CJ-series Input Units CJ1W-ID / IA


A wide range of CJ series input units are available featuring high-speed input and suitability for various applications. This unit is available for CJ/NJ controllers.

Features  CJ1W-ID / IA

High-speed input models are available, meeting versatile applications.
ON Response Time: 15μs, OFF Response Time: 90μs
Use 24-VDC, 100-VAC, and 200-VAC models to connect to devices with different types of outputs.
The 24-VDC models can be connected to devices with either NPN or PNP outputs. There is no need to select the polarity. *1
A digital filter in the Unit can be set from 0 to 32 ms to reduce the influence of external noise.
Either a Fujitsu or MIL connector interface can be used. *2
Several models of Terminal Block Conversion Units are available, making it easy to connect to external devices.
*1. The same polarity is used for the same common. 
*2. For models with 32 or 64 inputs.

International Standards

  • The standards are abbreviated as follows: U: UL, U1: UL (Class I Division 2 Products for Hazardous Locations), C: CSA, UC: cULus, UC1: cULus (Class I Division 2 Products for Hazardous Locations), CU: cUL, N: NK, L: Lloyd, and CE: EC Directives.
  • Contact your OMRON representative for further details and applicable conditions for these standards.

Input Units

Unit 
type
Product
name
SpecificationsCurrent 
consump- 
tion (A)
ModelStand- 
ards
I/O 
points
Input 
voltage 
and 
current
CommonsExternal 
con- 
nection
No. of 
words 
allo- 
cated
5 V24 V
CJ1 
Basic
I/O 
Units
DC 
Input 
Units
2054_lu_1_1
8 inputs12 to 
24 VDC, 
10 mA
Independent
contacts
Removable 
terminal 
block
1 word0.09---CJ1W-ID201UC1, 
N, L, 
CE
16 inputs24 VDC, 
7 mA
16 points, 
1 common
Removable 
terminal 
block
1 word0.08---CJ1W-ID211
16 inputs
(High 
speed)
24 VDC, 
7 mA
16 points, 
1 common
Removable 
terminal 
block
1 word0.13---CJ1W-ID212N, L, 
CE
32 inputs24 VDC, 
4.1 mA
16 points, 
1 common
Fujitsu 
connector
2 words0.09---CJ1W-ID231UC1, 
N, L, 
CE
32 inputs24 VDC, 
4.1 mA
16 points, 
1 common
MIL 
connector
2 words0.09---CJ1W-ID232
32 inputs
(High 
speed)
24 VDC, 
4.1 mA
16 points, 
1 common
MIL 
connector
2 words0.20---CJ1W-ID233N, L, 
CE
64 inputs24 VDC, 
4.1 mA
16 points, 
1 common
Fujitsu 
connector
4 words0.09---CJ1W-ID261UC1, 
N, L, 
CE
64 inputs24 VDC, 
4.1 mA
16 points, 
1 common
MIL 
connector
4 words0.09---CJ1W-ID262
AC 
Input 
Units
2054_lu_1_2
8 inputs200 to 24 
VAC, 10 mA
(200 V, 
50 Hz)
8 points, 
1 common
Removable 
terminal 
block
1 words0.08---CJ1W-IA201
16 inputs100 to 120 
VAC, 7 mA 
(100 V, 
50 Hz)
16 points, 
1 common
Removable 
terminal 
block
1 words0.09---CJ1W-IA111

Accessories

Connectors are not included for models with connectors. Either use one of the applicable connector listed below or use an applicable Connector-Terminal Block Conversion Unit or I/O Relay Terminal. For details on wiring methods, refer to Data Sheet.

