInstructions with long execution times can be executed over multiple cycles to prevent fluctuations in the cycle time.
Unit 
(I/O) 
Man- 
agement
Basic I/O 
Units, 
Special 
I/O Units, 
and CPU 
Bus Units
I/O 
Refreshing
Cyclic 
Refreshing
Cyclic refreshing of Basic I/O Units, Special I/O Units, and CPU Bus Units
Immediate 
Refreshing
I/O refreshing by immediate refreshing instructions
Refreshing 
by IORF
I/O refreshing by IORF instruction
Unit Recognition at StartupThe number of units recognized when the power is turned ON is displayed.
Basic I/O 
Units
Input Response Time SettingThe input response times can be set for Basic I/O Units. The response time can be increased to reduce the effects of chattering and noise at input contacts. The response time can be decreased to enable detecting shorter input pulses.
Load OFF FunctionAll of the outputs on Basic I/O Units can be turned OFF when an error occurs in RUN or MONITOR mode.
Basic I/O Unit Status MonitoringAlarm information can be read from Basic I/O Units and the number of Units recognized can be read.
Reading/writing data using instructions for specific UnitsSpecial instructions can be used to read/write required data for specific Units at high speed.
Special I/O 
Units and
CPU Bus 
Units
Unit Restart Bits to Restart UnitsA Special I/O Unit or CPU Bus Unit can be restarted.
Config- 
uration 
Man- 
agement
Automatic I/O Allocation at StartupI/O words can be automatically allocated to the Basic I/O Units that are connected in the PLC to start operation automatically without registering Units into I/O tables.
I/O Table CreationThe current unit configuration can be registered in I/O tables to prevent it from being changed, to reserve words, and to set words.
Rack/Slot First Word SettingsThe first words allocated to a Units on the Racks can be set.
Memory 
Man- 
agement
Holding I/O Memory when Changing Operating ModesThe status of I/O memory can be held when the operating mode is changed or power is turned ON. The forced-set/reset status can be held when the operating mode is changed or power is turned ON.
File MemoryFiles (such as program files, data files, and symbol table files) can be stored in Memory Card, EM File Memory, or Comment Memory.
Built-in Flash MemoryThe user program and Parameter Area can be backed up to an internal flash memory when they are transferred to the CPU Unit.
EM File FunctionParts of the EM Area can be treated as file memory.
Storing CommentsI/O comments can be stored as symbol table files in a Memory Card, EM file memory, or comment memory.
EM ConfigurationEM Area can be set as trace memory or EM file memory.
Memory 
Cards
Automatic File Transfer at StartupA program file and parameter files can be read from a Memory Card when the power is turned ON.
Program Replacement during PLC OperationUser programs can be transferred from a Memory Card to CPU Unit during operation.
Function for Reading and Writing Data from a Memory CardData in I/O memory in the CPU Unit can be written to a Memory Card in CSV/TXT format. Data in CSV/TXT format in the Memory Card can be read to I/O memory in the CPU Unit.
Communications-
Peripheral (USB) PortPeripheral BusBus for communications with various kinds of Support Software running on a personal computer. High-speed communications are supported.
Serial Port (Option) *12Application is possible when a Serial Communications Option Board is mounted.
Host Link (SYSWAY) CommunicationsHost Link commands or FINS commands placed between Host Link headers and terminators can be sent from a host computer or PT to read/write I/O memory, read/control the operating mode, and perform other operations for PLC.
No-protocol CommunicationsI/O instructions for communications ports (such as TXD/RXD instructions) can be used for data transfer with peripheral devices such as bar code readers and printers.
NT Link CommunicationsI/O memory in the PLC can be allocated and directly linked to various PT functions, including status control areas, status notification areas, touch switches, lamps, memory tables, and other objects.
Peripheral BusBus for communications with various kinds of Support Software running on a personal computer. High-speed communications are supported.
Serial GatewayThis gateway enables receiving and automatically converting FINS to the CompoWay/F.
Serial PLC LinksData is exchanged between CPU Units using serial ports without communications programming. PTs set to the 1:N NT Link protocol can be included in the network.
EtherNet/IP Port *13100Base-TX/10Base-T 
Protocols: TCP/IP, UDP, ARP, ICMP (ping only), BOOTP 
Applications: FINS, CIP, SNTP, DNS (Client), FTP (Server)
CIP 
Commun- 
ications 
Service
Tag Data LinksProgramless cyclic data exchanges with the devices on the EtherNet/IP network.
Message 
Communications
Any CIP commands can be received from the devices on the EtherNet/IP network.
FINS 
Commun- 
ications 
Service
Message 
Communications
Any FINS commands can be transferred with the devices on the EtherNet/IP network.
InterruptScheduled InterruptsTasks can be executed at a specified interval (minimum of 0.2 ms, Unit: 0.1 ms).
Resetting and restarting with MSKS (690)When MSKS(690) is executed, the internal timer is restarted and the time to first interrupt is set to a fixed value.
Reading present value of internal timer with MSKS (690)MSKS(690) can be used to read the time that has elapsed until the schedule interrupt is started or since the previous scheduled interrupt.
