Kontak Kami

KONTAK KAMI : Telpon : 02126071413 Hp/WhatsApp : 081212269831 Perwakilan Jakarta : Gedung LTC Glodok Lantai 1 Blok C30 No.31 Jl.Hayam Wuruk No.127 Jakarta , Indonesia

Kamis, 05 Maret 2020

Industrial Network Selection Guide ; By Selection Table & Selection Chart



Selection Table:
                            Network Type
 Item
Information System Network
Control System Network
Field Network
Motion Field Network
Ethernet
Controller LinkSYSMAC Link CompoBus/SCompoNet
MECHA-TROLINK-II
Communi-cation Type
Message Commu-nication
O
O
O
O
---
O
O
Data Link
---
O
O
---
---
---
---
Remote I/O
---
---
---
O
O
O
---
Baud Rate (Maximum Communication Speed)
100 Mbps
2Mbps
Communication Cycle: Approx. 34ms;
(Wire: 32, 2kBit + 2kWord Data Link)
2Mbps
Communication Cycle: Approx. 34ms;
(Wire: 32, 2kBit + 2kWord Data Link)
500kbps
(Communication Cycle: Approx. 5ms;
(Input: 128 Point; Output: 128 Point)
750kbps
(Communication Cycle: 1ms and below;
(Input: 128 Point; Output: 128 Point)
4 Mbps at 30 m
10Mbps
Communication Distance
2.5 km
Twisted Pair: 3km;
H-PCF Optical Cable: 20km;
GI Optical Cable: 30km
Coaxial Cable: 1km;
Optical Fiber Cable: 10km
500m
Trunk length: 500m;
Communication Cycle: 6ms and below
1.5 km with max. 2 repeaters
Maximum 50m
Maximum Number of Nodes
254
62
62
63
32
384 nodes (word type=128 nodes; bit type=256 nodes)
30
Communication Medium
Coaxial Cable (10BASE-5)
or
Twisted Pair
(100BASE-TX/
10BASE-T)
Twisted Pair
or
Optical Fiber Cable
Coaxial Cable

Optical Fiber Cable
DeviceNet Cable
2 Core VCTF Cables,
4 Core VCTF Cables,
Flat Cable
Special 4 pair flat cable, round cable (VCTF, Belden)
METCHATROLINK-II Cable
Data Link Capacity (Per Network)
---
32000CH
2966CH
---
---
---
---
Maximum I/O Point
---
---
---
32000 Points (When Using Configurator);
15000 Points (When Not Using Configurator)
256 Points
2560 Points
---
PLC Type
C200HX/HG/HE
C200HX/HG/HE;
C200HS;
C1000H/C2000H
CJ Series;C200HX/HG/HE

By Selection Chart:
Fieldbus Network Solutions
* Click on the field network name to view details.

Ethernet Connection
Enables direct connection to personal computers or information networks with open protocol: Ethernet/IP or FINS protocol.

Controller Link (Fiber Optic)
High-speed Optical LAN with a transmission rate of 2 Mbps allows easy data exchange among PLC and a wide range of FA across 30 km.

Ethernet/IP
With Ethernet as the backbone architecture, optical switches can be used to extend network of 100 Mbps with easy data sharing among PLCs.

Controller Link (Wired)
Allows high-speed, large capacity data link with cost-saving wiring, data can be shared among 62 nodes in total.

PC Link (1:1, 1:N)
Easy and low-cost communication between PLCs of limited data capacity.

DeviceNet
Open network, which connects a variety of components such as drivers, temperature controller and etc. with Smart Features built with totalization and signal indication for maintenance.