Applicable Connectors

Fujitsu Connectors for 32-input, 32-output, 64-input, 64-output, 32-input/32-output, and 16-input/16-output Units

NameCon- 
nection
RemarksApplicable UnitsModelStand- 
ards
40-pin 
Con- 
nectors
SolderedFCN-361J040-AUConnectorFujitsu Connectors: 
CJ1W-ID231(32 inputs): 1 per Unit 
CJ1W-ID261 (64 inputs): 2 per Unit 
CJ1W-OD231 (32 outputs):1 per Unit 
CJ1W-OD261 (64 outputs): 2 per Unit 
CJ1W-MD261 (32 inputs, 32 outputs): 
2 per Unit
C500-CE404---
FCN-360C040-J2Connector 
Cover
CrimpedFCN-363J040HousingC500-CE405
FCN-363J-AUContactor
FCN-360C040-J2Connector 
Cover
Pressure 
welded
FCN-367J040-AU/FC500-CE403
24-pin 
Con- 
nectors
SolderedFCN-361J024-AUConnectorFujitsu Connectors: 
CJ1W-MD231 (16 inputs, 16 outputs): 
2 per Unit
C500-CE241
FCN-360C024-J2Connector 
Cover
CrimpedFCN-363J024SocketC500-CE242
FCN-363J-AUContactor
FCN-360C024-J2Connector 
Cover
Pressure 
welded
FCN-367J024-AU/FC500-CE243

MIL Connectors for 32-input, 32-output, 64-input, 64-output, 32-input/32-output, and 16-input/16-output Units

NameCon- 
nection
RemarksApplicable UnitsModelStand- 
ards
40-pin 
Con- 
nectors
Pressure 
welded
FRC5-AO40-3TOSMIL Connectors: 
CJ1W-ID232/233 (32 inputs): 1 per Unit 
CJ1W-OD232/233/234 (32 outputs):1 per Unit 
CJ1W-ID262 (64 inputs): 2 per Unit 
CJ1W-OD262/263 (64 outputs): 2 per Unit 
CJ1W-MD263/563 (32 inputs, 32 outputs): 
2 per Unit
XG4M-4030-T---
Crimped-XG5N-401 *
20-pin 
Con- 
nectors
Pressure 
welded
FRC5-AO20-3TOSMIL Connectors: 
CJ1W-MD232/233 (16 inputs, 16 outputs): 
2 per Unit
XG4M-2030-T---
Crimped-XG5N-201 *
* Crimp Contacts are also required. Refer to Data Sheet for details.

Applicable Connector-Terminal Block Conversion Units

TypeSe- 
ries
I/ONum-
ber 
of 
poles
Wiring 
method
Ter- 
minal 
type
SizeMount-
ing
Common 
terminals
I/O UnitsModelStand-
ards
Bleeder 
resistance
Indicators
PLCsXW2ROut-
put
34Phillips 
screw 
2054_lu_4_1
M3Refer to 
Data Sheet
NoCJ1W-ID231 
CJ1W-ID261
XW2R-J34GD-C1---
CJ1W-ID232 
CJ1W-ID233 
CJ1W-ID262
XW2R-J34GD-C2
Slotted 
screw 
(rise up) 
2054_lu_4_2
M3 
(Euro-
pean 
type)
CJ1W-ID231 
CJ1W-ID261
XW2R-E34GD-C1
CJ1W-ID232 
CJ1W-ID233 
CJ1W-ID262
XW2R-E34GD-C2
Push-in 
spring 
2054_lu_4_3
ClampCJ1W-ID231 
CJ1W-ID261
XW2R-P34GD-C1
CJ1W-ID232 
CJ1W-ID233 
CJ1W-ID262
XW2R-P34GD-C2
Note: For the combination of Input Units with Connector-Terminal Block Conversion Units, refer to 2. Connecting 
          Connector-Terminal Block Conversion Units.