Power OFF InterruptsA task can be executed when CPU Unit's power turns OFF.
I/O Interrupt TasksA task can be executed when an input signal is input to an Interrupt Input Unit.
External Interrupt TasksA task can be executed when interrupts are requested from a Special I/O Unit or a CPU Bus Unit.
ClockClock FunctionClock data is stored in memory. 
Accuracy (Accuracy depends on the temperature.) 
Ambient temperature of 55 °C: - 3.5 to +0.5 min error per month 
Ambient temperature of 25 °C: - 1.5 to +1.5 min error per month 
Ambient temperature of 0 °C: - 3 to +1 min error per month
Operation Start Time StorageThe time when operating mode was last changed to RUN mode or MONITOR mode is stored.
Operation Stop Time StorageThe last time a fatal error occurred or the last time the operating mode was changed to PROGRAM mode is stored.
Startup Time StorageThe time when the power was turned ON is stored.
Power Interruption Time StorageThe time when the power is turned OFF is stored.
Total Power ON Time CalculationThe total time that the PLC has been ON is stored in increments of 10 hours.
Power ON Clock Data StorageA history of the times when the power was turned ON is stored.
User Program Overwritten Time StorageThe time that the user program was last overwritten is stored.
Parameter Date StorageThe time when the Parameter Area was overwritten is stored.
Power 
Supply 
Man- 
agement
Memory ProtectionHolding Area data, DM Area data, EM Area data, Counter Completion Flags, and counter present values are held even when power is turned OFF. CIO Area, Work Area, some Auxiliary Area data, and Timer Completion Flags, timer present values, index registers, and data registers can be protected by turning ON the IOM Hold Bit in the Auxiliary Area, and by also setting the IOM Hold Bit to "Hold" in the PLC Setup.
Power OFF Detection Time SettingThe detection time for power interruptions can be set. 
AC power supply: 10 to 25 ms (variable) 
DC power supply: 2 to 5 ms (CJ1W-PD022) or 2 to 20 ms (CJ1W-PD025)
Power OFF Detection Delay TimeThe detection of power interruptions can be delayed: 0 to 10 ms 
(Not supported by the CJ1W-PD022.)
Number of Power Interruptions CounterThe number of times power has been interrupted is counted.
Function BlocksStandard programming can be encapsulated as function blocks.
Languages in Function Block DefinitionsLadder programming or structured text
De- 
bugging
Online EditingThe program can be changed during operation (in MONITOR or PROGRAM mode), except for block programming areas.
Force-Set/ResetSpecified bits can be set or reset. 
Force-set/reset to the EM Area is enabled by specifying a start bank in parameter setting.
Differentiate MonitoringON/OFF changes in specified bits can be monitored.
Data TracingThe specified I/O memory data can be stored in the trace memory in the CPU Unit. The triggers can be set.
Continuous TracingThe trace data can be uploaded during data tracing using CX-Programmer, which enables continuously logging the data by constantly uploading the trace data.
Automatically starting tracing when operation startsData tracing can be automatically started when operation is started (i.e., when the operating mode is changed from PROGRAM mode to MONITOR or RUN mode).
Storing Location of Error when an Error OccursThe location and task number where execution stopped for a program error is recorded.
Program CheckThe programs can be checked for items such as no END instruction and FALS/FAL errors at startup.
Self- 
diagnosis
and 
Res- 
toration
Error LogA function is provided to store predefined error codes in CPU Unit, error information, and time at which the error occurred.
CPU Error DetectionCPU Unit WDT errors are detected.
User-defined Failure DiagnosisErrors can be generated for user-specified conditions: Non-fatal errors (FAL) and fatal errors (FALS). 
Program section time diagnosis and program section logic diagnosis are supported (FPD instruction).
Load OFF FunctionThis function turns OFF all outputs from Output Units when an error occurs.
RUN OutputThe RUN output from the CJ1W-PA205R turns ON while CPU Unit is in RUN mode or MONITOR mode.
Basic I/O Load Short-circuit DetectionThis function provides alarm information from Basic I/O Units that have load short-circuit protection.
Failure Point DetectionThe time and logic of an instruction block can be analyzes using the FPD instruction.
CPU Standby DetectionThis function indicates when the CPU Unit is on standby because all Special I/O Units and CPU Bus Units have not been recognized at the startup in RUN or MONITOR mode.
Non-fatal 
Error 
Detection
System FAL Error Detection (User-defined non-fatal error)This function generates a non-fatal (FAL) error when the user-defined conditions are met in program.
Duplicate Refreshing Error DetectionThis function detects an error when an immediate refreshing Instruction in an interrupt task is competing with I/O refreshing of a cyclic task.
Basic I/O Unit Error DetectionThis function detects the errors in Basic I/O Units.
Backup Memory Error DetectionThis function detects errors in the memory backup of the user programs and parameter area (backup memory).
PLC Setup Error DetectionThis function detects setting errors in the PLC Setup.
CPU Bus Unit Error DetectionThis function detects an error when there is an error in data exchange between the CPU Unit and a CPU Bus Unit.
Special I/O Unit Error DetectionThis function detects an error when there is an error in data exchange between the CPU Unit and a Special I/O Unit.