CompoNet
Next generation network is ideal for high-speed ON/OFF bus for machinery system. With communication cycle time less than 1 ms connecting up to 1.5 km

Rack PLC Series OMRON

Rack PLC Series

 Item                          Model
Appearance
CS1H / CS1G PLC
CS1D Duplex PLC
Built-in
Digital I/On.a.n.a.
Interrupt Inputsn.a.n.a.
Counter Inputsn.a.n.a.
Pulse Outputsn.a.n.a.
CPU Features / Option Boards
2 Serial Ports
Loop Control Board
Loop Control Board
Duplex CPU, Power Supply and Communications
Max. Digital I/O Points
960 - 5120
5120
Execution Time (Bit Instruction)
0.04/0.02 µs
0.02 µs
Program Memory
10 - 250 kSteps
60- 250 kSteps
Data Memory
64 - 448 kWords
128 - 448 kWords
CompactFlash Memory
Up to 64 MB
Analog I/O
Up to 80 × 8 points,
13-bit resolution or
80 × 4 points,
16-bit resolution
U, I, TC, Pt100, process I/O
Up to 75 × 8 points,
13-bit resolution or
75 × 4 points,
16-bit resolution
U, I, TC, Pt100, process I/O
Special Function Units
Temperature Control
SSI encoder input
High-speed counters (500 kHz)
Position Control
Motion Control
Process Control
Protocol Macro
RFID sensor unit
Industrial Networks
Ethernet (100 BASE-TX)
Controller Link
Serial Communication
Fieldbus Master
DeviceNet
Profibus-DP
CompoBus/S
Fieldbus I/O Link
DeviceNet
Profibus-DP

Modular PLC Series OMRON

Modular PLC Series

SYSMAC CJ2 Series

 Item                          Model
 Type
Simple Types
Standard Types
High-end Types
Flagship Types
 Models
CJ2M-CPU1[]
CJ2M-CPU3[]
CJ2H-CPU6[]CJ2H-CPU6[]-EIP
Appearance
Program Capacity
Up to 60 Ksteps
Up to 400 Ksteps
Data Memory Capacity
Up to 160 Kwords
Up to 832 Kwords
I/O Bits
2,560
Basic Instructions (LD)
40 ns
16 ns
Special instruction (MOV)
120 ns
48 ns
Floating-point decimal
instructions (SIN)
0.86 µs
0.59 µs
System overhead time
160 µs
270 µs
100 µs
200 µs
FB Program Area
Yes
(Equivalent to 20K steps.)
--
Communications Port
USB Port
Yes
Serial Port
Yes
(RS-232C)
One Serial Option Board
can be mounted
(RS-232C or RS-422A/485)
Yes
(RS-232C)
Ethernet/IP Port
--
Yes
--
Yes
Serial PLC Links
Yes
Yes
(A Serial Option Board is required)
--
High-speed Interrupt Function
--
Yes
Synchronous Unit Operation
--
Yes
(In combination with a CJ1W-NC[][]4 Position Control Unit)
Pulse I/O Modules *
Yes
(Up to two Pulse I/O Modules can be mounted)
--

*A Pulse I/O Module must be mounted for CJ2M CPU Units with unit version 2.0 or later.


SYSMAC CJ1 Series

 Item                          Model
Appearance
CJ1M PLC
CJ1G/CJ1H PLC
Built-in
Digital I/O16 n.a.
Interrupt Inputs4 n.a.
Counter Inputs2 (100 kHz) n.a.
Pulse Outputs2 (100 kHz) n.a.
CPU Features / Option Boards
• Choice of models with and without built-in I/O
• Ethernet CPU (3 models)
• Loop control CPU (4 models)
Max. Digital I/O Points
160 - 640
960 - 2560
Execution Time (Bit Instruction)
0.1 µs
0.04/0.02 µs
Program Memory
5 - 20 kSteps
10-250 kSteps
Data Memory
32 kWords
64 - 448 kWords
CompactFlash Memory
Up to 64 MB
Analog I/O
Up to 20 × 8 points
12-bit resolution
U, I, TC, Pt100
15-bit resolution
TC, Pt100, Pt1000 inputs
Up to 36 × 8 points
13-bit resolution
U, I, TC, Pt100
15-bit resolution
TC, Pt100, Pt1000 inputs
Special Function Units
Temperature Control
High-speed counters (500 kHz)
SSI encoder input
Position Control
Protocol Macro
RFID sensor Unit
Industrial Networks
Ethernet (100 BASE-TX)
Controller Link
Serial Communications
Fieldbus Master
DeviceNet
Profibus-DP
CompoBus/S
Fieldbus I/O Link
DeviceNet
Profibus-DP