Applicable I/O Relay Terminals

TypeSeriesSpecificationsSize 
(hori- 
zontal 
mount-
ing)
Mount-
ing
ModelStand-ards
ClassificationPo- 
larity
Number
of 
points
Rated
ON 
cur- 
rent 
at 
con- 
tacts
Oper- 
ation 
indi- 
cators
Ter- 
minal 
block 
for 
power 
supply
wiring
Space- 
saving
G70DVerti- 
cal 
type 
G70D-
V
Out-
puts
Relay 
outputs
NPN16 
(SPST- 
NO x 16)
5A or 
3A
YesEx- 
pand- 
able
Refer to 
Data Sheet
G70D-VSOC16U, C, 
CE
MOSFET
relay 
outputs
0.3AG70D-VFOM16
Flat 
type 
G70D
Relay 
outputs
NPN
(SPST- 
NO x 8)
5AYes---G70D-SOC08---
16 
(SPST- 
NO x 16)
3AG70D-SOC16---
PNP16 
(SPST- 
NO x 16)
3AG70D-SOC16-1
MOSFET
relay 
outputs
NPN16 
(SPST- 
NO x 16)
0.3AG70D-FOM16---
PNPG70D-FOM16-1
High- 
capacity,
space- 
saving
G70ROut-
puts
Relay 
outputs
NPN
(SPST- 
NO x 8)
10AYes---G70R-SOC08---
StandardG7TCIn- 
puts
AC 
inputs
NPN16 
(SPST- 
NO x 16)
1AYes---G7TC-IA16U, C
DC 
inputs
G7TC-ID16
Out-
puts
Relay 
outputs
NPN
(SPST- 
NO x 8)
5AG7TC-OC08
16 
(SPST- 
NO x 16)
G7TC-OC16
PNP16 
(SPST- 
NO x 16)
G7TC-OC16-1---
High- 
capacity 
socket
G70A 
(Socket only)
Out-
puts
Relay 
outputs
NPN16 
(SPDT 
× 16 
possible
with 
G2R 
Relays)
10 A 
(Ter- 
mi- 
nal 
block 
allow-
able 
cur- 
rent)
No---G70A-ZOC16-3 
(Socket only) + 
Relay/SSR/ 
MOSFET 
Relay/Timer
U, C, 
CE
PNPG70A-ZOC16-4 
(Socket only) + 
Relay/SSR/ 
MOSFET 
Relay/Timer
Note: For the combination of Input Units with I/O Relay Terminal and Connecting Cables, refer to 3. Connecting I/O 
          Relay Terminals.