Tag Memory Error Detection *13This function detects errors in tag memory.
Battery Error DetectionThis function detects an error when a battery is not connected to the CPU Unit or when the battery voltage drops.
CPU Bus Unit Setting Error DetectionThis function detects an error when the model of a CPU Bus Unit in the registered I/O tables does not agree with the model that is actually mounted in the PLC.
Special I/O Unit Setting Error DetectionThis function detects an error when the model of a Special I/O Unit in the registered I/O tables does not agree with the model of Unit that is actually mounted.
Option Board Error Detection *13This function detects the errors in Serial Option Board mounting status.
Fatal 
Error 
Detection
Memory Error DetectionThis function detects errors that occur in memory of the CPU Unit.
I/O Bus Error DetectionThis function detects when an error occurs in data transfers between the Units mounted in Rack slots and the CPU Unit and detects when the End Cover is not connected to the CPU Rack or an Expansion Rack.
Unit/Rack Number Duplication ErrorThis function detects an error when the same unit number is set for two or more Units, the same word is allocated to two or more Basic I/O Units, or the same rack number is set for two or more Racks.
Too Many I/O Points Error DetectionThis function detects an error when the total number of I/O points set in the I/O tables or the number of Units per Rack exceeds the specified range.
I/O Setting Error DetectionThis function detects an error when the number of Units in the registered I/O tables does not agree with the actual number of Units that is mounted, or an Interrupt Unit has been connected in the wrong position, i.e., not in slot 0 to 4.
Program Error DetectionThis function detects errors in programs.
Instruction 
Processing 
Error Detection
This function detects an error when the given data value is invalid when executing an instruction, or execution of instruction between tasks was attempted.
Indirect DM/EM 
BCD Error 
Detection
This function detects an error when an indirect DM/EM address in BCD mode is not BCD.
Illegal Area 
Access Error 
Detection
This function detects an error when an attempt is made to access an illegal area with an instruction operand.
No END Error 
Detection
This function detects an error when there is no END instruction at the end of the program.
Task Error 
Detection
This function detects an error when there are no tasks that can be executed in a cycle, there is no program for a task, or the execution condition for an interrupt task was met but there is no interrupt task with the specified number.
Differentiation 
Overflow Error 
Detection
This function detects an error when too many differentiated instructions are entered or deleted during online editing (131,072 times or more).
Invalid 
Instruction Error 
Detection
This function detects an error when an attempt is made to execute an instruction that is not defined in the system.
User Program 
Area Overflow 
Error Detection
This function detects an error when instruction data is stored after the last address in user program area.
Cycle Time Exceeded Error DetectionThis function monitors the cycle time (10 to 40,000 ms) and stops the operation when the set value is exceeded.
System FALS Error Detection (User-defined Fatal Error)This function generates a fatal (FALS) error when the user-defined conditions are met in program.
Version Error DetectionThis function detects an error when a user program includes a function that is not supported by the current unit version.
Memory Card Transfer Error DetectionThis function detects an error when the automatic file transfer from Memory Card fails at startup.
Main- 
tenance
Simple Backup FunctionThis function collectively backs up the data in CPU Unit (user programs, parameters, and I/O memory) and internal backup data in the I/O Units.
Unsolicited CommunicationsA function that allows the PLC to use Network Communications Instruction to send required FINS commands to a computer connected via a Host Link
Remote Programming and MonitoringHost Link communications can be used for remote programming and remote monitoring through a Controller Link, Ethernet, DeviceNet, or SYSMAC LINK Network. Communications across network layers can be performed. 
Controller Link or Ethernet: 8 layers 
DeviceNet or SYSMAC LINK: 3 layers
Automatic Online Connection via NetworkDirect Serial 
Connection
This function enables automatically connecting to the PLC online when the CX-Programmer is directly connected by a serial connection (peripheral (USB) port or serial port).
Via NetworksThis function enables connecting the CX-Programmer online to a PLC that is connected via an EtherNet/IP network.
SecurityRead Protection using PasswordThis function protects reading and displaying programs and tasks using passwords. 
Write protection: Set using the DIP switch. 
Read protection: Set a password using the CX-Programmer.
FINS Write ProtectionThis function prohibits writing by using FINS commands sent over the network.
Unit Name FunctionThis function allows the users to give any names to the Units. Names are verified at online connection to prevent wrong connection
Hardware ID Using Lot NumbersThis function sets operation protection by identifying hardware using the user programs according to lot numbers stored in the Auxiliary Area.
*12. A Serial Option Board is required to use a serial port for the CJ2M-CPU3[] CJ2M CPU Unit. 
*13. Supported only by the CJ2M-CPU3[].