Compact PLC Series OMRON

Compact PLC Series

Classification
Basic Micro Range
Advanced Micro Range
 Item         Model
Appearance
CPM1A PLC
CPM2A PLCCP1E PLCCP1L PLCCP1H PLC
Features
• Economical model
• Built-in analog setting with rotary selector
• Economical model
• Built-in analog setting with rotary selector
• With built-in RS-232C functions
• Removal Terminal Block
• Easy ladder programming with "smart input"
• Full motion control instruction for 2 × 100 kHz pulse output, and 4/6 high-speed counter for close loop control
• Optional RS-232C or RS-422/485 communication port
• Support floating point, function block programming
• Full motion control instruction for 2 × 100 kHz pulse output, and 4/6 high-speed counter for close loop control
• Optional RS-232C or RS-422/485 communication port
• Support floating point, function block programming
• Full motion control instruction for high-speed pulse output, and high-speed counter for close loop control
• Optional RS-232C or RS-422/485 communication port
Number of I/O
10-100
80-120
20-160
10-18020-320
Built-in features
Pulse output1 (2 kHz)2 (10 kHz)2 (100 kHz)
Y model: 2 (1 MHz),
2 (100 kHz)
X, XA model: 4 (100kHz)
High-speed counter input1 (5 kHz)1 (20 kHz)
E-model: 2 (10 kHz)
N-model: 2 (100 kHz)
4 (100 kHz, single phase)
2 (50 kHz, differential phase)
Interrupt input2 or 4464 or 64
Program memory
2 kWords
4 kWords
E-model: 2 kSteps
N-model: 8 kSteps
L=5 kSteps; M=10 kSteps
20 kSteps
Data memory
1 kWords
2 kWords
2 kWords / 8 kWords
10 kWords / 32 kWords
32 kWords
No. of expansion
Max. 3 units (30 I/O onwards)
Max. 3 units (20 I/O onwards)
Max. 3 units (30 I/O onwards)
CP1L-L Model: 1 unit
CP1L-M Model: 3 units
(40 I/O onwards)
Max. 7 units of CP1W expansion units; Max. 2 units of CJ1W series modules
Execution time
0.72 - 1.72 µs *
0.26 - 0.64 µs *
1.19 µs *
0.55 µs *
0.1 µs *
Built-in communications
Peripheral port
Peripheral port, RS-232C
USB port (for programming only)
Communication adapter
CPM1-CIF01 (RS-232C)
CPM1-CIF11 (RS-422C)
CP1W-CIF01 (RS-232C)
CP1W-CIF11 (RS-422C / RS-485)
CP1W-CIF12 (RS-422C / RS-485 Isolated Type)
CP1W-CIF41 (Ethernet)
Communications
Profibus-DP, DeviceNet, CompoBus/S
CompoBus/S, Ethernet
DeviceNet, CompoBus/S, Profibus-DP, Serial Gateway, Ethernet
DeviceNet, CompoNet, CompoBus/S, Profibus-DP, Protocol Macro, Ethernet, Controller Link, Ethernet IP, Serial Gateway, CANOpen
Expansion modules
8/16/20/40 I/O modules, Analog I/O (mix, analog input only or output only), Temperature Sensor Input
All CP1W I/O modules
All CP1W I/O modules, besides 2 units of CJ1W-Series CPU Bus Unit or Special I/O Units
Programming language
Ladder
Ladder Logic, Structure Text, Function Block and IL
Software
CX-Programmer in CX-ONE software package
CX-Programmer for CP1E / CX-Programmer
CX-Programmer in CX-ONE software package
Standards
UL, SA, CE, NK, LRCECE, RoHS, cUL, NK, LR