Dimensi Ukuran CJ1W-PA205R, CJ1W-PA205C ,CJ1W-PA202, CJ1W-PD025, CJ1W-PD022

CJ1W-PA205R

CJ1W-PA / PD Dimensions 2 CJ1W-PA205R_Dim

CJ1W-PA205C

CJ1W-PA / PD Dimensions 4 CJ1W-PA205C_Dim

CJ1W-PA202

CJ1W-PA / PD Dimensions 6 CJ1W-PA202_Dim

CJ1W-PD025

CJ1W-PA / PD Dimensions 8 CJ1W-PD025_Dim

CJ1W-PD022

CJ1W-PA / PD Dimensions 10 CJ1W-PD022_Dim

CJ1> Power Supply Units> CJ1W-PA / PD

ItemSpecifications
ModelCJ1W-PA205RCJ1W-PA205CCJ1W-PA202
Supply voltage100 to 240 V AC (wide-range), 50/60 Hz
Operating voltage and
frequency ranges
85 to 264 V AC, 47 to 63 Hz
Power consumption100 VA max.50 VA max.
Inrush current *1At 100 to 120 V AC: 15 A/8 ms max. for cold start at room temperature
At 200 to 240 V AC: 30 A/8 ms max. for cold start at room temperature
At 100 to 120 V AC:
20 A/8 ms max. for cold start at
room temperature
At 200 to 240 V AC:
40 A/8 ms max. for cold start at
room temperature
Output capacity *75.0 A, 5 V DC (including supply to CPU Unit)2.8 A, 5 V DC
(including supply to CPU Unit)
0.8 A, 24 V DC0.4 A, 24 V DC
Total: 25 W max.Total: 14 W max.
Output terminal
(service supply)
Not provided.
RUN output *2Contact configuration: SPST-NO
Switch capacity:
250 V AC, 2 A (resistive load)
120 V AC, 0.5 A (inductive load),
24 V DC, 2A (resistive load)
24 V DC, 2 A (inductive load)
Not provided.
Replacement
notification function
Not provided.With Alarm output (open-collector
output)
30 V DC max., 50 mA max.
Not provided.
Insulation resistance20 MΩ min. (at 500 V DC) between
AC external and GR terminals *3
20 MΩ min. (at 500 V DC) between
all external terminals and GR
terminal *3, and between all alarm
output terminals.
20 MΩ 1 min. (at 250 V DC)
between all alarm output terminals
and GR terminal *3.
20 MΩ min. (at 500 V DC) between
AC external and GR terminals *3
Dielectric strength *42,300 V AC 50/60 Hz for 1 min
between AC external and GR
terminals *3
Leakage current: 10 mA max.
2,300 VAC, 50/60 Hz for 1 min
between all external terminals and
GR terminal *3 and between all
alarm output terminals with a
leakage current of 10 mA max.
1,000 V AC, 50/60 Hz for 1 min
between all alarm output terminals
and GR terminal *3 with a leakage
current of 10 mA max.
2,300 V AC 50/60 Hz for 1 min
between AC external and GR
terminals *3
Leakage current: 10 mA max.
1,000 V AC, 50/60 Hz for 1 minute between DC external and GR terminals *3
Leakage current: 10 mA max.
Noise immunity2 kV on power supply line (conforming to IEC61000-4-4)
Vibration resistanceConforms to IEC60068-2-6
5 to 8.4 Hz with 3.5-mm amplitude, 8.4 to 150 Hz
Acceleration of 9.8 m/s2 for 100 min in X, Y, and Z directions (10 sweeps of 10 min each = 100 min)
Shock resistanceConforms to IEC60068-2-27
147 m/s2, 3 times in X, Y, and Z directions (100 m/s2 for Relay Output Units)
Ambient operating
temperature
0 to 55 ° C
Ambient operating
humidity
10% to 90% (with no condensation)10% to 90% (with no condensation) *510% to 90% (with no condensation)
AtmosphereMust be free from corrosive gases.
Ambient storage
temperature
- 20 to 70 ° C (excluding battery)- 20 to 75 ° C *5- 20 to 75 ° C (excluding battery)
GroundingLess than 100 Ω
EnclosureMounted in a panel.
WeightAll models are each 5 kg max.
CPU Rack dimensions90.7 to 466.7 × 90 × 65 mm (W × H × D) (not including cables)
Note:
W = a + b + 20 × n + 31 × m + 14.7
a: Power Supply Unit: PA205R and PA205C = 80; PA202 = 45; PD025 = 60; PD022=27
b: CPU Unit: CJ1-H or CJ1 = 62; CJ1M-CPU1[] = 31; CJ1M-CPU2[] = 49
The total width is given by the following: W = 156.7 + n × 20 + m × 31, where n is the number of 32-point I/O Units
or I/O Control Units and m is the number of other Units.
Safety measuresConforms to cULus and EC Directives.
Item
Power Supply Unit
Specifications
CJ1W-PD025CJ1W-PD022
Supply voltage24 VDC
Operating voltage and
frequency ranges
19.2 to 28.8 V DC21.6 to 26.4 V DC
Power consumption50 W max.35 W max.
Inrush current *1At 24 V DC: 30 A/20 ms max. for cold start
Output capacity *75.0 A, 5 V DC (including supply to CPU Unit)2.0 A, 5 V DC (including supply to CPU Unit)
0.8 A, 24 V DC0.4 A, 24 V DC
Total: 25 W max.Total: 19.6 W max.
Output terminal
(service supply)
Not provided.
RUN output *2Not provided.
Replacement
notification function
Not provided.
Insulation resistance20 MΩ min. (at 500 V DC) between DC external
and GR terminals *3
---
*6
Dielectric strength *41,000 V AC, 50/60 Hz for 1 min between DC
external and GR terminals *3
Leakage current: 10 mA max.
---
*6
Noise immunity2 kV on power supply line (conforming to IEC61000-4-4)
Vibration resistanceConforms to IEC60068-2-6
5 to 8.4 Hz with 3.5-mm amplitude, 8.4 to 150 Hz
Acceleration of 9.8 m/s2 for 100 min in X, Y, and Z directions (10 sweeps of 10 min each = 100 min)
Shock resistanceConforms to IEC60068-2-27
147 m/s2, 3 times in X, Y, and Z directions (100 m/s2 for Relay Output Units)
Ambient operating
temperature
0 to 55 ° C
Ambient operating
humidity
10% to 90% (with no condensation)
AtmosphereMust be free from corrosive gases.
Ambient storage
temperature
- 20 to 75 ° C (excluding battery)
GroundingLess than 100 Ω
EnclosureMounted in a panel.
WeightAll models are each 5 kg max.
CPU Rack dimensions90.7 to 466.7 × 90 × 65 mm (W × H × D) (not including cables)
Note:
W = a + b + 20 × n + 31 × m + 14.7
a: Power Supply Unit: PA205R and PA205C = 80; PA202 = 45; PD025 = 60; PD022=27
b: CPU Unit: CJ1-H or CJ1 = 62; CJ1M-CPU1[] = 31; CJ1M-CPU2[] = 49
The total width is given by the following: W = 156.7 + n × 20 + m × 31, where n is the number of 32-point I/O Units
or I/O Control Units and m is the number of other Units.
Safety measuresConforms to cULus and EC Directives.
*1. Disconnect the Power Supply Units LG terminal from the GR terminal when testing insulation and dielectric strength. 
       Testing the insulation and dielectric strength with the LG terminal and the GR terminals connected will damage 
       internal circuits in the CPU Unit. 
*2. Supported only when mounted to CPU Rack. 
*3. The inrush current is given for a cold start at room temperature. The inrush control circuit uses a thermistor element 
       with a low-temperature current control characteristic. If the ambient temperature is high or the PLC is hot-started, the 
       thermistor will not be sufficiently cool, and the inrush currents given in the table may be exceeded by up to twice the 
       given values. When selecting fuses or breakers for external circuits, allow sufficient margin in shut-off performance. 
*4. Maintain an ambient storage temperature of −25 to 30°C and relative humidity of 25% to 70% when storing the Unit for 
       longer than 3 months to keep the replacement notification function in optimum working condition. 
*5. Change the applied voltage gradually using the adjuster on the Tester. If the full dielectric strength voltage is applied 
       or turned OFF using the switch on the Tester, the generated impulse voltage may damage the Power Supply Unit. 
*6. CJ1W-PD022 is not insulated between the primary DC power and secondary DC power. 
*7. Internal components in the Power Supply Unit will deteriorate or be damaged if the Power Supply Unit is used for an 
       extended period of time exceeding the power supply output capacity or if the outputs are shorted.