Pulse I/O Functions

The following functions of CJ2M can be used by installing one or two Pulse I/O Modules. Each module has 10 high-speed inputs and 6 high-speed outputs. Pulse I/O Modules can be installed on CJ2M CPU Units with Unit Version 2.0 or Later.
  • The inputs can be used as general-purpose inputs, interrupt inputs, quick-response inputs, high-speed counters, or origin search inputs.
  • The outputs can be used as general-purpose outputs, pulse outputs, origin search outputs, or PWM outputs.

One Pulse I/O Module can be mounted

CJ2M-CPU3[] / CPU1[] / MD21[] Specifications 8

Two Pulse I/O Modules can be mounted

CJ2M-CPU3[] / CPU1[] / MD21[] Specifications 9
Note: The Pulse I/O Module closest to the CPU Unit is Pulse I/O Module 0 and the other one is Pulse I/O Module 1.

Performance Specifications

ItemDescription
Pulse
I/O
Model of Pulse I/O 
Modules
CJ2M-MD211 (Sinking-type) 
CJ2M-MD212 (Sourcing-type )
External Interface40-pin MIL connector
Pulse InputsCan be used as normal inputs, interrupt inputs, quick-response inputs, or high-speed 
counter inputs. 
(Function of each input must be selected in the PLC Setup.) 
Input method: Line-driver input or 24-VDC input (selected by wiring)
Normal Inputs20 max. (10 per Pulse I/O Module) 
Input constants: Set in the PLC Setup (0, 0.5, 1, 2, 4, 8, 16, or 32 ms). Default: 8 ms
Interrupt Inputs and 
Quick-response 
Inputs
8 max. (4 per Pulse I/O Module) 
Input signal minimum ON pulse width: 30 μs
High-speed Counter
Inputs
4 max. (2 per Pulse I/O Module) 
Input method: Differential-phase (×4) pulses, pulse + direction, up/down pulses, or 
increment pulse 
Maximum response frequency: 50 kHz for differential phases or 100 kHz for single 
phase 
Counting mode: Linear mode or circular (ring) mode 
Count value: 32 bits 
Counter reset: Phase Z + software reset or software reset 
Control method: Target-value comparison or range comparison 
Gate function: Supported
Pulse OutputsCan be used as normal outputs, pulse outputs, or PWM outputs. (Function of each 
output must be selected in the PLC Setup.) 
Output method: Sinking or sourcing transistor outputs (The method is determined by 
Pulse I/O Module model.)
Normal Outputs12 max. (6 per Pulse I/O Module)
Pulse Outputs4 max. (2 per Pulse I/O Module) 
Output method: CW/CCW or pulse + direction (The method is determined by the I/O 
wiring and the instructions used in the ladder program.) 
Output frequency: 1 pps to 100 kpps (in increments of 1 pps) 
Output Mode: Continuous mode (for speed control) or independent mode (for position 
control) 
Output pulses: Relative coordinates: 0000 0000 to 7FFF FFFF hex (0 to 2,147,483,647 
pulses) 
Absolute coordinates: 8000 0000 to 7FFF FFFF hex (-2,147,483,648 to 2,147,483,647)
Acceleration/deceleration curves: Linear or S-curve 
Origin search function: Supported
PWM Outputs4 max. (2 per Pulse I/O Module) 
Output frequency: 0.1 to 6,553.5 Hz (in 0.1-Hz increments) or 1 to 32,800 Hz (in 1-Hz 
increments) 
Duty ratio: 0.0% to 100.0% (in 0.1% increments)

Function Specifications

FunctionsDescription
Pulse I/O 
Functions
Pulse 
Input 
Func- 
tions
Normal InputsInput signals are read during I/O refreshing and stored in I/O memory.
Interrupt InputsAn interrupt task can be started when an input signal turns ON or turns OFF.
Quick-response 
Inputs
Input signals that are shorter than the cycle time are read and stored in I/O 
memory.
High-speed 
Counter Inputs
High-speed pulse signals are counted. Interrupt tasks can also be started.
Pulse 
Output
Func- 
tions
Normal OutputsThe status of I/O memory is output during I/O refreshing.
Pulse OutputsA pulse signal is output with the specified frequency and number of pulses 
at a fixed duty ratio (50%).
PWM OutputsA pulse signal is output at the specified duty ratio.
Origin SearchesThe origin point of the machine is determined according to the specified 
origin search parameters while actually outputting pulses and using the 
origin and origin proximity input signals as conditions. (Pulse inputs and 
outputs are also used for this function.)
InterruptInput Interrupt FunctionA task is started for an interrupt input from a Pulse I/O Module or for a high- 
speed counter input.
Input InterruptsInterrupt tasks are executed when the interrupt input turns ON or turns OFF. 
Direct Mode: An interrupt task is executed each time an input signal changes. 
Counter Mode: Changes in the input signal are counted up or down and the
interrupt task is executed when the counter counts out. (The maximum 
response frequency is 3 kHz.)
High-speed Counter 
Interrupts
An interrupt task is executed when preset comparison conditions for a high- 
speed counter are met. 
Target-value comparison: The interrupt task is executed when the count 
matches a specified value. 
Range comparison: The interrupt task is executed when the count enters or 
leaves a specified range of values.

Pulse Input Functions

Interrupt Inputs

ItemDirect ModeCounter Mode
Number of interrupt inputsMax.8 inputs
Allocated bitCIO 2960 and CIO 2962,bits 00 to 03
Interrupt detection methodON-to-OFF or OFF-to-ON transitions
Interrupt task numbers140 to 147 (fixed)
Counting method---Incrimenting or decrementing 
(Set with the MSKS(690)instruction.)
Counting range---0001 to FFFF hex (16 bits) 
(Set in A532 to A535 and A544 to A547.)
Response frequency---Single-phase:3 kHz x 8 inputs
Storage locations for PVs for 
interrupt inputs in Counter Mode
---A536 to A539 and A548 to A551

Quick-response inputs

ItemSpecifications
Number of Quick-response inputsMax. 8 inputs
Quick-response inputsSignals that are shorter than the cycle time are latched for one PLC cycle, so they 
can be detected in the PLC program. Minimum detectable pulse width is 30 μs.

High-speed Counter Inputs

ItemDescription
Number of High-speed 
Counter Inputs
Max. 4 inputs
Pulse input method 
(counting mode)
Incremental pulse inputsDifferential phase input 
(4×)
Up/down inputsPulse + direction 
inputs
Input signalsIncrement pulsePhase AUp pulsePulse
---Phase BDown pulseDirection
---Phase ZResetReset
Frequency and number 
of high-speed counters
100 kHz, 2 inputs × 2 
I/O Modules
50 kHz, 2 inputs × 2 
I/O Modules
100 kHz, 2 inputs 
× 2 I/O Modules
100 kHz, 2 inputs 
× 2 I/O Modules
Counting modeLinear mode or ring mode
Count valueLinear mode: 8000 0000 to 7FFF FFFF hex 
0000 0000 to FFFF FFFF hex (for increment pulse) 
Ring mode: 0000 0000 to Max. ring value
High-speed counter PV 
storage locations
High-speed counter 0: A271 (upper 4 digits) and A270 (lower 4 digits) 
High-speed counter 1: A273 (upper 4 digits) and A272 (lower 4 digits) 
High-speed counter 2: A317 (upper 4 digits) and A316 (lower 4 digits) 
High-speed counter 3: A319 (upper 4 digits) and A318 (lower 4 digits) 
Refreshed during overseeing processing. Use PRV(881) to read the most recent PVs.
Data format: 8 digit hexadecimal 
Linear mode: 8000 0000 to 7FFF FFFF hex 
0000 0000 to FFFF FFFF hex (for increment pulse) 
Ring mode: 0000 0000 to Max. ring value
Control 
method
Target value 
comparison
Up to 48 target values and corresponding interrupt task numbers can be registered.
Range 
Comparison
Up to 8 or up to 32 ranges can be registered, with a separate upper limit, lower limit, and 
interrupt task number for each range.
Counter reset methodPhase-Z + Software reset 
The counter is reset when the phase-Z input goes ON while the Reset Bit (A531.00 to 
A531.03) is ON. 
Software reset 
The counter is reset when the Reset Bit (A531.00 to A531.03) is turned ON. 
Operation can be set to stop or continue the comparison operation when the high-speed 
counter is reset.

Pulse Output Functions

Position Control and Speed Control

ItemSpecifications
Number of Pulse OutputsMax. 4 outputs (Pulse Output 00 to 03)
Output modeContinuous mode (for speed control) or independent mode (for position control)
Positioning (independent 
mode) instructions
PULS (886) and SPED (885), PULS (886) and ACC (888), or PULS2 (887) instruction
Speed control (continuous 
mode) instructions
SPED (885) and ACC (888) instructions
Origin (origin search and origin
return) instructions
ORG (889) instruction
Interrupt feeding instructionIFEED (892) instruction
Output frequency1 pps to 100 kpps (1 pps units), two pulse outputs × 2 Pulse I/O Modules
Frequency acceleration and 
eceleration rates
Set in increments of 1 pps for acceleration/deceleration rates from 1 to 65,535 pps 
(every 4 ms). 
The acceleration and deceleration rates can be set independently only with the PLS2 
(887) instruction.
Changing SVs during 
instruction execution
The target frequency, acceleration/deceleration rate, and target position can be 
changed.
Pulse output methodCW/CCW or pulse + direction
Number of output pulsesRelative coordinates: 0000 0000 to 7FFF FFFF hex (Accelerating or decelerating in 
either direction: 2,147,483,647) 
Absolute coordinates: 8000 0000 to 7FFF FFFF hex (-2,147,483,648 to 2,147,483,647)
Relative/absolute coordinate 
specifications for pulse output 
PVs
Absolute coordinates are specified automatically when the origin location has been 
defined by changing the pulse output PV with the INI (880) instruction or performing 
an origin search with the ORG(889) instruction. Relative coordinates must be used 
when the origin is undefined.
Relative pulse/absolute pulse 
specifications
The pulse type can be specified with an operand in the PULS (886) or PLS2 (887) 
instruction. 
Absolute pulses can be used when absolute coordinates are specified for the pulse 
output PV, i.e. the origin location has been defined. Absolute pulse cannot be used 
when relative coordinates are specified, i.e., when the origin location is undefined. 
An instruction error will occur.
Pulse output PV's storage 
location
The following Auxiliary Area words contain the pulse output PVs 
Pulse output 0: A277 (leftmost 4 digits) and A276 (rightmost 4 digits) 
Pulse output 1: A279 (leftmost 4 digits) and A278 (rightmost 4 digits) 
Pulse output 2: A323 (leftmost 4 digits) and A322 (rightmost 4 digits) 
Pulse output 3: A325 (leftmost 4 digits) and A324 (rightmost 4 digits) 
The PVs are refreshed during regular I/O refreshing.