Checking Current Consumption and Power Consumption

After selecting a Power Supply Unit based on considerations such as the power supply voltage, calculate the current and power requirements for each Rack.

Condition 1: Current Requirements

There are two voltage groups for internal power consumption: 5 V and 24 V.
Current consumption at 5 V (internal logic power supply)
Current consumption at 24 V (relay driving power supply)

Condition 2: Power Requirements

For each Rack, the upper limits are determined for the current and power that can be provided to the mounted Units. Design the system so that the total current consumption for all the mounted Units does not exceed the maximum total power or the maximum current supplied for the voltage groups shown in the following tables. 
The maximum current and total power supplied for CPU Racks and Expansion Racks according to the Power Supply Unit model are shown below. 
Note: 1. For CPU Racks, include the CPU Unit current and power consumption in the calculations. When expanding, also 
              include the current and power consumption of the I/O Control Unit in the calculations. 
           2. For Expansion Racks, include the I/O Interface Unit current and power consumption in the calculations.
Power Supply UnitsMax. current suppliedMax. total power supplied
5 V24 V (relay driving current)
CJ1W-PA205R5.0 A0.8 A25 W
CJ1W-PA205C5.0 A0.8 A25 W
CJ1W-PA2022.8 A0.4 A14 W
CJ1W-PD0255.0 A0.8 A25 W
CJ1W-PD0222.0 A0.4 A19.6 W
Conditions 1 and 2 below must be satisfied.