Variable-duty Pulse Outputs (PWM)

ItemSpecifications
Number of PWM OutputsMax.4 outputs (PWM Output 00 to 03)
Duty ratio0.0%to 100.0%in 0.1%increments
Frequency0.1 Hz to 6,553.5 Hz (Set in 0.1-Hz increments.) 
1 Hz to 32,800 Hz (Set in 1-Hz increments.)
Output modeContinuous Mode
InstructionPWM (891)instruction

Pulse I/O Modules

Input Specifications (IN00 to IN09/IN10 to IN19 )

Normal Inputs

InputsIN00 to IN05 and
IN10 to IN15
IN06 to IN09 and
IN16 to IN19
IN00 to IN05 and 
IN10 to IN15
IN06 to IN09 and 
IN16 to IN19
Input form24 VDC inputsLine driver inputs
Input current6.0 mA typical5.5 mA typical13 mA typical10 mA typical
Input voltage range24 VDC +10%/-15%RS-422A or RS-422 line driver (conforming to AM26LS31),
Power supply voltage of 5 V ±5%
Input impedance3.6 kΩ4.0 kΩ---
Number of circuits1 common,1 circuit
ON voltage/current17.4 VDC min.,3 mA min.---
OFF voltage/current1 mA max.at 5 VDC max.---
ON response time8 ms max.(The input time constant can be set to 0,0.5,1,2,4,8,16,or 32 ms in the PLC Setup.)
OFF response time8 ms max.(The input time constant can be set to 0,0.5,1,2,4,8,16,or 32 ms in the PLC Setup.)

Input Circuit Configuration

ItemSpecifications
InputIN00 to IN05/IN10 to IN15IN06 to IN09/IN16 to IN19
Circuit configuration

Interrupt Input and Quick-response Input Specifications (IN00 to IN03 and IN10 to IN13)

ItemSpecifications
ON response time30 μs max.
OFF response time150 μs max.
Response pulse

High-speed Counter Input Specifications (IN06 to IN09 and IN16 to IN19)

24-VDC inputLine driver input
Set to 60 kHzPhase-A/Phase-B encoder input, Single-phase 
60-kHz pulse input with 50% duty ratio 
2712_sp_16_1


Phase-A/Phase-B encoder inputs, Differential 
phases, 30 kHz
2712_sp_16_2
Encoder input phase A or B, single-phase 60- 
kHz pulse input with 50% duty ratio 
2712_sp_16_6


Phase-A/Phase-B encoder inputs, Differential 
phases, 30 kHz
2712_sp_16_7
Set to 100 kHzPhase-A/Phase-B encoder input, Single-phase 
100-kHz pulse input with 50% duty ratio 
2712_sp_16_3


Phase-A/Phase-B encoder inputs, Differential 
phases, 50 kHz
2712_sp_16_4
Single-phase 100-kHz pulse input with 50% duty 
ratio 
2712_sp_16_8


Differential-phase 50-kHz pulse input
2712_sp_16_9
Phase Z/ 
reset input
Encoder input phase Z (IN02/IN03 or IN12/IN13)
2712_sp_16_5
Encoder input phase Z (IN02/IN03 or IN12/IN13)
2712_sp_16_10

Output Specifications (OUT00 to OUT05 and OUT10 to OUT15)

ItemSpecifications
Output SpecificationsSinking-type (CJ2M-MD211)Sourcing-type (CJ2M-MD212)
Rated voltage5 to 24 VDC
Allowable voltage range4.75 to 26.4 VDC
Maximum switching current0.3 A/output,1.8 A/Unit
Number of circuits6 outputs (6 outputs/common)
Maximum inrush current3.0 A/output,10 ms max.2.0 A/output,10 ms max.
Leakage current0.1 mA max.
Residual voltage0.6 V max.
ON response time0.1 ms max.
OFF response time0.1 ms max.
FuseNone
External supply power 
(power supply input for 
outputs)
10.2 to 26.4 VDC,20 mA min.
Circuit configuration

Pulse Outputs (OUT00 to OUT03 and OUT10 to OUT13)

ItemSpecifications
Output SpecificationsSinking-type (CJ2M-MD211)Sourcing-type (CJ2M-MD212)
Rated voltage5 to 24 VDC
Allowable voltage range4.75 to 26.4 VDC
Maximum switching capacity30 mA
Minimum switching capacity7 mA
Maximum output frequency100 kHz
Output waveform

PWM Outputs (OUT04, OUT05, OUT14, and OUT15)

ItemSpecifications
Output SpecificationsSinking-type (CJ2M-MD211)Sourcing-type (CJ2M-MD212)
Rated voltage5 to 24 VDC
Allowable voltage range4.75 to 26.4 VDC
Maximum switching capacity6.5535 kHz or less:300 mA,6.5535 to 32.8 kHz:100 mA
Maximum output frequency32,800 Hz
PWM output accuracy 
(for ON pulse width of 2 μs or longer)
ON duty at 6.5535 kHz or less:-0.2%to +1%, 
ON duty at 32.8 kHz:-1%to +5% 
(at switching current of 30 mA)
ON duty at 6.5535 kHz or less:±0.5%, 
ON duty at 32.8 kHz:+2.5% 
(at switching current of 30 mA)
Output waveform

CJ2M-CPU3[] / CPU1[] / MD21[]

Since 2001, CJ1M-series PLCs are in control of a wide variety of applications worldwide. The accumulated experience and advancements in technology now result in CJ2M; fully compatible, yet fully new.


International Standards

  • The standards are abbreviated as follows: U: UL, U1: UL (Class I Division 2 Products for Hazardous Locations), C: CSA, UC: cULus, UC1: cULus (Class I Division 2 Products for Hazardous Locations), CU: cUL, N: NK, L: Lloyd, and CE: EC Directives.
  • Contact your OMRON representative for further details and applicable conditions for these standards.

CJ2M CPU Units (Built-in EtherNet/IP)

Product 
name
SpecificationsCurrent 
consump- 
tion (A)
ModelStand- 
ards
I/O 
capacity/ 
Mountable 
Units 
(Expansion 
Racks)
Pro- 
gram 
ca- 
pacity
Data 
memory 
capacity
LD 
instruc- 
tion 
exe- 
cution 
time
EtherNet/ 
IP 
function
Option 
board 
slot
5 V24 V
CJ2M 
(Built-in 
EtherNet/ 
IP) CPU 
Units
2712_lu_1_1
2,560 
points/ 
40 Units 
(3 
Expansion 
Racks 
max.)
60K 
steps
160K 
words 
(DM: 32K 
words, 
EM: 32K 
words × 
4 banks)
0.04 
μs
YESYES0.7 
*
-CJ2M-CPU35UC1, 
N, L, 
CE
30K 
steps
CJ2M-CPU34
20K 
steps
64K words 
(DM: 32K 
words, 
EM: 32K 
words × 
1 bank)
CJ2M-CPU33
10K 
steps
CJ2M-CPU32
5K 
steps
CJ2M-CPU31
* Add 0.005A, 0.030A and 0.075A when using Serial Communications Option Boards (CP1W-CIF01/11/12), respectively. 
    Add 0.15A/Unit when using NT-AL001 RS-232C/RS-422A Adapters. 
    Add 0.04A/Unit when using CJ1W-CIF11 RS-422A Adapters. 
    Add 0.20A/Unit when using NV3W-M[]20L(-V1) Programmable Terminals.

CJ2M CPU Units

Product 
name
SpecificationsCurrent 
consump- 
tion (A)
ModelStand- 
ards
I/O 
capacity/ 
Mountable 
Units 
(Expansion 
Racks)
Pro- 
gram 
ca- 
pacity
Data 
memory 
capacity
LD 
instruc- 
tion 
exe- 
cution 
time
EtherNet/ 
IP 
function
Option 
board 
slot
5 V24 V
CJ2M 
CPU 
Units
2712_lu_2_1
2,560 
points/ 
40 Units 
(3 
Expansion 
Racks 
max.)
60K 
steps
160K 
words 
(DM: 32K 
words, 
EM: 32K 
words × 
4 banks)
0.04 μs--0.5 
*
-CJ2M-CPU15UC1, 
N, L, 
CE
30K 
steps
CJ2M-CPU14
20K 
steps
64K words 
(DM: 32K 
words, 
EM: 32K 
words × 
1 bank)
CJ2M-CPU13
10K 
steps
CJ2M-CPU12
5K 
steps
CJ2M-CPU11
* Add 0.15A/Unit when using NT-AL001 RS-232C/RS-422A Adapters. 
   Add 0.04A/Unit when using CJ1W-CIF11 RS-422A Adapters. 
   Add 0.20A/Unit when using NV3W-M[]20L(-V1) Programmable Terminals.

Serial Communications Option Boards (Only CJ2M-CPU3[])