Condition 1: Maximum Current

(1) Total Unit current consumption at 5 V ≤ (A) value 
(2) Total Unit current consumption at 24 V ≤ (B) value

Condition 2: Maximum Power

(1) × 5 V + (2) × 24 V ≤ (C) value

Example: Calculating Total Current and Power Consumption

Example: When the Following Units are Mounted to a CJ-series CPU Rack Using a CJ1W-PA202 Power Supply Unit
Unit typeModelQuantityVoltage group
5 V24 V
CPU UnitCJ1G-CPU45H10.910 A---
I/O Control UnitCJ1W-IC10110.020 A---
Basic I/O Units
(Input Units)
CJ1W-ID21120.080 A---
CJ1W-ID23120.090 A---
Basic I/O Units
(Output Units)
CJ1W-OC20120.090 A0.048 A
Special I/O UnitCJ1W-DA04110.120 A---
CPU Bus UnitCJ1W-CLK2310.350 A---
Current consumptionTotal0.910 + 0.020 + 0.080 × 2 + 0.090 ×
2 + 0.090 × 2 + 0.120 + 0.350
0.048 A × 2
Result1.92 A ( ≤ 2.8 A)0.096 A ( ≤ 0.4 A)
Power consumptionTotal1.92 × 5 V = 9.60 W0.096 A × 24 V = 2.304 W
Result9.60 + 2.304 = 11.904 W ( ≤ 14 W)

Power Supply UNit For CJ

Equipped with the RUN output for checking the operation status, as well as the replacement notification function for easy maintenance. Lineup of five models including the AC power supply (25W).

Please refer to the overview page for features of this product.

The replacement notification function can prevent an overflow of the system due to the power lifetime. (CJ1W-PA205C only)
Power Supply Unit provides wide variations according to the system scale up to maximum 25 W.
Power Supply Unit provides wide variations according to the power supply (100 to 240 V AC/ 24 V DC) status.
The output contact during operation enables you to check the CPU operation. (CJ1W-PA205R only)
Conforming to the SEMI-F47 Standard. *
* AC input type, 200 V min. input.

International Standards

  • The standards are abbreviated as follows: U: UL, U1: UL(Class I Division 2 Products for Hazardous Locations), C: CSA, UC: cULus, UC1: cULus (Class I Division 2 Products for Hazardous Locations), CU: cUL, N: NK, L: Lloyd, and CE: EC Directives.
  • Contact your OMRON representative for further details and applicable conditions for these standards.

Power Supply Units

Product namePower 
supply 
voltage
Output capacityOptionsModelStand- 
ards
5-VDC 
output 
capacity
24-VDC 
output 
capacity
Total 
power 
con- 
sumption
24-VDC
service 
power 
supply
RUN 
output
Mainte- 
nance 
forecast 
monitor
AC 
Power 
Supply
Unit
100 to 
240 
VAC
5 A0.8 A25 WNoNoYesCJ1W-PA205CUC1, 
N, L, 
CE
YesNoCJ1W-PA205R
2.8 A0.4 A14 WNoNoCJ1W-PA202
DC 
Power 
Supply
Unit
24 
VDC
5 A0.8 A25 WNoNoCJ1W-PD025
2 A0.4 A19.6 WNoNoCJ1W-PD022UC1, 
CE
Note: This unit cannot be used with the Machine Automation Controller NJ-series.