The serial communications port can be equipped by installing the serial communications option board to the option board slot in front of CPU unit.
Product nameSpecificationsSerial 
communications 
mode
Current 
consump- 
tion (A)
ModelStand- 
ards
5 V24 V
RS-232C 
Option Board
2712_lu_3_1
One RS-232C port 
Connector: D-Sub, 9 pin, female 
Maximum transmission distance: 15m 
One RS-232C connector (D-Sub, 9 pin, 
male) is included.
Host Link, 
1:N NT Link, 
Noprotocol, 
Serial PLC Link 
Slave, 
Serial PLC Link 
Master, 
Serial Gateway 
converted to 
CompoWay/F, 
and Tool Bus *
0.005---CP1W-CIF01UC1, 
N, L, 
CE
RS-422A/485 
Option Board
2712_lu_3_2
One RS-422A/485 port 
Terminal block: using ferrules 
Maximum transmission distance: 50m
0.03---CP1W-CIF11
RS-422A/485 
Isolated-type 
Option Board
2712_lu_3_3
One RS-422A/485 port (Isolated) 
Terminal block: using ferrules 
Maximum transmission distance: 500m
0.075---CP1W-CIF12
Note: It is not possible to use a CP-series Ethernet Option Board (CP1W-CIF41), LCD Option Board (CP1W-DAM01) with 
          a CJ2M CPU Unit. 
* The following modes cannot be used: 1:1 NT Link, Serial Gateway converted to Host Link FINS, 1:1 Link Master, and 
    1:1 Link Slave.

Pulse I/O Modules (Only CJ2M CPU Unit with Unit Version 2.0 or Later)

Optional Pulse I/O Modules can be mounted to enable pulse I/O. Up to two Pulse I/O Modules can be mounted to the left side of a CJ2M CPU Unit.
Product 
name
SpecificationsCurrent 
consumption 
(A)
ModelStand- 
ards
5 V24 V
Pulse I/O 
Modules
2712_lu_4_1
Sinking outputs, MIL connector 
10 inputs (including four interrupt/quickresponse inputs and 
two high-speed counter inputs) 
6 outputs (including two pulse outputs and two PWM outputs)
0.08---CJ2M-MD211UC1, 
N, L, 
CE
Sourcing outputs, MIL connector CE 
10 inputs (including four interrupt/quickresponse inputs and 
two high-speed counter inputs) 
6 outputs (including two pulse outputs and two PWM outputs)
0.08---CJ2M-MD212
Note: Connectors are not provided with Pulse I/O Modules. Purchase the following Connector, an OMRON Cable with 
          Connectors for Connector Terminal Block Conversion Units, or an OMRON Cable with Connectors for Servo Relay 
          Units.

Connecting to Pulse I/O Modules

Product 
name
SpecificationsModelStand- 
ards
Applicable 
Connector
2712_lu_5_1
MIL Flat Cable Connectors (Pressure-fitted Connectors)XG4M-4030-T---
Connector- 
Terminal 
Block 
Conversion 
Units
Phillips screw (M3 screw terminals, 40-terminals)
2712_lu_5_2
XW2R-J40G-T---
Slotted screw (M3 European type, 40-terminals)
2712_lu_5_3
XW2R-E40G-T
Push-in spring (Clamp 40-terminals)
2712_lu_5_4
XW2R-P40G-T
Cable for 
Connector- 
Terminal 
Block 
Conversion 
Unit
2712_lu_5_5
Cable length: 0.25 mXW2Z-C25K
Cable length: 0.5 mXW2Z-C50K
Cable length: 1 mXW2Z-100K
Cable length: 1.5 mXW2Z-150K
Cable length: 2 mXW2Z-200K
Cable length: 3 mXW2Z-300K
Cable length: 5 mXW2Z-500K
Servo Relay 
Units
Servo Relay Unit for 1 axis
2712_lu_5_6
XW2B-20J6-8A---
Servo Relay Unit for 2 axes
2712_lu_5_7
XW2B-40J6-9A
Cables for 
Servo Relay 
Units
OMNUC 
G5/G Series
Cable for Pulse I/O Modules
2712_lu_5_8
Cable length: 0.5 mXW2Z-050J-A33---
Cable length: 1 mXW2Z-100J-A33
Servo Driver Connecting Cables
2712_lu_5_9
Cable length: 1 mXW2Z-100J-B31
Cable length: 2 mXW2Z-200J-B31
SMARTSTEP2Cable for Pulse I/O Modules
2712_lu_5_10
Cable length: 0.5 mXW2Z-050J-A33
Cable length: 1 mXW2Z-100J-A33
Servo Driver Connecting Cables
2712_lu_5_11
Cable length: 1 mXW2Z-100J-B32
Cable length: 2 mXW2Z-200J-B32
SMARTSTEP 
Junior
Cable for Pulse I/O Modules
2712_lu_5_12
Cable length: 1 mXW2Z-100J-A26
Servo Driver Connecting Cables
2712_lu_5_13
Cable length: 1 mXW2Z-100J-B17
Cable length: 2 mXW2Z-200J-B17
SMARTSTEP 
A Series
Cable for Pulse I/O Modules
2712_lu_5_14
Cable length: 1 mXW2Z-100J-A26
Servo Driver Connecting Cables
2712_lu_5_15
Cable length: 1 mXW2Z-100J-B5
Cable length: 2 mXW2Z-200J-B5

Accessories

The following accessories come with CPU Unit:
ItemSpecification
BatteryCJ1W-BAT01
End CoverCJ1W-TER01 (necessary to be mounted at the right end of CPU Rack)
End PlatePFP-M (2 pcs)
Serial Port (RS-232C) Connector *Connector set for serial port connection (D-SUB 9-pin male connector)
* Connector is provided with CJ2M-CPU1[].